2021-03-16 14:08:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21020368 360 S ROSEMARY AVE
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 GENERAL: PER WPB FBC 107.2.1, CLOUD AND TAG ALL
 REVISIONS ON THE PLANS.
  
 1.RE: MEPFPT
 A.P1.01 ASI#1/REV 4; UPDATED ELEVATOR SUMP PUMPS AND
 SIZES. PLAN SHOWS COLLECTION SYSTEMS FROM SUMP PUMPS TO
 A SANITARY CONNECTION. PIPING IS NOT SIZED. PER WPB FBC
 107.2.1, PROVIDE 1) SIZING OF PIPING 2) A DETAIL OF
 CONNECTION(S) TO SANITARY SYSTEM. CLOUD AND TAG.
 B.P1.02 ASI#1/REV 7; UPDATED ELEVATOR SUMP PUMPS AND
 SIZES. NOT ADDRESSED. PER WPB FBC 107.2.1, CLARIFY.
 C.P1.03 ASI#1/REV 4; UPDATED ELEVATOR SUMP PUMPS AND
 SIZES. NOT ADDRESSED. PER WPB FBC 107.2.1, CLARIFY.
 E.P-1.01 ASI#2/REV 5; A) REVISED STORM SIZE TO 12 INCH
 FOR BOTH HIGH AND LOW ZONE. NOTED HIGH ZONE IS 12 INCH,
 BUT LOW ZONE IS 8 INCH. PER WPB FBC 107.2.1, CLARIFY.
 PER WPB FBC 107.2.1, IDENTIFY PIPING SECTIONS WITH REV
 5 TAG AND CLOUD. B) ADDED CIVIL REFERENCE TO PIPING IN
 LOADING DOCK AND SKETCH OUT PIPING ON PLANS. CIVIL
 REFERENCE NOTED. SKETCHED PIPE NOTED. PLUMBING DRAWINGS
 P4.01, P1.01 AND P9.02, SHOW PIPING THAT IS ALSO SHOWN
 ON CIVIL DRAWING C5.00. CLEARLY INDICATE ON THE PLANS
 WHICH IS PART OF THE BUILDING SYSTEM AND WHICH IS PART
 OF THE SITE WORK. PER WPB FBC 107.2.1, IDENTIFY PIPING
 CONNECTION WITH REV 5 TAG AND CLOUD. C) REVISED
 PLUMBING WORK OUTSIDE OF STAIR TOWER #2. PER WPB FBC
 107.2.1, IDENTIFY PIPING WITH REV 5 TAG AND CLOUD. I
 ONLY SEE REV 3 NOTED IN THIS AREA. PER WPB FBC 107.2.1,
 IDENTIFY PIPING CONNECTION WITH REV 5 TAG AND CLOUD. D)
 ADDED CD PIPING CONNECTION OUTSIDE ELEVATOR LOBBY. DO
 NOT SEE ADDED CONNECTION. PER WPB FBC 107.2.1, IDENTIFY
 PIPING CONNECTION WITH REV 5 TAG AND CLOUD.
 F.P-1.02 ASI#2/REV 5; ASI#2/REV 5 NOT NOTED ON PLAN.
 ADD REV 5 TO PLAN AND A) REVISED PLUMBING WORK OUTSIDE
 OF STAIR TOWER #2. PER WPB FBC 107.2.1, IDENTIFY PIPING
 WITH REV 5 TAG AND CLOUD. B) ADDED CD PIPING CONNECTION
 OUTSIDE ELEVATOR LOBBY. DO NOT SEE ADDED CONNECTION.
 PER WPB FBC 107.2.1, IDENTIFY PIPING CONNECTION WITH
 REV 5 TAG.
 G.P-1.03 ASI#2/REV 2; A) REVISED PLUMBING WORK OUTSIDE
 OF STAIR TOWER #2. PER WPB FBC 107.2.1, IDENTIFY PIPING
 WITH REV 2 TAG. B) ADDED CD PIPING CONNECTION OUTSIDE
 ELEVATOR LOBBY. DO NOT SEE ADDED CONNECTION. PER WPB
 FBC 107.2.1, IDENTIFY PIPING CONNECTION WITH REV 2 TAG
 AND CLOUD.
 H.P4.01A ASI#2/REV 8; A) REVISED STORM SIZE TO 12 INCH
 FOR BOTH HIGH AND LOW ZONE. B) REVISED PLUMBING WORK
 OUTSIDE OF STAIR TOWER #2. PER WPB FBC 107.2.1,
 IDENTIFY PIPING WITH REV 2 TAG AND CLOUD. C) ADDED CD
 PIPING CONNECTION OUTSIDE ELEVATOR LOBBY. DO NOT SEE
 ADDED CONNECTION. PER WPB FBC 107.2.1, IDENTIFY PIPING
 CONNECTION WITH REV 2 TAG AND CLOUD.
 I.P4.01B ASI#2/REV 8; REVISED FUEL PIPE ROUTING.
 ASI#2/REV 8 IS NOT NOTED ON THE PLAN. PER WPB FBC
 107.2.1, ADD TO PLAN AND IDENTIFY PIPING WITH REV 8 TAG
 AND CLOUD OR MATCH UP WITH ASI#2 REV 5 NOTED ON PLANS.
 J.P4.02A ASI#2/REV 8; ASI#2/REV 8 IS NOT NOTED ON THE
 PLAN. PER WPB FBC 107.2.1, ADD TO PLAN AND A) REVISED
 PLUMBING WORK OUTSIDE OF STAIR TOWER #2. PER WPB FBC
 107.2.1, IDENTIFY PIPING WITH REV 8 TAG AND CLOUD. B)
 ADDED CD PIPING CONNECTION OUTSIDE ELEVATOR LOBBY. DO
 NOT SEE ADDED CONNECTION. PER WPB FBC 107.2.1, IDENTIFY
 PIPING CONNECTION WITH REV 8 TAG AND CLOUD. C) REVISE
 REVISION SCHEDULE TO REFLECT OR MATCH UP WITH ASI#2 REV
 5 NOTED ON PLANS, CLOUD AND TAG.
 K.P4.03A ASI#2/REV 5; ASI#2/REV 5 IS NOT NOTED ON THE
 PLAN. PER WPB FBC 107.2.1, ADD TO PLAN AND A) REVISED
 PLUMBING WORK OUTSIDE OF STAIR TOWER #2. PER WPB FBC
 107.2.1, IDENTIFY PIPING WITH REV 5 TAG AND CLOUD. B)
 ADDED CD PIPING CONNECTION OUTSIDE ELEVATOR LOBBY. DO
 NOT SEE ADDED CONNECTION. PER WPB FBC 107.2.1, IDENTIFY
 PIPING CONNECTION WITH REV 5 TAG AND CLOUD. C) REVISE
 REVISION SCHEDULE TO REFLECT OR MATCH UP WITH ASI#2 REV
 4 NOTED ON PLANS, CLOUD AND TAG.
 L.P4.04A ASI#2/REV 5; ASI#2/REV 5 IS NOT NOTED ON THE
 PLAN. PER WPB FBC 107.2.1, ADD TO PLAN AND A) REVISED
 PLUMBING WORK OUTSIDE OF STAIR TOWER #2. PER WPB FBC
 107.2.1, IDENTIFY PIPING WITH REV 5 TAG AND CLOUD. B)
 ADDED CD PIPING CONNECTION OUTSIDE ELEVATOR LOBBY. DO
 NOT SEE ADDED CONNECTION. PER WPB FBC 107.2.1, IDENTIFY
 PIPING CONNECTION WITH REV 5 TAG AND CLOUD. C) REVISE
 REVISION SCHEDULE TO REFLECT OR MATCH UP WITH ASI#2 REV
 4 NOTED ON PLANS, CLOUD AND TAG.
 M.P4.05A ASI#2/REV 4; A) REVISED PLUMBING WORK OUTSIDE
 OF STAIR TOWER #2. PER WPB FBC 107.2.1, IDENTIFY PIPING
 WITH REV 4 TAG AND CLOUD. B) ADDED CD PIPING CONNECTION
 OUTSIDE ELEVATOR LOBBY. DO NOT SEE ADDED CONNECTION.
 PER WPB FBC 107.2.1, IDENTIFY PIPING CONNECTION WITH
 REV 4 TAG AND CLOUD.
 N.P4.06A ASI#2/REV 5; A) REVISED PLUMBING WORK OUTSIDE
 OF STAIR TOWER #2. PER WPB FBC 107.2.1, IDENTIFY PIPING
 WITH REV 5 TAG AND CLOUD. B) ADDED CD PIPING CONNECTION
 OUTSIDE ELEVATOR LOBBY. DO NOT SEE ADDED CONNECTION.
 PER WPB FBC 107.2.1, IDENTIFY PIPING CONNECTION WITH
 REV 5 TAG AND CLOUD.
 O.P4.07A ASI#2/REV 5; ASI#2/REV 5 IS NOT NOTED ON THE
 PLAN. PER WPB FBC 107.2.1, ADD TO PLAN AND A) REVISED
 PLUMBING WORK OUTSIDE OF STAIR TOWER #2. PER WPB FBC
 107.2.1, IDENTIFY PIPING WITH REV 5 TAG AND CLOUD. B)
 ADDED CD PIPING CONNECTION OUTSIDE ELEVATOR LOBBY. DO
 NOT SEE ADDED CONNECTION. PER WPB FBC 107.2.1, IDENTIFY
 PIPING CONNECTION WITH REV 5 TAG AND CLOUD. C) REVISE
 REVISION SCHEDULE TO REFLECT OR MATCH UP WITH ASI#2 REV
 4 NOTED ON PLAN REVISION SCHEDULE, CLOUD AND TAG.
 P.P4.08A ASI#2/REV 4; A) REVISED PLUMBING WORK OUTSIDE
 OF STAIR TOWER #2. PER WPB FBC 107.2.1, IDENTIFY PIPING
 WITH REV 4 TAG AND CLOUD. B) ADDED CD PIPING CONNECTION
 OUTSIDE ELEVATOR LOBBY. DO NOT SEE ADDED CONNECTION.
 PER WPB FBC 107.2.1, IDENTIFY PIPING CONNECTION WITH
 REV 4 TAG AND CLOUD.
 Q.P9.04 ASI#2/REV 2; REVISED CD ISO. PER WPB FBC
 107.2.1, CLOUD CHANGES AND TAG REV 2. ADDITIONALLY,
 FILL IN MISSING SPOOLS TO PROVIDE COMPLETE DRAWING.
 R.P1.01 ASI#2R/REV 5; ASI#2R/REV 5 IS NOT NOTED ON THE
 PLAN. PER WPB FBC 107.2.1, ADD TO PLAN AND A) ADDED DAY
 TANK FOR GENERATOR. PER WPB FBC 107.2.1, IDENTIFY DAY
 TANK WITH REV 5 TAG AND CLOUD. B) ADDED CD PIPING AND
 STORM PIPING AS SHOWN ON CIVIL PLANS IN LOADING DOCK.
 DO NOT SEE ADDED CONNECTIONS. PER WPB FBC 107.2.1,
 IDENTIFY PIPING CONNECTIONS WITH REV 5 TAG AND CLOUD.
 C) NOTE ELIMINATION OF ST-1 WITH REV 5 TAG AND CLOUD.
 D) REVISE REVISION SCHEDULE TO REFLECT OR MATCH UP WITH
 ASI#2R REV 6 NOTED ON PLAN REVISION SCHEDULE, CLOUD AND
 TAG.
 S.P1.02 ASI#2R/REV 5; ASI#2R/REV 5 IS NOT NOTED ON THE
 PLAN. PER WPB FBC 107.2.1, ADD TO PLAN AND A) ADDED CD
 CONNECTION. PER WPB FBC 107.2.1, IDENTIFY CD CONNECTION
 WITH REV 5 TAG AND CLOUD. B) MOVED STORM PIPING TO
 TRENCH DRAIN. PER WPB FBC 107.2.1, IDENTIFY WITH REV 5
 TAG AND CLOUD. C) SHIFTED STORM RISERS AND ELIMINATED
 ST-9. ST-1 IS STILL SHOWN ON PLAN. CLARIFY. NOTE
 CHANGES WITH REV 5 TAG AND CLOUD. D) REVISE REVISION
 SCHEDULE TO REFLECT OR MATCH UP WITH ASI#2R REV 3 NOTED
 ON PLAN REVISION SCHEDULE, CLOUD AND TAG. PLEASE NOTE
 THAT P1.03, P1.04 AND P1.05 ARE STILL SHOWING ST-1
 STORM RISER. PER WPB FBC 107.2.1, CLARIFY.
 ADDITIONALLY, PER WPB FBC 107.2.1, REVIEW PLAN SHEETS
 P1.06, P1.07, P-1.08, P1.09 AND ANY OTHER POTENTIALLY
 AFFECTED PLANS FOR ANY NOTE OF STORM RISER ST-9, REVISE
 AND RESUBMIT AS REQUIRED.
 T.P4.01A ASI#2R/REV 5; ASI#2R/REV 5 IS NOT NOTED ON THE
 PLAN. PER WPB FBC 107.2.1, ADD TO PLAN AND PER WPB FBC
 107.2.1, IDENTIFY CHANGES WITH REV 5 TAG AND CLOUD.
 REVISE REVISION SCHEDULE TO REFLECT OR MATCH UP WITH
 ASI#2R REV 9 NOTED ON PLAN REVISION SCHEDULE, CLOUD AND
 TAG. ADDITIONALLY, ASI#2R/REV 9 IS INDICATED IN THE
 FUEL TANK ROOM. PER WPB FBC 107.2.1, CLARIFY.
 U.P4.02A ASI#2R/REV 5; ASI#2R/REV 5 IS NOT NOTED ON THE
 PLAN. PER WPB FBC 107.2.1, ADD TO PLAN AND PER WPB FBC
 107.2.1, IDENTIFY CHANGES WITH REV 5 TAG AND CLOUD.
 REVISE REVISION SCHEDULE TO REFLECT OR MATCH UP WITH
 ASI#2R REV 6 NOTED ON PLAN REVISION SCHEDULE, CLOUD AND
 TAG.
 V.P4.03A ASI#2R/REV 5; PER WPB FBC 107.2.1, IDENTIFY
 CHANGES WITH REV 5 TAG AND CLOUD.
 W.P4.04A ASI#2R/REV 5; PER WPB FBC 107.2.1, IDENTIFY
 CHANGES WITH REV 5 TAG AND CLOUD.
 X.P4.05A ASI#2R/REV 5; PER WPB FBC 107.2.1, IDENTIFY
 CHANGES WITH REV 5 TAG AND CLOUD.
 Y.P4.06A ASI#2R/REV 5; ASI#2R/REV 5 IS NOT NOTED ON THE
 PLAN. PER WPB FBC 107.2.1, ADD TO PLAN AND PER WPB FBC
 107.2.1, IDENTIFY CHANGES WITH REV 5 TAG AND CLOUD.
 REVISE REVISION SCHEDULE TO REFLECT OR MATCH UP WITH
 ASI#2R REV 6 NOTED ON PLAN REVISION SCHEDULE, CLOUD AND
 TAG.
 Z.P4.07A ASI#2R/REV 5; PER WPB FBC 107.2.1, IDENTIFY
 CHANGES WITH REV 5 TAG AND CLOUD.
 AA.P4.08A ASI#2R/REV 5; PER WPB FBC 107.2.1, IDENTIFY
 CHANGES WITH REV 5 TAG AND CLOUD.
 BB.P4.06A ASI#4/REV 7; ASI#4/REV 7 IS NOT NOTED ON THE
 PLAN. THERE IS AN ASI#5/REV 6 IN THE REVISION SCHEDULE.
 PER WPB FBC 107.2.1, CLARIFY, IDENTIFY CHANGES WITH REV
 7, TAG AND CLOUD. REVISE REVISION SCHEDULE TO REFLECT
 OR MATCH UP WITH ASI#5/REV 6 NOTED ON PLAN REVISION
 SCHEDULE, CLOUD AND TAG.
 CC.P4.07A ASI#4/REV 6; ASI#4/REV 6 IS NOT NOTED ON THE
 PLAN. THERE IS AN ASI#5/REV 6 IN THE REVISION SCHEDULE.
 PER WPB FBC 107.2.1, CLARIFY, IDENTIFY CHANGES WITH REV
 6, TAG AND CLOUD. REVISE REVISION SCHEDULE TO REFLECT
 OR MATCH UP WITH ASI#5/REV 6 NOTED ON PLAN REVISION
 SCHEDULE, CLOUD AND TAG.
 DD.P4.08A ASI#4/REV 6; ASI#4/REV 6 IS NOT NOTED ON THE
 PLAN. THERE IS AN ASI#5/REV 6 IN THE REVISION SCHEDULE.
 PER WPB FBC 107.2.1, CLARIFY, IDENTIFY CHANGES WITH REV
 6, TAG AND CLOUD. REVISE REVISION SCHEDULE TO REFLECT
 OR MATCH UP WITH ASI#5/REV 6 NOTED ON PLAN REVISION
 SCHEDULE, CLOUD AND TAG.
 EE.P4.09 ASI#4/REV 2; ASI#4/REV 2 IS NOT NOTED ON THE
 PLAN. THERE IS AN ASI#5/REV 2 IN THE REVISION SCHEDULE.
 PER WPB FBC 107.2.1, CLARIFY, IDENTIFY CHANGES WITH REV
 2, TAG AND CLOUD. REVISE REVISION SCHEDULE TO REFLECT
 OR MATCH UP WITH ASI#5/REV 2 NOTED ON PLAN REVISION
 SCHEDULE, CLOUD AND TAG.
 FF.P4.07A ASI#4/REV 6; ASI#4/REV 6 IS NOT NOTED ON THE
 PLAN. THERE IS AN ASI#5/REV 6 IN THE REVISION SCHEDULE.
 PER WPB FBC 107.2.1, CLARIFY, IDENTIFY CHANGES WITH REV
 6, TAG AND CLOUD. REVISE REVISION SCHEDULE TO REFLECT
 OR MATCH UP WITH ASI#5/REV 6 NOTED ON PLAN REVISION
 SCHEDULE, CLOUD AND TAG.
 GG.P9.02 ASI#4/REV 3; ASI#4/REV 3 IS NOT NOTED ON THE
 PLAN. THERE IS AN ASI#5/REV 3 IN THE REVISION SCHEDULE.
 PER WPB FBC 107.2.1, CLARIFY, IDENTIFY CHANGES WITH REV
 3, TAG AND CLOUD. REVISE REVISION SCHEDULE TO REFLECT
 OR MATCH UP WITH ASI#5/REV 3 NOTED ON PLAN REVISION
 SCHEDULE, CLOUD AND TAG.
 HH.P0.02 ASI#9/REV 5; PER WPB FBC 107.2.1, IDENTIFY
 CHANGES WITH REV 5 TAG AND CLOUD.
 II.P4.10 ASI#10/REV 2; PER WPB FBC 107.2.1, IDENTIFY
 CHANGES WITH REV 2 TAG AND CLOUD.
  
 2.DOMESTIC PUMP SYSTEM IS DESIGNED AT 246 TDH WHICH IS
 THE EQUIVALENT OF 107 PSI ADDED TO THE INCOMING
 PRESSURE SUPPLIED BY THE CITY AT THE PUMP.
 NOTE FBC PL 604.8 WATER PRESSURE-REDUCING VALVE OR
 REGULATOR. WHERE WATER PRESSURE WITHIN A BUILDING
 EXCEEDS 80 PSI (552 KPA) STATIC, AN APPROVED WATER
 PRESSURE-REDUCING VALVE CONFORMING TO ASSE 1003 OR CSA
 B356 WITH STRAINER SHALL BE INSTALLED TO REDUCE THE
 PRESSURE IN THE BUILDING WATER DISTRIBUTION PIPING TO
 NOT GREATER THAN 80 PSI (552 KPA) STATIC.
 EXCEPTION: SERVICE LINES TO SILL COCKS AND OUTSIDE
 HYDRANTS, AND MAIN SUPPLY RISERS WHERE PRESSURE FROM
 THE MAINS IS REDUCED TO 80 PSI (552 KPA) OR LESS AT
 INDIVIDUAL FIXTURES.
 ADDITIONALLY NOTE THAT MANY MANUFACTURER?S PRODUCT?S
 (IE. FAUCETS, FLUSH VALVES, DRINKING FOUNTAINS, WASHING
 MACHINES, SHOWER VALVES, ETC.) SPECIFICALLY STATE THAT
 IF WATER PRESSURE EXCEEDS A CERTAIN PRESSURE (IE. 65
 PSI) THEN THE WARRANTY MAY BE VOIDED. PLEASE SEE FBC PL
 303.2 INSTALLATION OF MATERIALS. ALL MATERIALS USED
 SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE
 STANDARDS UNDER WHICH THE MATERIALS ARE ACCEPTED AND
 APPROVED. IN THE ABSENCE OF SUCH INSTALLATION
 PROCEDURES, THE MANUFACTURER?S INSTRUCTIONS SHALL BE
 FOLLOWED. WHERE THE REQUIREMENTS OF REFERENCED
 STANDARDS OR MANUFACTURER?S INSTALLATION INSTRUCTIONS
 DO NOT CONFORM TO MINIMUM PROVISIONS OF THIS CODE, THE
 PROVISIONS OF THIS CODE SHALL APPLY.
 PER WPB FBC 107.2.1, INDICATE SERVICE PRESSURE AT EACH
 FLOOR ON DOMESTIC WATER RISER DIAGRAM. ADDITIONALLY,
 PROVIDE SUCTION AND DISCHARGE PRESSURES AT THE DOMESTIC
 BOOSTER PUMP. SPECIFY AND PROVIDE LEAD FREE PRESSURE
 REDUCING VALVES WITH STRAINERS AT SERVICE OUTLET(S) ON
 THE HIGH PRESSURE SIDE OF THE DOMESTIC BOOSTER PUMP
 SYSTEMS IN ACCORDANCE WITH FBC PL 604.8 AND 302.2
  
 3.WATER RISER DIAGRAM APPEARS TO BE INCOMPLETE AND/OR
 DOES NOT NECESSARILY REFLECT THE PLUMBING FLOOR
 PLAN(S). PER WPB FBC 107.2.1, PROVIDE COMPLETE RISER
 DIAGRAM(S) SHOWING ALL FLOORS AND DISTRIBUTION. IF
 NECESSARY, PROVIDE SUPPLEMENTAL SCHEMATIC(S) TO PROVIDE
 CLARIFICATION. SHOW ALL SERVICE OUTLETS BOTH FOR SHELL
 AND FUTURE. SHOW REQUIRED PRVS.THERE ARE DISCONNECTED
 SPOOLS AS WELL AS SYMBOLS WITH NO PIPING TO THEM. PER
 WPB FBC 107.2.1, REMOVE ANY DISCONNECTED ITEMS OR
 PROVIDE CONNECTIONS TO THE SAME. SHOW ALL
  
 4.INDICATE ALL FLOOR LEVELS ON ALL RISER DIAGRAMS.
  
 5.PROVIDE COMPLETE, SIZED SANITARY BUILDING RISER
 DIAGRAM TO INCLUDE ALL BUILDING DRAIN, POINT OF
 CONNECTION TO BUILDING SEWER, BRANCHES OF THE BUILDING
 DRAIN, SOIL AND WASTE STACKS, FIXTURE BRANCHES, FIXTURE
 DRAINS, INDIVIDUAL VENTS, BRANCH VENTS, VENT STACKS,
 STACK VENTS. AT TYPICAL
  
 6.LABEL RISER DIAGRAMS INDICATING FIXTURE/EQUIPMENT
 EACH INLET OR OUTLET IS SERVICING
  
 7.PROVIDE SIZED SANITARY AND WATER RISER DIAGRAMS FOR
 CORE AREA BATHROOMS/JANITOR ROOMS. PROVIDE TYPICAL FOR
 FLOORS 9, 10, 12, 13, 14 AND 16 AND A SEPARATE FOR
 FLOORS 11, 15 AND 17 IF REQUIRED; SEE NOTE*
 *JANITOR?S ROOM, FLOORS 9 THROUGH 17. SHEET AE4.10
 PRESENTS AS ALL FLOORS ARE TYPICAL, BUT AE6.02 FINISH
 SCHEDULE INDICATES JANITOR?S ROOMS ON FLOORS 9 (RM
 907), 10 (RM 1007), 12 (RM 1206), 13 (RM 1306), 14 (RM
 1406) AND 16 (RM 1606) AND NO MENTION OF JANITOR?S
 ROOMS ON FLOORS 11,15 AND 17. PER WPB FBC 107.2.1,
 CLARIFY AND RECONCILE.
  
 8.PLEASE NOTE THAT THE FOLLOWING PLUMBING PLAN SHEETS
 WHICH ARE LISTED ON SHEET G10.03 ARE NOT INCLUDED IN
 THE CURRENT SUBMITTED DRAWINGS: P0.01, P1.06, P1.07,
 P1.08, P1.09, P1.10, P1.11, P4.01, P4.02B, P4.03B,
 P4.04B, P4.07B, P4.08B, P4.13, P5.01, P5.02, P9.01, AND
 P9.03. PER WPB FBC 107.2.1, PROVIDE THE NOTED
 DOCUMENTS.
 PLEASE NOTE THERE ARE OTHER SHEETS MISSING IN OTHER
 DISCIPLINES AS WELL AND MAY BE REQUIRED TO RECEIVE A
 COMPREHENSIVE REVIEW.
  
 9.SEE PLAN SHEETS AE4.09, P4.09 AND P9.02. STORM PIPING
 PLAN VIEW AND ISOMETRIC INDICATE ROOF DRAINS WITH
 PRIMARY STORM PIPING AND OVERFLOW PIPING (SEE ST-7,
 ST-8, ST-10A AND ST-10B RISERS). PLAN VIEW ON AE4.09
 AND ON P4.09 SHOW A COMBINATION ROOF AND OVERFLOW DRAIN
 REGARDLESS OF WHETHER THE DRAIN IS DESIGNATED A PLANTER
 DRAIN (PD) OR A ROOF DRAIN (RD). PER WPB FBC 107.2.1,
 CLARIFY.
  
 10.NEED TO CLARIFY ST-9 RISER P4.01A AND P9.02
 PLAN SHEETS P4.01, P1.01, P1.02, P1.03, P1.04 AND P1.05
 SHOW RISER ST-9 (AS PREVIOUSLY NOTED, DRAWINGS P1.06
 THROUGH P1.09 ARE NOT INCLUDED IN THE SUBMITTED PLANS).
 HOWEVER, ST-9 IS NOT INDICATED ON P9.02 RISER DIAGRAM,
 ALTHOUGH THERE IS A TAG DESIGNATED ST-9. PER WPB FBC
 107.2.1, CLARIFY AND RECONCILE.
  
 11.PER WPB FBC 107.2.1, IDENTIFY ST-10A AND ST-10B ON
 P9.02 RISER DIAGRAM. CLARIFY ON P1.01 THAT ST-10 IS
 ACTUALLY ST-10B.
  
 12.ST-10A NOTED AS 8 INCH DIAMETER IS SHOWN CONNECTING
 TO ST-11 WHICH IS 6 INCH DIAMETER AND CONTINUES AS 6
 INCH TO THE POINT OF DISPOSAL SEE P9.02. PER WPB FBC
 107.2.1, SIZE BRANCH TO ACCOMMODATE THE COMBINED
 DISCHARGE OF ST-10A AND ST-11.
  
 13.ST-10B (ALSO NOTED AS ST-10 ON P1.01) APPEARS TO
 DISCHARGE DIRECTLY ONTO THE FIRST FLOOR. IS THIS THE
 POINT OF DISPOSAL? PER WPB FBC 107.2.1, CLARIFY AND
 SHOW COMPLIANCE WITH FBC PL 1101.2 DISPOSAL: RAINWATER
 FROM ROOFS AND STORM WATER FROM PAVED AREAS, YARDS,
 COURTS AND COURTYARDS SHALL DRAIN TO AN APPROVED PLACE
 OF DISPOSAL. FOR ONE- AND TWO-FAMILY DWELLINGS, AND
 WHERE APPROVED, STORM WATER IS PERMITTED TO DISCHARGE
 ONTO FLAT AREAS, SUCH AS STREETS OR LAWNS, PROVIDED
 THAT THE STORM WATER FLOWS AWAY FROM THE BUILDING.
  
 14.REGARDING STORM PIPING, PER WPB FBC 107.2.1,
 INDICATE ON BOTH PLAN VIEW SHEETS AND RISER DIAGRAM THE
 GPM OF ALL ROOF DRAINS AND PLANTER DRAINS AND ANY OTHER
 DRAIN INLETS THAT ADD RAINWATER TO THE SYSTEM. INDICATE
 ON THE SAME SHEETS THE ACCUMULATED GPM WHERE ONE
 AFFECTED BRANCH CONNECTS TO ANOTHER (IE. ST-10B
 CONNECTS TO ST-11) AND NOTE GPM AT ALL POINTS OF
 DISPOSAL
  
 15.SIZE ALL STORM PIPING MAINS AND BRANCHES ON P9.02
 AND P4.01A
  
 16.P9.02; WHAT IS THE STAND ALONE HORIZONTAL PIPING
 SPOOL ADJACENT TO THE BASE OF ST-12 AND THE OTHER
 HORIZONTAL PIPING SPOOL WITH THE WYE BELOW THAT?
  
 17.P9.02; WHAT IS THE STAND ALONE VERTICAL PIPING SPOOL
 SHOWN TO THE RIGHT OF ST-12?
  
 18.RECONCILE CIVIL AND BUILDING PLANS: P1.01 INDICATES
 16 INCH DIAMETER STORM SERVICE DRAIN AT I.E. 16.16
 (1600 GPM). CIVIL C5.00 INDICATES SAME SECTION OF
 PIPING TO BE 15 INCH HDPE. PER WPB FBC 107.2.1 CLARIFY
 AND RECONCILE.
  
 19. JANITOR?S ROOM, FLOORS 9 THROUGH 17. SHEET AE4.10
 PRESENTS AS ALL FLOORS ARE TYPICAL, BUT AE6.02 FINISH
 SCHEDULE INDICATES JANITOR?S ROOMS ON FLOORS 9 (RM
 907), 10 (RM 1007), 12 (RM 1206), 13 (RM 1306), 14 (RM
 1406) AND 16 (RM 1606) AND NO MENTION OF JANITOR?S
 ROOMS ON FLOORS 11,15 AND 17. PER WPB FBC 107.2.1,
 CLARIFY AND RECONCILE.
  
 20.NOTED JANITOR?S ROOMS PARTITION TYPE DESIGNATED SAM
 IN SHEET AE7.01 NOTES 5/8 INCH GYPSUM (GWB) ON THE
 JANITOR ROOM SIDE OF THE PARTITION. AE6.02 FINISH
 SCHEDULE FOR THE WALL INDICATES DESIGNATION PT-12
 SEMI-GLOSS PAINT. PLEASE REFER TO FBC PL 310.3 AND FBC
 1210.2.2. WALLS AND PARTITIONS WITHIN 2 FEET (610 MM)
 OF SERVICE SINKS, URINALS AND WATER CLOSETS SHALL HAVE
 A SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT OF
 NOT LESS THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND
 EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIALS USED IN
 SUCH WALLS SHALL BE OF A TYPE THAT IS NOT ADVERSELY
 AFFECTED BY MOISTURE. PLEASE NOTE THAT FBC 1210.2.2
 STIPULATES THAT THE MATERIAL BE "HARD." THE INTENT OF
 THIS SECTION IS THAT THE SURROUNDING MATERIAL SHOULD
 NOT BE OF A TYPE THAT IS EASILY DAMAGED SUCH THAT THE
 MATERIAL COULD BECOME ABSORBENT AND THUS, NOT READILY
 CLEANABLE AND SANITIZED. PAINTED DRYWALL, EVEN WHERE
 COATED WITH HIGHLY DURABLE PAINTS, DOES NOT MEET THE
 INTENT OF SECTION 1210.2.2. THE TYPICAL MATERIALS USED
 FOR THIS APPLICATION ARE CERAMIC TILE, FIBERGLASS
 REINFORCED PLASTIC (FRP) PANELS, PHENOLIC PANELS,
 LAMINATED PLASTIC PANELS, PAINTED STEEL AND STAINLESS
 STEEL. PER FBC PL 310.3 AND FBC 1210.2.2, JANITOR ROOM
 WALLS AT SERVICE SINK SHALL COMPLY
  
 END OF COMMENTS.
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS
 FROM THE FIRST REVIEW.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-243-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21020368 360 S ROSEMARY AVE
  
  
  
  