| 2021-03-10 14:07:15 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 21020328 |
| | ADD: 327 HIBISCUS ST. |
| | CONT: SHUTTER UP INDUSTRIES INC/ QUALIFIER JEREMY S |
| | KOBOSKO |
| | TEL: 561-588-2623 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: MARCH 10TH/ 2021 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. THE CONTRACTOR (QUALIFIER/ JEREMY S |
| | KOBOSKO) THAT CREATED / DREW THE SET OF PLANS SHEET 1 & |
| | 2TWILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF THE |
| | PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND |
| | LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN AND |
| | PLANS DRAWN. |
| | 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE |
| | EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) |
| | ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) |
| | (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT |
| | WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE |
| | CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE. |
| | THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET |
| | OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR |
| | OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME |
| | AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN |
| | AND PLANS DRAWN. |
| | |
| | 2A)SEMI-COMPLIED. THERE IS A SINGLE DRAWING (ELEVATION |
| | OF OPENING) BUT THERE IS CONFUSION AS TO THE |
| | TERMINOLOGY USED AND WHAT IS SHOWN IN THE ELEVATION |
| | DETAIL. THERE ARE 2 OPENINGS PLEASE MAKE A ELEVATION |
| | DRAWING FOR EACH OPENING, PROVIDE THE OVER ALL WIDTH |
| | AND HEIGHT OF THE OPENING TO DETERMINE MULLION LENGTHS. |
| | 2ND PROVIDE THE OPENING SIZE ( GLAZING FOR EACH OPENING |
| | BE IT WINDOW OR DOOR. IDENTIFY IF THE OPENING IS A |
| | WINDOW AND OR DOOR. |
| | 1ST ROUND COMMENTS. THE PERMIT APPLICATION INDICATES |
| | THE REPLACEMENT OF 4 PICTURE WINDOWS AND 1 EXTERIOR |
| | DOOR. THE FLOOR PLAN ONLY SHOWS 2 OPENINGS. THE WRITTEN |
| | WORDS ARE SO SMALL WHEN THE PLANS GO TO RECORD |
| | RETENTION, THEY MAY NOT BE LEGIBLE FOR RECORD |
| | RETENTION. 107.2.1.3. QUALITY OF PLANS. THE BUILDING |
| | OFFICIAL MAY ESTABLISH THROUGH DEPARTMENT POLICY OTHER |
| | STANDARDS FOR THE PLANS AND SPECIFICATIONS IN ORDER TO |
| | PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM. |
| | THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, |
| | SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO |
| | RECORD MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE |
| | WITH THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES. |
| | |
| | 2B) 2ND REQUEST, THE FLOOR PLAN IDENTIFIES 2 OPENINGS, |
| | OPENING # 1 APPEARS TO BE CLOSE TO AN OUTSIDE CORNER OF |
| | THE BUILDING BUT NO DIMENSION IS GIVEN TO HOW CLOSE |
| | OPENING # 1 IS TO THE CORNER OF THE BUILDING. WHEN IN A |
| | CORNER WALL ZONE THE PRESSURES FOR THE OPENING ARE |
| | HIGHER. |
| | 1ST ROUND OF COMMENTS. THE WORDING ON THIS DOCUMENT |
| | APPEARS THE 4 SUPPOSED PICTURE WINDOWS ARE MULTIPLE (2) |
| | WINDOWS IN EACH OPENING WITH MULLIONS, ACTUALLY 2 |
| | OPENINGS, IS THAT CORRECT? WHERE IS THE DOOR THAT IS |
| | GOING TO BE REPLACED. 107.2.1.2 ADDITIONAL INFORMATION |
| | IS REQUIRED. NO LOCATION IS GIVEN FOR THE DOOR MAYBE IN |
| | ZONE 4 OR 5. |
| | |
| | 3) COMPLIED. THE DESIGN PRESSURE REPORT. THE DESIGN |
| | PRESSURE REPORT IS NOT DESIGNED BY A PROFESSIONAL |
| | ENGINEER. THERE IS NO DESIGNATION AS TO WHERE THE |
| | SUBMITTED PRESSURES CAME FROM. CONTRACTORS CAN NOT ACT |
| | AS ENGINEERS, YOU MUST PULL THE DESIGN PRESSURES FROM |
| | ASCE 7-16, THE 2020 FBC-B OR SOME OTHER RECOGNIZED |
| | SOURCE. ONE AND TWO FAMILY DWELLINGS THE CONTRACTOR CAN |
| | USE THE TABLE IN THAT CODE BOOK WITH MULTIPLIERS FOR |
| | EXPOSURE AND HEIGHT FOR RESIDENTIAL UNITS. |
| | |
| | 4) COMPLIED. THE DESIGN PRESSURE REPORT SUBMITTED LIST |
| | THE MEAN ROOF HEIGHT AS 15 FEET. GOOGLE MAPS INDICATES |
| | THIS BUILDING IS A 2 STORY BUILDING. THE MEAN ROOF |
| | HEIGHT IS HIGHER THAN 15 FEET. |
| | |
| | 5) COMPLIED. THE SUBMITTED DESIGN PRESSURE SHEET LIST |
| | THE HEIGHT OF THE ONE OPENING AS 92 INCHES WHEREAS THE |
| | 2ND OPENING THE HEIGHT IS LISTED AS 149 INCHES IN |
| | HEIGHT. MAYBE A TYPO. 107.2.1.2 ADDITIONAL INFORMATION |
| | IS REQUIRED. |
| | |
| | 6) 2ND REQUEST. IDENTIFY GLAZING/ MULLIONS. PLEASE |
| | IDENTIFY ON THE PRODUCT APPROVAL BEFORE SUBMITTING TO |
| | DESIGNER OF RECORD AND BEFORE SUBMISSION TO THE |
| | BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, |
| | PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF |
| | GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR |
| | REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B |
| | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| | RETIRED. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |