| Plan Review Notes For Permit 21020831 |
| Permit Number |
21020831 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-03-03 11:37:05 | PROVISO: | | | | | | FLAT ROOF (BONDED INSULATION OR MEMBRANE) | | | GENERAL NOTE #12 OF PRODUCT APPROVAL SUBMITTED REQUIRES | | | THAT: "FOR BONDED INSULATION OR MEMBRANE OVER EXISTING | | | SUBSTRATES IN A RE-ROOF (TEAR OOF) OR RECOVER | | | INSTALLATION, THE EXISTING DECK OR EXISTING ROOF | | | SURFACE SHALL BE EXAMINED FOR COMPATIBILITY WITH THE | | | ADHESIVE TO BE INSTALLED. IF ANY SURFACE CONDITIONS | | | EXIST THAT BRING SYSTEM PERFORMANCE INTO QUESTION, | | | FIELD UPLIFT TESTING IN ACCORDANCE SHALL BE CONDUCTED | | | ON MOCK-UPS OF THE PROPOSED NEW ROOF ASSEMBLY. FOR | | | BONDED INSULATION OR MEMBRANE OVER EXISTING SUBSTRATES | | | IN A RECOVER INSTALLATION, THE EXISTING ROOF SYSTEM | | | SHALL BE CAPABLE OF RESISTING PROJECT DESIGN PRESSURES | | | ON ITS OWN MERIT TO THE SATISFACTION OF THE AUTHORITY | | | HAVING JURISDICTION, AS DOCUMENTED THROUGH FIELD UPLIFT | | | TESTING. FIELD UPLIFT TESTING SHALL BE IN ACCORDANCE | | | WITH ASTM E907, FM LOSS PREVENTION DATA SHEET 1-52 OR | | | TESTING APPLICATION STANDARD TS 124." | | | |
|