2021-03-01 07:43:34PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) INDICATE ON THE GENERATOR LOCATION DRAWING THAT THE
 GENERATOR EXHAUST WILL BE LOCATED 10 FEET FROM ANY
 OPENINGS INTO A STRUCTURE. FBC-R303.5.1 INTAKE
 OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE
 OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048
 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS
 VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS,
 PARKING LOTS AND LOADING DOCKS.
  
 2) THE GENERATOR IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA AND IS REQUIRED TO BE ELEVATED TO OR ABOVE THE DFE
 OR THE FINISH FLOOR ELEVATION OF THE HABITABLE AREA OF
 THE DWELLING. FBC-R322
  