| 2021-04-01 14:38:58 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC SEVENTH EDITION (2020) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE PRODUCT APPROVALS THAT WERE SUBMITTED DO NOT |
| | MATCH THE IMPACT RATED ONES SPECIFIED BY THE DESIGNER |
| | OF RECORD IN THE WINDOW AND DOOR SCHEDULES ON THE |
| | PLANS. THE ROOFING PRODUCT APPROVALS ARE ALSO |
| | DIFFERENT. SUBMIT THE ONES THAT ARE APPROVED BY THE |
| | DESIGNER OF RECORD AND LISTED ON THE PLANS. CIRCLE OR |
| | HI-LIGHT THE SPECIFIC ITEMS AND DESIGN PRESSURES IN THE |
| | PRODUCT APPROVALS. FBC AMENDMENTS 107.3.4 - PROVIDE TWO |
| | SETS OF PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE |
| | REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE |
| | 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE |
| | PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING |
| | INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES |
| | FOR EACH OF THE DIFFERENT ROOFING MATERIALS, WINDOW |
| | (GLASS TYPES), STRUCTURAL MULLIONS AND EXTERIOR DOOR |
| | TYPES. ONLY ONE SET IS REQUIRED TO BE UPLOADED FOR |
| | ELECTRONICALLY SUBMITTED DOCUMENTS. |
| | |
| | 2) THE SURFACE WATER DRAINAGE PLAN DOES NOT ADEQUATELY |
| | SHOW THAT THE SURFACE WATER WILL BE CONTAINED ON THE |
| | LOT AND HAS A 6 INCH FALL AWAY FROM THE BUILDING. |
| | PROVIDE A MORE DETAILED DRAINAGE PLAN. |
| | FBC-R401.3 DRAINAGE. SURFACE DRAINAGE SHALL BE DIVERTED |
| | TO A STORM SEWER CONVEYANCE OR OTHER APPROVED POINT OF |
| | COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS SHALL BE |
| | GRADED TO DRAIN SURFACE WATER AWAY FROM FOUNDATION |
| | WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 INCHES (152 |
| | MM) WITHIN THE FIRST 10 FEET (3048 MM). EXCEPTION: |
| | WHERE LOT LINES, WALLS, SLOPES OR OTHER PHYSICAL |
| | BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL WITHIN 10 |
| | FEET (3048 MM), DRAINS OR SWALES SHALL BE CONSTRUCTED |
| | TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE. IMPERVIOUS |
| | SURFACES WITHIN 10 FEET (3048 MM) OF THE BUILDING |
| | FOUNDATION SHALL BE SLOPED A MINIMUM OF 2 PERCENT AWAY |
| | FROM THE BUILDING. |
| | |
| | |
| | |
| | |
| | |
| | |