Plan Review Notes
Plan Review Notes For Permit 21020790
Permit Number 21020790
Review Stop P
Sequence Number 1
Notes
Date Text
2021-03-05 17:18:131ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21020790
 3/5/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE DEMOLITION PLANS SHOWING THE EXISTING
 AND NEW FLOOR PLAN- SECTION 107.2.1 WPB.
  
 2) SHEET MP-1: PROVIDE SANITARY DRAINAGE AND WATER
 SUPPLY ISOMETRIC DRAWINGS FOR THE KITCHEN- SECTION
 107.3.5.1.3 WPB.
  
 3) MP-1: SHOW THE REQUIRED 1.4 IN. PER FT. SLOPE IN THE
 DRAIN DETAIL, AND CORRECT THE CODE SECTION- SECTION
 421.5.2 FBC P.
  
 4) MP-1: ADD PLUMBING NOTES FOR TBD SHOWER VALVE AND
 BATHTUB FAUCET.
 412.3 INDIVIDUAL SHOWER VALVES. INDIVIDUAL SHOWER AND
 TUB-SHOWER COMBINATION VALVES SHALL BE
 BALANCED-PRESSURE, THERMOSTATIC OR COMBINATION
 BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO
 THE REQUIREMENTS OF ASSE 1016/ASME A112.1016/CSA
 B125.16 OR ASME A112.18.1/CSA B125.1 AND SHALL BE
 INSTALLED AT THE POINT OF USE. SHOWER AND TUB-SHOWER
 COMBINATION VALVES REQUIRED BY THIS SECTION SHALL BE
 EQUIPPED WITH A MEANS TO LIMIT THE MAXIMUM SETTING OF
 THE VALVE TO 120 DEGREES F, WHICH SHALL BE FIELD
 ADJUSTED IN ACCORDANCE WITH THE MANUFACTURER'S
 INSTRUCTIONS. IN-LINE THERMOSTATIC VALVES SHALL NOT BE
 UTILIZED FOR COMPLIANCE WITH THIS SECTION.
 412.5 BATHTUB AND WHIRLPOOL BATHTUB VALVES. THE HOT
 WATER SUPPLIED TO BATHTUBS AND WHIRLPOOL BATHTUBS SHALL
 BE LIMITED TO A MAXIMUM TEMPERATURE OF 120 DEGREES F BY
 A WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO
 ASSE 1070 OR CSA B125.3, EXCEPT WHERE SUCH PROTECTION
 IS OTHERWISE PROVIDED BY A COMBINATION TUB/SHOWER VALVE
 IN ACCORDANCE WITH SECTION 412.3.
  
 5) MP-1: PROVIDE A FIRESTOPPING ASSEMBLY DETAIL FOR
 PIPES PENETRATING THE EXISTING SLAB- SECTIONS 315.1 FBC
 P, AND 714.4.1.2 FBC B.
  
 6) A-1: PROVIDE THE WIDTH OF THE NEW SHOWER DOOR IN THE
 MASTER BATHROOM- SECTION 421.4.2 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  