| 2021-07-28 14:27:03 | 3RD REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21020294 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE UNDERSTAND THAT THE MECHANICAL EQUIPMENT |
| | SIZING CALCULATIONS AND THE EQUIPMENT TABLE ON SHEET |
| | M4.0 MUST MATCH. FBC 107.2.1, FBC EC C403.2.1 |
| | |
| | 2) IF AHU-3 IS NOT TO BE INSTALLED AT THIS TIME UNDER |
| | THIS PERMIT THEN IT MUST BE REMOVED FROM THIS PROJECT |
| | DOCUMENTS. FBC 107.2.1 |
| | |
| | 3) THE TABLES ON M3.1 ARE IDENTIFIED AS ASHRAE 62.1 |
| | PRESSURIZATION CALCULATION, PLEASE IDENTIFY THESE AS |
| | MINIMUM VENTILATION RATES IN BREATHING ZONE AS THEY ARE |
| | TITLE IN THE REFERENCE. PLEASE ALSO LABEL THE SPACE |
| | NAMES ACCORDING TO THE MINIMUM VENTILATION TABLES SO I |
| | CAN CORRECTLY COMPARE YOUR CALCULATIONS TO THE TABLE |
| | USED. FBC 107.2.1 PLEASE REMEMBER THAT IF UNIT 3 IS NOT |
| | INSTALLED UNDER THIS PERMIT IT WILL NOT BE COUNTED IN |
| | THE OUTDOOR AIR CALCULATIONS. |
| | |
| | 4) I DO NOT SEE A RESPONSE TO COMMENT (7) OF PREVIOUS |
| | CYCLE: PLEASE PROVIDE THE MANUFACTURING PROCESS IN THIS |
| | FACILITY. FBC 107.2.1 |
| | |
| | 5) I DO NOT SEE A RESPONSE TO COMMENT (8) OF PREVIOUS |
| | CYCLE: PLEASE PROVIDE THE EQUIPMENT SPECIFICATION |
| | SHEETS. FBC 107.2.1 |
| | |
| | 6) I DO NOT SEE A RESPONSE TO COMMENT (9) OF PREVIOUS |
| | CYCLE: PLEASE LIST ALL MATERIALS TO BE STORED IN THIS |
| | FACILITY AND THEIR QUANTITIES. FBC 107.2.1 |
| | |
| | 7) I DO NOT SEE A RESPONSE TO COMMENT (10) OF PREVIOUS |
| | CYCLE: WHAT IS THE OCCUPANCY ABOVE THE TENANT SPACE? |
| | |
| | 8) THE COFFEE ROASTER MANUFACTURER MUST PROVIDE |
| | INSTALLATION INSTRUCTIONS FOR THE EXHAUST DUCT SYSTEM |
| | FOR THE ROASTERS. FBC FG TABLE 503.4 |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |