Plan Review Notes
Plan Review Notes For Permit 21020448
Permit Number 21020448
Review Stop P
Sequence Number 1
Notes
Date Text
2021-02-10 10:04:1602/10/21 1ST REVIEW PLUMBING REVIEW**DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR
 THE MAXIMUM SYSTEM FLOW. THE PUMP'S MAXIMUM FLOW FROM
 ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN
 DETERMINING THE MAXIMUM SYSTEM FLOW RATE PER
 ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013
 EDITION ADDRESSES THE FLOW RATE IN GALLONS PER MINUTE
 (GPM). IT REQUIRES THAT THE MAXIMUM SYSTEM FLOW RATE
 DOES NOT EXCEED THE LISTED MAXIMUM FLOW RATE OF THE
 SUCTION OUTLET FITTING ASSEMBLY (DRAIN COVER). THE TDH
 CALCULATIONS MUST INCLUDE ALL THE SYSTEM COMPONENTS,
 INCLUDING SUCTION AND RETURN PIPING, FITTINGS, VALVES,
 HEAT PUMP, FILTER, AND CHLORINATOR. ALL SYSTEM
 COMPONENTS EXCEPT THE PUMP.
  
 2. PLEASE SUBMIT SPECIFICATIONS FOR THE HEAT PUMP AND
 CHLORINE GENERATOR PER THE WPB AMEND. TO FBC SEC.
 107.2.1.
  
 3. HEAT PUMP POOL HEATERS SHALL HAVE A MINIMUM COP OF
 4.0 WHEN TESTED IN ACCORDANCE WITH AHRI 1160, TABLE 2,
 STANDARD RATING CONDITIONS ? LOW AIR TEMPERATURE. A
 TEST REPORT FROM AN INDEPENDENT LABORATORY IS REQUIRED
 TO VERIFY PROCEDURE COMPLIANCE PER THE 2017 FBC-ENERGY
 ? SEC. R 403.10.5.
  
 4. TWO SEPARATE BACKFLOW DEVICES ARE REQUIRED; ONE IS A
 CONTAINMENT, A REDUCED PRINCIPAL ZONE BACKFLOW BY A
 LICENSED CONTRACTOR. IT WILL NEED TO BE AT THE WATER
 METER DUE TO POOL FILL, AND IT WILL NEED TO BE
 CERTIFIED BY THE CITY OF WEST PALM BEACH UTILITIES
 DEPARTMENT. THE SECOND IS AN ISOLATION PRESSURE VACUUM
 BREAKER BACKFLOW FOR POOL FILL IS REQUIRED, AND IT WILL
 BE REQUIRED TO BE CERTIFIED BY A LICENSED BACKFLOW
 CONTRACTOR. A REPORT MUST BE FILLED OUT AND BE WITH THE
 PERMIT AT FINAL AS THE INSPECTION MUST TAKE FOR CITY
 RECORDS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved