| 2021-05-20 17:41:21 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21050266 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE REFERENCE THE 2020 FBC. | | | | | | 2) PLEASE SHOW THE RETURN AIR PATH FROM ALL AREAS THAT | | | HAVE A DOOR INTO THE HABITABLE ROOMS. FBC RES M1602.3 | | | | | | 3) PLEASE SHOW THE CONDENSATION LINES AND THE | | | TERMINATION LOCATION FOR EACH UNIT. FBC RES M1411.3 | | | | | | 4) PLEASE INDICATE ON THE DRAWING IF THE KITCHEN HOOD | | | IS DUCTED TO EXTERIOR AND THE CFM?S FBC 107.2.1 | | | | | | 5) PLEASE PROVIDE AN EXHAUST FAN FOR THE MASTER BATH | | | SHOWER AREA. FBC RES DEFINITION OF A BATHROOM AND FBC | | | RES 303.3 | | | | | | 6) PLEASE SHOW THE TERMINATION LOCATION FOR THE EXHAUST | | | DUCT FOR BATH-2 AND THE FAN ADDED IN THE MASTER BATH. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|