| Date |
Text |
| 2021-02-25 22:17:42 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. NO MAIN SHOWN IN PANEL, AND PANEL IS A 10 CIRCUIT |
| | PANEL. EITHER CHANGE TO A 6 CIRCUIT PANEL OR PROVIDE A |
| | MAIN BREAKER SO IS NO CAPABILITY OF HAVING MORE THAN |
| | SIX THROWS OF THE HAND. NEC 230.71A |
| | |
| | 2. VALUE LOW FOR AMOUNT OF WORK SHOWN. PROVIDE ACCURATE |
| | VALUE FOR ALL MATERIALS AND LABOR, FAILURE TO PROVIDE |
| | AN ACCURATE VALUE MAY RESULT IN VALUE BEING SET BY |
| | BUILDING OFFICAL. FBC 109.3 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |