| Plan Review Notes For Permit 21020334 |
| Permit Number |
21020334 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-02-17 14:20:58 | THIS PLAN WAS REVIEWED AND FAILED BY LT. BRIAN DOLAN, | | | FIRE INSPECTOR WITH THE FOLLOWING COMMENTS: | | | | | | 1. THE BRAIDED HOSE ASSEMBLIES (FLEX DROPS) LISTED IN | | | THE PLANS AND THE HYDRAULIC CALCULATION ARE | | | INCONSISTENT AND SIGNIFICANTLY DIFFERENT. PLEASE | | | EXPLAIN WHICH IS THE END USE PRODUCT AND PROVIDE | | | CONSISTENT LANGUAGE IN PLAN AND HYDRAULIC CALCULATIONS. |
|