2021-02-20 21:42:33ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE CLEAR ELECTRICAL DRAWING OF WHERE REQUIRED
 ELECTRICAL WORK IS LOCATED IN HOME. FBC 107.2.1
  
 2. PROVIDE LOAD CACLUATION OF EXISTING SERVICE TO
 INCLUDE BOTH NEW AND EXISTING LOADS. NEC 220 FBC
 107.2.1
  
 END OF COMMENTS.
  