Plan Review Notes
Plan Review Notes For Permit 21020294
Permit Number 21020294
Review Stop G
Sequence Number 4
Notes
Date Text
2021-08-04 10:30:474TH REVIEW FBC-2017 FUEL GAS
 PERMIT-21020294
 8/4//2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IN RESPONSE TO THE 3RD REVIEW COMMENTS PRINTED
 BELOW, THE DESIGN ENGINEER FOR THE SYSTEM SUBMITTED A
 LETTER AND ADDITIONAL EXHAUST DUCT SPECIFICATIONS
 THROUGH EMAIL, BUT THOSE DOCUMENTS WERE NOT UPLOADED
 INTO THE PROJECT DOX SYSTEM FOR REVIEW. I HAVE ALSO
 BEEN ADVISED THROUGH EMAIL THAT MORE DOCUMENTS HAVE YET
 TO BE SUBMITTED. PLEASE PROVIDE A COMPLETE SUBMITTAL
 PACKAGE FOR THE COFFEE ROASTERS AND COMBUSTION AIR AND
 EXHAUST VENTILATION SYSTEMS. THE CURRENT SUBMITTAL
 PACKAGE UPLOADED FOR IN THIS REVIEW CYCLE DOES NOT
 INCLUDE THE MANUFACTURER'S SPECIFICATIONS FOR THE
 PROBAT G90- SECTION 623.1 FBC FG.
  
 2) SHEET M.3.2: PROBAT RECOMMENDATIONS PRINTED ON THE
 SHEET IDENTIFY THE VENT SYSTEM AS A CHIMNEY. PLEASE SEE
 SECTION 202 DEFINITIONS FBC FG- A CHIMNEY IS DEFINED AS
 PRIMARILY A VERTICAL STRUCTURE. THE EXHAUST VENT SYSTEM
 SHOWN ON THE PLAN IS PRIMARILY A HORIZONTAL STRUCTURE.
 AS NOTED IN THE 3RD REVIEW COMMENTS BELOW THE SYSTEM
 DESIGN DOES NOT APPEAR TO MEET THE "STRAIGHT OUT"
 REQUIREMENT AND IN FACT, IS TRAVELING THROUGH AN AREA
 THAT WILL BE OCCUPIED BY B0TH THE PUBLIC AND OTHER
 EMPLOYEES. PROBAT RECOMMENDATIONS SPECIFCALLY STATE
 THAT WHEN USING A SINGLE WALL DUCT, THE ROASTER AREA
 CANNOT BE ACCESSED BY ANYONE OTHER THAN THE OPERATOR.
 BASED ON THESE RECOMMENDATIONS IT APPEARS THAT USE OF
 THE SINGLE WALL DUCT SYSTEM SHOULD BE ALSO CONFINED TO
 THE ROASTER AREA. PLEASE NOTE THE RECOMMENDATIONS DO
 NOT HAVE THE SAME LIMITATION OF USE FOR THE DOUBLE WALL
 DUCT.
  
 3) WITH RESPECT TO THE COMBUSTION AIR/MAKEUP AIR BEING
 SUPPLIED MECHANICALLY USING AHU-4, PLEASE ADDRESS THESE
 CODE FBC FG REQUIRMENTS:
  
 A) SECTION 304.9: PROVIDE THE COMBUSTION AIR
 CALCULATIONS USING .35 CFMS PER 1000 BTUH TOTAL INPUT
 RATING OF THE ROASTERS.
  
 B) SECTION 304.9.1: EXHAUST FANS ARE SHOWN WHICH
 REQUIRE MAKE UP AIR TO REPLACE THE EXHAUSTED AIR. THE
 EXHAUST FAN CFM CAPACITIES HAVE NOT BEEN PROVIDED AND
 MAKEUP AIR NOT CALCULATED.
  
 C) SECTION 304.9.2: THE ROASTERS SHALL BE INTERLOCKED
 WITH THE SOURCE OF THE AIR TO PREVENT GAS BURNER
 OPERATION WHEN THE MECHANICAL AIR SUPPLY SYSTEM IS NOT
 IN OPERATION. PLEASE SHOW THE INTERLOCK SYSTEM BETWEEN
 THE ROASTERS AND AHU-4. IT IS ALSO IMPORTANT TO REVIEW
 THE FBC-MECHANICAL CODE- 2017 IN REGARD TO AIR
 BALANCING AND RECIRCULATION RESTRICTION OF AIR FROM THE
 ROASTER AREA TO OTHER OCCUPIED AREAS.
  
 3RD REVIEW
 SHEET M3.2: THERE APPEAR TO BE CONFLICTS BETWEEN THE
 PROBAT AND NORDFAB SPECIFICATIONS. THE PROBAT VENTING
 RECOMMENDATIONS ON THE NEW PLAN SHEET IDENTIFY THE
 ROASTERS AS CLASS III APPLIANCES WITH POSITIVE PRESSURE
 VENTING. PLEASE CLARIFY IF CLASS III IS INTENDED TO
 MEAN CATEGORY III AS DEFINED IN THE SECTION 202 FBC FG.
  
 PROBAT RECOMMENDS:
 A) POSITIVE PRESSURE VENT SYSTEM. (THE VENT DIAGRAM
 DOES INDICATE "POSITIVE PRESSURE" USING EXHAUST FANS AT
 THE APPLIANCES).
 B) TYPE G DUCTWORK WITH THE TEMPERATURE NOT TO EXCEED
 450 DEGREES F IN THE DUCTWORK.
 C) THE SINGLE OR DOUBLE DUCT SHOULD GO "STRAIGHT OUT"
 THE WALL.
 D) DUCT JOINTS SHALL BE SEALED.
 CHECKING DUCT COMPATIBILITY FOR ITEMS A, B, C, & D, THE
 NORDFAB SPECS INDICATE:
 A) USED UNDER VARIOUS "NEGATIVE STATIC PRESSURES"
 B) NOT IDENTIFIED AS TYPE G, AND COMPLETE PROBAT SPECS
 HAVE NOT BEEN SUBMITTED SO OPERATING EQUIPMENT AND DUCT
 TEMPERATURES ARE NOT KNOWN.
 C) THE VENT DIAGRAM INDICATES INDIVIDUAL EXHAUST RISERS
 CONNECTING TO A LARGE HORIZONTAL MAIN DUCT WHICH IS
 TRAVELING THROUGH OTHER AREAS WHICH DOES NOT APPEAR TO
 MEET THE "STRAIGHT OUT" REQUIREMENT.
 D) THE DUCT AND JOINTS WILL LEAK WHEN SEALED, AND
 LEAKAGE RATES HAVE BEEN ESTABLISHED UNDER "NEGATIVE"
 PRESSURES TESTING ONLY.
  
 BASED ON THE URGENCY EXPRESSED TO ME IN EMAILS FROM THE
 OWNER, PROMPT RESPONSES TO THE ABOVE ISSUES WOULD BE
 VERY HELPFUL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719