| 2021-03-10 08:00:27 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | BUILDING REVIEW DENIED: | | | | | | 1) FBC B 303.4/FBC B 1010.1.10; AS THIS IS AN A-3 | | | (GROUP A ASSEMBLY). THEREFORE PANIC HARDWARE IS | | | REQUIRED ON THE DOORS. | | | | | | 2) FBC B 1609: PLEASE PROVIDE THE PRODUCT APPROVALS FOR | | | THE PROPOSED REPLACEMENT DOORS. THE PRODUCT APPROVALS | | | NEED TO SHOW IMPACT RESISTANCE, WINDLOAD PRESSURE | | | CAPACITY, PANIC HARDWARE & THE CONNECTION OPTIONS. | | | | | | | | | |
|