| 2021-05-13 09:20:25 | 2ND REVIEW FBC-2020 RES. FUE GAS |
| | PERMIT- 21020420 |
| | 5/13/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1)) THE SUBMITTED MANUFACTURER'S SPECIFICATIONS FOR THE |
| | AFPO-C ARTISAN FIRE PIZZA OVEN AND THE K750HB HYBRID |
| | FIRE GRILL EACH HAVE THIS STATEMENT PRINTED ON THEIR |
| | FRONT PAGES- "NEVER PLACE (OVEN) (GRILL) UNDERNEATH AN |
| | OVERHEAD COMBUSTIBLE STRUCTURE". THE ARCHITECTURAL PLAN |
| | APPEARS TO INDICATE AN EXISTING WOOD FRAME ROOF OR |
| | TRELLIS ABOVE IT. THE INSTALLATIONS ARE DENIED. |
| | |
| | 2) THE SUBMITTAL FOR THE GOVERNOR GAS REGULATORS |
| | INDICATES OUTLET PRESSURES OF 8- 11 IN. W.C., HOWEVER |
| | THE NEW OVEN AND GRILL HAVE INPUT PRESSURES OF 7 IN. |
| | W.C. PLEASE SPECIFY THE CORRECT REGULATORS FOR THE |
| | INSTALLATIONS- SECTION G2421.2 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |