| 2021-02-26 10:01:59 | PLAN REVIEW / BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER PX3169 / 1&2 FAMILY SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | 2017 NEC | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | | | | NOTICE: FLAT ROOF | | | DESIGN PRESSURES PER FBC TABLE R301.2(2) FOR A 1-STORY | | | STRUCTURE WITH EXPOSURE B IS -89.4PSF FOR ZONE 3. | | | MAXIMUM ALLOWABLE DESIGN PRESSURE FOR PROPOSED SYSTEM | | | W-60 IS -67.5. | | | | | | 1. PROVIDE ENHANCED FASTENER DENSITIES FOR ZONES 2 AND | | | 3 PER NOTES 5.7.2, PAGE 4 OF 5 OF THE EVALUATION REPORT | | | AND NOTE #9, APPENDIX 1, PAGE 2 OF 94. CALCULATIONS | | | SHALL BE PREPARED BY A DESIGN PROFESSIONAL. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 2. PROVIDE THE FLORIDA STATE PRODUCT APPROVAL COVER | | | PAGES FOR PRODUCT APPROVALS FL1654-R27 AND FL5968-R11. | | | THE COVER PAGE SHOWS THE APPROVAL NUMBER, CODE VERSION, | | | AND STATUS; FBC R 301. | | | (MIAMI DADE NOAS DO NOT REQUIRE A COVER PAGE). | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
|