| 2021-03-09 13:29:27 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SEVENTH EDITION (2020) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) ON PAGE 004, 3-4 THE FOUNDATION PLAN IS MISSING SOME |
| | OF THE FILLED CELLS AT THE EAST WALL OF THE DINING |
| | ROOM. FBC 107.2.1 |
| | |
| | 2) THE PRODUCT APPROVALS FOR THE WINDOWS AND DOORS HAVE |
| | MULTIPLE TYPES OF WINDOWS AND DOORS LISTED IN THE |
| | PRODUCT APPROVALS WITH DIFFERENT DESIGN PRESSURES, ETC. |
| | CIRCLE OR HI-LIGHT THE ITEMS THAT ARE SPECIFIC TO THIS |
| | PROJECT. FBC 107.2.1 |
| | |
| | 3) THE DESIGNER OF RECORD IS REQUIRED TO REVIEW AND |
| | APPROVE THE PRODUCT APPROVALS IN WRITING. FBC 107.3.4 - |
| | PROVIDE TWO SETS OF PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001 PER |
| | FLORIDA STATUTE 553.842 (5) THAT HAVE BEEN REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD. PROVIDE |
| | TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA NUMBERS |
| | INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN |
| | PRESSURES FOR EACH OF THE DIFFERENT ROOFING MATERIALS, |
| | WINDOW (GLASS TYPES), STRUCTURAL MULLIONS AND EXTERIOR |
| | DOOR TYPES. THESE ITEMS CAN BE DEFERRED IF REQUESTED, |
| | HOWEVER, THE DOCUMENTS MUST BE SUBMITTED AND APPROVED |
| | BY THE BUILDING DEPARTMENT BEFORE THEY CAN BE |
| | INSTALLED. ONLY ONE SET IS REQUIRED TO BE UPLOADED FOR |
| | ELECTRONICALLY SUBMITTED DOCUMENTS. |
| | |
| | 4) THE PRODUCT APPROVALS FOR THE WINDOWS AND SLIDING |
| | GLASS DOOR ARE NOT IMPACT RATED. SUBMIT A KEY PLAN, AN |
| | INSTALLATION SCHEDULE AND PRODUCT APPROVALS FOR THE |
| | REQUIRED IMPACT PROTECTION DEVICES. FBC 107.2.1 |
| | |
| | 5) PROVIDE A SURFACE WATER DRAINAGE PLAN FOR THE SITE |
| | THAT SHOWS COMPLIANCE WITH FBC-R401.3 DRAINAGE. SURFACE |
| | DRAINAGE SHALL BE DIVERTED TO A STORM SEWER CONVEYANCE |
| | OR OTHER APPROVED POINT OF COLLECTION THAT DOES NOT |
| | CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN SURFACE |
| | WATER AWAY FROM FOUNDATION WALLS. THE GRADE SHALL FALL |
| | A MINIMUM OF 6 INCHES (152 MM) WITHIN THE FIRST 10 FEET |
| | (3048 MM). |
| | EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER |
| | PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL |
| | WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE |
| | CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE. |
| | IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE |
| | BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2 |
| | PERCENT AWAY FROM THE BUILDING. |
| | |
| | |
| | |
| | |