| Plan Review Notes For Permit 21020804 |
| Permit Number |
21020804 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-02-22 16:46:41 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) SHEET A 1.1 - THE FLOOR PLAN AND DOOR SCHEDULE | | | INDICATE DOORS 200 & 202 AS H.M. NONRATED DOORS. | | | | | | THESE DOORS ARE INDICATED WITHIN A FIRE RATED CORRIDOR | | | AND SHALL REFLECTED THE REQUIRED FIRE RATING AS DOOR | | | 201, IN THE SAME WALL. | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|