| 2021-04-06 16:03:11 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21020368 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M1.01: LEVEL 1B- DUCTWORK SECTION: PLEASE |
| | REMOVE ALL PIPING THAT IS IN STAIRWAY FBC 1023.5 |
| | |
| | 2) SHEET M1.01: DUCT WORK PENETRATING THE FIRE COMMAND |
| | ROOM (2) HOUR RATED WALL SHALL HAVE FIRE DAMPERS. FBC M |
| | 607 |
| | |
| | 3) SHEET M1.01: PLEASE SHOW THE REQUIRED PROTECTION AT |
| | THE (2) HOUR RATED WALL WHERE THE OUTDOOR AIR DUCT |
| | PENETRATES THE RATED WALL. FBC M 607 |
| | |
| | 4) SHEET M1.01: PLEASE SHOW THE PENETRATION PROTECTION |
| | IN THE RATED WALL WHERE EF-1-2, EF-1-4 AND EF-1-5 |
| | PENETRATE THE RATED WALL. FBC M 607 |
| | |
| | 5) SHEET M1.02: FRESH AIR INTAKE DUCT IS PENETRATING A |
| | RATED WALL IN ROOM 205 (STORAGE) PLEASE SHOW THE |
| | REQUIRED PROTECTION. FBC M 607 |
| | |
| | 6) PLEASE SHOW CONDENSATE DISPOSAL LOCATION FOR ALL |
| | CU?S IN THE GARAGE. FBC M 307 |
| | |
| | 7) SHEET M1.03PLEASE SHOW PROTECTION FOR ALL DUCT WORK |
| | PENETRATING RATED FLOOR/CEILING AREAS. FBC M 607 |
| | |
| | 8) SHEET M1.04: PLEASE SHOW PROTECTION WHERE DUCTWORK |
| | PENETRATES RATED WALLS. FBC M 607 |
| | |
| | 9) SHEET M1.05: PLEASE SHOW PROTECTION WHERE DUCTWORK |
| | PENETRATES RATED WALLS. FBC M 607 |
| | |
| | 10) SHEET M1.05: IT APPEARS THAT THE FRESH AIR AT UNIT |
| | AH-DX-4-3 IS BEING DUCTED INTO THE STAIRWAY. PLEASE |
| | REMOVE. FBC 1023.5 |
| | |
| | 11) SHEET M1.05: PLEASE EXPLAIN THE DUCTWORK |
| | PENETRATING THE RATED WALL IN THE ELEVATOR 7 AREA AND |
| | SHOW THE PROTECTION WHERE THE DUCTWORK PENETRATES THE |
| | RATED WALL. |
| | |
| | 12) SHEET M1.05: PLEASE SHOW PROTECTION FOR THE RATED |
| | WALL WHERE THE O.A. DUCT PENETRATES THE RATED WALL AT |
| | BF-1. |
| | |
| | 13) SHEET M8.01 PLEASE SHOW THE CALCULATIONS HOW THE |
| | POST FIRE SMOKE PURGE FANS WERE REDUCED BY 2 FANS AND A |
| | TOTAL OF 23,200 CFM. FBC 107.2.1 |
| | |
| | 14) SHEET M8.02: PLEASE SHOW HOW THE ELECTRIC DUCT |
| | HEATER SCHEDULE WAS REDUCED BY 3600 CFM. FBC 107.2.1 |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |