2021-04-06 16:03:111ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21020368
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.01: LEVEL 1B- DUCTWORK SECTION: PLEASE
 REMOVE ALL PIPING THAT IS IN STAIRWAY FBC 1023.5
  
 2) SHEET M1.01: DUCT WORK PENETRATING THE FIRE COMMAND
 ROOM (2) HOUR RATED WALL SHALL HAVE FIRE DAMPERS. FBC M
 607
  
 3) SHEET M1.01: PLEASE SHOW THE REQUIRED PROTECTION AT
 THE (2) HOUR RATED WALL WHERE THE OUTDOOR AIR DUCT
 PENETRATES THE RATED WALL. FBC M 607
  
 4) SHEET M1.01: PLEASE SHOW THE PENETRATION PROTECTION
 IN THE RATED WALL WHERE EF-1-2, EF-1-4 AND EF-1-5
 PENETRATE THE RATED WALL. FBC M 607
  
 5) SHEET M1.02: FRESH AIR INTAKE DUCT IS PENETRATING A
 RATED WALL IN ROOM 205 (STORAGE) PLEASE SHOW THE
 REQUIRED PROTECTION. FBC M 607
  
 6) PLEASE SHOW CONDENSATE DISPOSAL LOCATION FOR ALL
 CU?S IN THE GARAGE. FBC M 307
  
 7) SHEET M1.03PLEASE SHOW PROTECTION FOR ALL DUCT WORK
 PENETRATING RATED FLOOR/CEILING AREAS. FBC M 607
  
 8) SHEET M1.04: PLEASE SHOW PROTECTION WHERE DUCTWORK
 PENETRATES RATED WALLS. FBC M 607
  
 9) SHEET M1.05: PLEASE SHOW PROTECTION WHERE DUCTWORK
 PENETRATES RATED WALLS. FBC M 607
  
 10) SHEET M1.05: IT APPEARS THAT THE FRESH AIR AT UNIT
 AH-DX-4-3 IS BEING DUCTED INTO THE STAIRWAY. PLEASE
 REMOVE. FBC 1023.5
  
 11) SHEET M1.05: PLEASE EXPLAIN THE DUCTWORK
 PENETRATING THE RATED WALL IN THE ELEVATOR 7 AREA AND
 SHOW THE PROTECTION WHERE THE DUCTWORK PENETRATES THE
 RATED WALL.
  
 12) SHEET M1.05: PLEASE SHOW PROTECTION FOR THE RATED
 WALL WHERE THE O.A. DUCT PENETRATES THE RATED WALL AT
 BF-1.
  
 13) SHEET M8.01 PLEASE SHOW THE CALCULATIONS HOW THE
 POST FIRE SMOKE PURGE FANS WERE REDUCED BY 2 FANS AND A
 TOTAL OF 23,200 CFM. FBC 107.2.1
  
 14) SHEET M8.02: PLEASE SHOW HOW THE ELECTRIC DUCT
 HEATER SCHEDULE WAS REDUCED BY 3600 CFM. FBC 107.2.1
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  