Plan Review Notes
Plan Review Notes For Permit 21020804
Permit Number 21020804
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-02-22 16:46:41THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 1.1 - THE FLOOR PLAN AND DOOR SCHEDULE
 INDICATE DOORS 200 & 202 AS H.M. NONRATED DOORS.
  
 THESE DOORS ARE INDICATED WITHIN A FIRE RATED CORRIDOR
 AND SHALL REFLECTED THE REQUIRED FIRE RATING AS DOOR
 201, IN THE SAME WALL.
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  