| 2021-02-23 12:49:44 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE ARE INDICATIONS OF FLOOR UNDERLAYMENT BUT NO |
| | SPECIFICATIONS SHEETS THAT INDICATE MEETING THE |
| | REQUIREMENTS PER NFPA' |
| | |
| | PER NFPA 101, CH 32 |
| | |
| | 30.3.3.2 INTERIOR WALL AND CEILING FINISH. INTERIOR |
| | WALL AND |
| | CEILING FINISH MATERIALS COMPLYING WITH SECTION 10.2 |
| | SHALL BE |
| | PERMITTED AS FOLLOWS: |
| | (1) EXIT ENCLOSURES ? CLASS A |
| | (2) LOBBIES AND CORRIDORS ? CLASS A OR CLASS B |
| | (3) OTHER SPACES ? CLASS A, CLASS B, OR CLASS C |
| | |
| | 30.3.3.3 INTERIOR FLOOR FINISH. |
| | 30.3.3.3.1 INTERIOR FLOOR FINISH SHALL COMPLY WITH |
| | SECTION 10.2. |
| | 30.3.3.3.2 INTERIOR FLOOR FINISH IN EXIT ENCLOSURES AND |
| | EXIT ACCESS |
| | CORRIDORS AND SPACES NOT SEPARATED FROM THEM BY WALLS |
| | COMPLYING |
| | WITH 30.3.6 SHALL BE NOT LESS THAN CLASS II. |
| | 30.3.3.3.3 INTERIOR FLOOR FINISH SHALL COMPLY WITH |
| | 10.2.7.1 OR |
| | 10.2.7.2, AS APPLICABLE |
| | |
| | |
| | 10.2.1.1 CLASSIFICATION OF INTERIOR FINISH MATERIALS |
| | SHALL BE IN |
| | ACCORDANCE WITH TESTS MADE UNDER CONDITIONS SIMULATING |
| | ACTUAL |
| | INSTALLATIONS, PROVIDED THAT THE AUTHORITY HAVING |
| | JURISDICTION IS |
| | PERMITTED TO ESTABLISH THE CLASSIFICATION OF ANY |
| | MATERIAL FOR WHICH |
| | CLASSIFICATION BY A STANDARD TEST IS NOT AVAILABLE, |
| | UNLESS OTHERWISE |
| | PROVIDED IN 10.2.1.2 OR 10.2.1.4. |
| | 10.2.1.2 THE PROVISIONS OF 10.2.1.1 SHALL NOT APPLY TO |
| | MATERIALS HAVING |
| | A TOTAL THICKNESS OF LESS THAN 1?28 IN. (0.9 MM) THAT |
| | ARE APPLIED DIRECTLY |
| | TO THE SURFACE OF WALLS AND CEILINGS WHERE BOTH OF THE |
| | FOLLOWING |
| | CONDITIONS ARE MET: |
| | (1) THE WALL OR CEILING SURFACE IS A NONCOMBUSTIBLE OR |
| | LIMITED COMBUSTIBLE |
| | MATERIAL. |
| | (2) THE MATERIALS APPLIED MEET THE REQUIREMENTS OF |
| | CLASS A INTERIOR |
| | WALL OR CEILING FINISH WHEN TESTED IN ACCORDANCE WITH |
| | 10.2.3, |
| | USING FIBER CEMENT BOARD AS THE SUBSTRATE MATERIAL. |
| | |
| | 10.2.7* INTERIOR FLOOR FINISH TESTING AND |
| | CLASSIFICATION. |
| | 10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR |
| | FINISHES SHALL |
| | COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR |
| | IGNITION |
| | CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING |
| | MATERIALS. |
| | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| | 10.2.2.2 |
| | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| | HAVE A |
| | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| | |
| | PLEASE REVIEW AND PROVIDE SPEC SHEETS. |
| | |
| | |
| | 2) THERE ARE INDICATIONS OF WALL AND VANITY REPLACEMENT |
| | AND PAINTING. |
| | |
| | ANY WORK INVOLVING FIRE SPRINKLERS/FIRE ALARM SYSTEMS |
| | OR EQUIPMENT SHALL BE DONE UNDER SEPARATE PERMITS AND |
| | SHOP DRAWINGS. |
| | |
| | FIRE SPRINKLERS AND FIRE ALARM EQUIPMENT SHALL BE |
| | PROTECTED FROM PAINTING OR DAMAGE. |
| | |
| | THE FIRE SPRINKLER/FIRE ALARM SYSTEMS SHALL BE |
| | MAINTAINED THROUGHOUT DEMO AND RECONSTRUCTION. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT AND ENSURE |
| | COMPLIANCE. |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |