| Plan Review Notes For Permit 21020360 |
| Permit Number |
21020360 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-04-22 13:00:42 | SFR REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | 2ND REVIEW - NO NEW DRAWINGS OR ROOFING PRODUCT | | | APPROVAL WAS ADDED. | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE SHOW THE REQUIRED EXERIOR WALL WATER BARRIER | | | FBC R703.2 WATER-RESISTIVE BARRIER. | | | ONE LAYER OF NO. 15 ASPHALT FELT, FREE FROM HOLES AND | | | BREAKS, COMPLYING WITH ASTM D226 FOR TYPE 1 FELT OR | | | OTHER APPROVED WATER-RESISTIVE BARRIER SHALL BE APPLIED | | | OVER STUDS OR SHEATHING OF ALL EXTERIOR WALLS. | | | 2) CODE IN EFFECT HAS CHANGED ON 1/1/2021 - PLEASE | | | REVISE THE DRAWINGS TO SHOW THE DESIGN PER THE CODE IN | | | EFFECT (2020 FBC AND ASCE 7-16) | | | 3) ROOF PRODUCT APPROVAL PROVIDED - THE ROOFING SYSTEM | | | CHOSEN HAS A WIND DESIGN PRESSURE OF (-90) - PER 2020 | | | FBC TABLE TABLE R301.2(2) AND TABLE R301.2(3) ROOF ZONE | | | 3 REQUIRES A WIND DESIGN PRESSURE OF (-108.17) THIS | | | SYSTEM CANNOT BE USED UNLESS PROVIDED WITH SITE | | | SPECIFIC WIND DESIGN PRESSURES FROM A QUALIFIED DESIGN | | | PROFESSIONAL THAT SHOW THE WIND DESIGN BELOW THE (-90) | | | - SEE NOTE NUMBER 10 ON THE PRODUCT APPROVAL. |
|