| Date |
Text |
| 2021-02-10 10:04:16 | 02/10/21 1ST REVIEW PLUMBING REVIEW**DENIED** WITH |
| | COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. PLEASE SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR |
| | THE MAXIMUM SYSTEM FLOW. THE PUMP'S MAXIMUM FLOW FROM |
| | ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN |
| | DETERMINING THE MAXIMUM SYSTEM FLOW RATE PER |
| | ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 |
| | EDITION ADDRESSES THE FLOW RATE IN GALLONS PER MINUTE |
| | (GPM). IT REQUIRES THAT THE MAXIMUM SYSTEM FLOW RATE |
| | DOES NOT EXCEED THE LISTED MAXIMUM FLOW RATE OF THE |
| | SUCTION OUTLET FITTING ASSEMBLY (DRAIN COVER). THE TDH |
| | CALCULATIONS MUST INCLUDE ALL THE SYSTEM COMPONENTS, |
| | INCLUDING SUCTION AND RETURN PIPING, FITTINGS, VALVES, |
| | HEAT PUMP, FILTER, AND CHLORINATOR. ALL SYSTEM |
| | COMPONENTS EXCEPT THE PUMP. |
| | |
| | 2. PLEASE SUBMIT SPECIFICATIONS FOR THE HEAT PUMP AND |
| | CHLORINE GENERATOR PER THE WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | |
| | 3. HEAT PUMP POOL HEATERS SHALL HAVE A MINIMUM COP OF |
| | 4.0 WHEN TESTED IN ACCORDANCE WITH AHRI 1160, TABLE 2, |
| | STANDARD RATING CONDITIONS ? LOW AIR TEMPERATURE. A |
| | TEST REPORT FROM AN INDEPENDENT LABORATORY IS REQUIRED |
| | TO VERIFY PROCEDURE COMPLIANCE PER THE 2017 FBC-ENERGY |
| | ? SEC. R 403.10.5. |
| | |
| | 4. TWO SEPARATE BACKFLOW DEVICES ARE REQUIRED; ONE IS A |
| | CONTAINMENT, A REDUCED PRINCIPAL ZONE BACKFLOW BY A |
| | LICENSED CONTRACTOR. IT WILL NEED TO BE AT THE WATER |
| | METER DUE TO POOL FILL, AND IT WILL NEED TO BE |
| | CERTIFIED BY THE CITY OF WEST PALM BEACH UTILITIES |
| | DEPARTMENT. THE SECOND IS AN ISOLATION PRESSURE VACUUM |
| | BREAKER BACKFLOW FOR POOL FILL IS REQUIRED, AND IT WILL |
| | BE REQUIRED TO BE CERTIFIED BY A LICENSED BACKFLOW |
| | CONTRACTOR. A REPORT MUST BE FILLED OUT AND BE WITH THE |
| | PERMIT AT FINAL AS THE INSPECTION MUST TAKE FOR CITY |
| | RECORDS. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |