Plan Review Notes For Permit 21020360
Permit Number 21020360
Review Stop E
Sequence Number 1
Notes
Date Text
2021-03-11 09:36:21ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NOTES ON PLANS REFERNCE 2014 NEC THIS PERMIT IS
 UNDER THE 2017 NEC AND THE 2020FBC, PLEASE CORRECT THE
 CODE EDITIONS BEING USE.
  
 2) RISER SHOWS TWO PANEL A'S PLEASE CORRECT TO A AND B
  
 3) WIRE SIZES NOT SHOWN TO ONE OF THE PANELS
  
 4) WHICH TAP RULE ARE YOU USING FOR THE FEEDERS?
  
 5) ARC FAULT CIRCUITS ARE REQUIRED IN MORE AREAS THAN
 NOTED PLEASE CORRECT.