| Plan Review Notes For Permit 21020360 |
| Permit Number |
21020360 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-03-11 09:36:21 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) NOTES ON PLANS REFERNCE 2014 NEC THIS PERMIT IS | | | UNDER THE 2017 NEC AND THE 2020FBC, PLEASE CORRECT THE | | | CODE EDITIONS BEING USE. | | | | | | 2) RISER SHOWS TWO PANEL A'S PLEASE CORRECT TO A AND B | | | | | | 3) WIRE SIZES NOT SHOWN TO ONE OF THE PANELS | | | | | | 4) WHICH TAP RULE ARE YOU USING FOR THE FEEDERS? | | | | | | 5) ARC FAULT CIRCUITS ARE REQUIRED IN MORE AREAS THAN | | | NOTED PLEASE CORRECT. |
|