2021-02-22 10:01:23WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 21020804
 W. P. B. PERMIT: 20110522
 ADD: 700 S. ROSEMARY AVE. SUITES 202 & 204
 CONT: TRM CONSTRUCTION MANAGEMENT, INC.
 TEL: 772-905-2727
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. FEB. 22ND / 2021
 ACTION: DENIED
  
 1A) SHEET A1.1.1SHOWS THE WORK ON BOTH THE 1ST FLOOR
 AREA AS WELL AS THE 2ND FLOOR AREA BACK AT THE EXIT
 PASSAGEWAY.
 THE PLANS CALL IT A SERVICE CORRIDOR, BUT THE CORRIDOR
 SHOULD BE NAMED AN EXIT PASSAGEWAY SINCE IT IS THE BACK
 EXIT FROM MANY OF THE TENANT SPACES. SEE 2017 FBC-B
 SECTION 402.8.6.1.
  
 1B) THE DOOR SCHEDULE SHOWS THE DOORS BEING IDENTIFIED
 FOR BOTH FLOORS 1ST AND 2ND FLOOR. ALL NEW EXIT DOORS
 THAT LED FROM A TENANT SPACE BOTH 1ST FLOOR AND 2ND
 FLOOR 102,103,200 & 202 ALL SHOW A 90 MINUTE FIRE
 RATING AS PER REQUIRED UNDER SECTION 402.8.6.1.
 WHAT THE DOOR SCHEDULE FAILS TO SHOW A FIRE RATING ON
 DOORS IDENTIFIED AS 200 & 202 CLOSET/ STORAGE OR
 SERVICE AREA DOORS SUCH AS ELECTRICAL ROOMS, MECHANICAL
 ROOMS OR ACCESS ROOM TO ROOF. THE DOOR SCHEDULE DOES
 NOT SHOW A FIRE RATING FOR THESE DOORS IN ACCORDANCE
 WITH THE 2017 FBC-B SECTION 402.8.7 SERVICE AREAS
 FRONTING ON AN EXIT PASSAGEWAY. EXIT PASSAGEWAYS ARE
 SEPARATED FROM SUCH ROOMS WITH NOT LESS THAN 1-HOUR
 FIRE-BARRIER CONSTRUCTED IN ACCORDANCE WITH 707.THE
 FIRE PROTECTION RATING OF OPENINGS IN FIRE BARRIERS
 SHALL NOT BE LESS THAN 1 HOUR.
  
 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER