Plan Review Notes
Plan Review Notes For Permit 21020294
Permit Number 21020294
Review Stop M
Sequence Number 3
Notes
Date Text
2021-07-28 14:27:033RD REVIEW FBC-2020 MECHANICAL
 PERMIT-21020294
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE UNDERSTAND THAT THE MECHANICAL EQUIPMENT
 SIZING CALCULATIONS AND THE EQUIPMENT TABLE ON SHEET
 M4.0 MUST MATCH. FBC 107.2.1, FBC EC C403.2.1
  
 2) IF AHU-3 IS NOT TO BE INSTALLED AT THIS TIME UNDER
 THIS PERMIT THEN IT MUST BE REMOVED FROM THIS PROJECT
 DOCUMENTS. FBC 107.2.1
  
 3) THE TABLES ON M3.1 ARE IDENTIFIED AS ASHRAE 62.1
 PRESSURIZATION CALCULATION, PLEASE IDENTIFY THESE AS
 MINIMUM VENTILATION RATES IN BREATHING ZONE AS THEY ARE
 TITLE IN THE REFERENCE. PLEASE ALSO LABEL THE SPACE
 NAMES ACCORDING TO THE MINIMUM VENTILATION TABLES SO I
 CAN CORRECTLY COMPARE YOUR CALCULATIONS TO THE TABLE
 USED. FBC 107.2.1 PLEASE REMEMBER THAT IF UNIT 3 IS NOT
 INSTALLED UNDER THIS PERMIT IT WILL NOT BE COUNTED IN
 THE OUTDOOR AIR CALCULATIONS.
  
 4) I DO NOT SEE A RESPONSE TO COMMENT (7) OF PREVIOUS
 CYCLE: PLEASE PROVIDE THE MANUFACTURING PROCESS IN THIS
 FACILITY. FBC 107.2.1
  
 5) I DO NOT SEE A RESPONSE TO COMMENT (8) OF PREVIOUS
 CYCLE: PLEASE PROVIDE THE EQUIPMENT SPECIFICATION
 SHEETS. FBC 107.2.1
  
 6) I DO NOT SEE A RESPONSE TO COMMENT (9) OF PREVIOUS
 CYCLE: PLEASE LIST ALL MATERIALS TO BE STORED IN THIS
 FACILITY AND THEIR QUANTITIES. FBC 107.2.1
  
 7) I DO NOT SEE A RESPONSE TO COMMENT (10) OF PREVIOUS
 CYCLE: WHAT IS THE OCCUPANCY ABOVE THE TENANT SPACE?
  
 8) THE COFFEE ROASTER MANUFACTURER MUST PROVIDE
 INSTALLATION INSTRUCTIONS FOR THE EXHAUST DUCT SYSTEM
 FOR THE ROASTERS. FBC FG TABLE 503.4
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728