| 2021-03-05 17:18:13 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21020790 |
| | 3/5/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE DEMOLITION PLANS SHOWING THE EXISTING |
| | AND NEW FLOOR PLAN- SECTION 107.2.1 WPB. |
| | |
| | 2) SHEET MP-1: PROVIDE SANITARY DRAINAGE AND WATER |
| | SUPPLY ISOMETRIC DRAWINGS FOR THE KITCHEN- SECTION |
| | 107.3.5.1.3 WPB. |
| | |
| | 3) MP-1: SHOW THE REQUIRED 1.4 IN. PER FT. SLOPE IN THE |
| | DRAIN DETAIL, AND CORRECT THE CODE SECTION- SECTION |
| | 421.5.2 FBC P. |
| | |
| | 4) MP-1: ADD PLUMBING NOTES FOR TBD SHOWER VALVE AND |
| | BATHTUB FAUCET. |
| | 412.3 INDIVIDUAL SHOWER VALVES. INDIVIDUAL SHOWER AND |
| | TUB-SHOWER COMBINATION VALVES SHALL BE |
| | BALANCED-PRESSURE, THERMOSTATIC OR COMBINATION |
| | BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO |
| | THE REQUIREMENTS OF ASSE 1016/ASME A112.1016/CSA |
| | B125.16 OR ASME A112.18.1/CSA B125.1 AND SHALL BE |
| | INSTALLED AT THE POINT OF USE. SHOWER AND TUB-SHOWER |
| | COMBINATION VALVES REQUIRED BY THIS SECTION SHALL BE |
| | EQUIPPED WITH A MEANS TO LIMIT THE MAXIMUM SETTING OF |
| | THE VALVE TO 120 DEGREES F, WHICH SHALL BE FIELD |
| | ADJUSTED IN ACCORDANCE WITH THE MANUFACTURER'S |
| | INSTRUCTIONS. IN-LINE THERMOSTATIC VALVES SHALL NOT BE |
| | UTILIZED FOR COMPLIANCE WITH THIS SECTION. |
| | 412.5 BATHTUB AND WHIRLPOOL BATHTUB VALVES. THE HOT |
| | WATER SUPPLIED TO BATHTUBS AND WHIRLPOOL BATHTUBS SHALL |
| | BE LIMITED TO A MAXIMUM TEMPERATURE OF 120 DEGREES F BY |
| | A WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO |
| | ASSE 1070 OR CSA B125.3, EXCEPT WHERE SUCH PROTECTION |
| | IS OTHERWISE PROVIDED BY A COMBINATION TUB/SHOWER VALVE |
| | IN ACCORDANCE WITH SECTION 412.3. |
| | |
| | 5) MP-1: PROVIDE A FIRESTOPPING ASSEMBLY DETAIL FOR |
| | PIPES PENETRATING THE EXISTING SLAB- SECTIONS 315.1 FBC |
| | P, AND 714.4.1.2 FBC B. |
| | |
| | 6) A-1: PROVIDE THE WIDTH OF THE NEW SHOWER DOOR IN THE |
| | MASTER BATHROOM- SECTION 421.4.2 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |