| 2021-03-15 14:08:20 | 1ST REVIEW FBC-2020 RES. |
| | PERMIT- 21020406 |
| | 3/15/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE A UG LP TANK HOLD-DOWN DETAIL SHOWING HOW |
| | THE TANK WILL BE ANCHORED TO PREVENT FLOTATION, |
| | COLLAPSE, OR LATERAL MOVEMENT- SECTION 6.6.1.6 NFPA-58. |
| | PLEASE INCLUDE A FRONT AND SIDE ELEVATION VIEW THAT |
| | SHOWS THE BURIAL DEPTH, ANCHORING BASE MATERIAL, AND |
| | THE TYPES, SIZES, AND NUMBERS OF ANCHORS, CABLES OR |
| | STRAPS, AND THE TYPE OF PROTECTIVE SLEEVES FOR THE |
| | CABLES OR STRAPS. |
| | |
| | 2) THE UG LP TANK SHALL BE PROTECTED AGAINST CORROSION |
| | BY INSTALLATION OF A CATHODIC PROTECTION SYSTEM |
| | CONSISTING OF A SACRIFICIAL ANODE OR AN IMPRESSED |
| | CURRENT ANODE PER SECTIONS 5.2.1.11 & 6.6.6.1(I) NFPA |
| | 58. INDICATE THE TYPE OF PROTECTION AND SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS- SECTION 6.17.1. |
| | |
| | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FIRE |
| | BOWLS- SECTION G2454.1 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |