Plan Review Notes
Plan Review Notes For Permit 21020360
Permit Number 21020360
Review Stop E
Sequence Number 3
Notes
Date Text
2021-06-15 13:54:16ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 WORK SURFACE COUNTER TOP IN LAUNDRY ROOM REQUIRES
 OUTLETS PER 210.52(C)(1)
  
 210.52(C)(1) WALL COUNTERTOP AND WORK SURFACE. A
 RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL
 COUNTERTOP AND WORK SURFACE THAT IS 300 MM (12 IN.) OR
 WIDER. RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO
 POINT ALONG THE WALL LINE IS MORE THAN 600 MM (24 IN.)
 MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT
 SPACE.