| 2021-02-19 15:47:08 | CODES IN EFFECT |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020 |
| | 7TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1) SHEET A-1 FLOOR PLAN DOES NOT MENTION ELECTRICAL |
| | WORK BEING DONE (EXCEPT FOR THE MOTORIZED SHADES ON |
| | MASTER SUITE) BUT SHEET A1.2 REFLECTED CEILING SHOWS |
| | SUBSTANTIAL ELECTRICAL WORK. PLEASE CLARIFY SCOPE OF |
| | WORK AND SHOW WHAT IS NEW AND WHAT IS EXISTING TO |
| | REMAIN. FBC 107 |
| | |
| | 2) ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| | SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| | KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| | PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, |
| | RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND |
| | SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE |
| | CORRECTION. NEC 210.12 (A NOTE WILL SUFFICE) |
| | |
| | |
| | 3) TAMPER-RESISTANT RECEPTACLES REQUIRED AS PER NEC |
| | 406.12 (A NOTE WILL SUFFICE) |
| | |
| | 4) PROVIDE COMPLIANCE: "NOT LESS THAN 90 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LUMINAIRES SHALL HAVE AN |
| | EFFICACY OF AT LEAST 45 LUMENS-PER-WATT OR SHALL |
| | UTILIZE LAMPS WITH AN EFFICACY OF NOT LESS THAN 65 |
| | LUMENS-PER-WATT?. A NOTE WILL SUFFICE. FBC EC R404.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A |
| | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| | |
| | HTTPS://WWW.WPB.ORG/GOVERNMENT/DEVELOPMENT-SERVICES/FOR |
| | MS |
| | |
| | |
| | ENRIQUE QUINONEZ P.E. |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |