Plan Review Notes
Plan Review Notes For Permit 21020294
Permit Number 21020294
Review Stop P
Sequence Number 2
Notes
Date Text
2021-05-27 16:50:302ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21020294
 5/27/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS FROM THE 1ST
 REVIEW ARE MARKED OR FAILED. NOTES HAVE BEEN ADDED TO
 FAILED COMMENT FOR FURTHER CLARIFICATION.
  
 1) PASSED. SHEET G1.0: PLEASE UPDATE THE APPLICABLE
 CODES TO THE FBC 2020 7TH EDITION.
  
 2) SHEETS A1.0 & A1.1: ACCESSIBILITY CORRECTIONS- FBC
 ACC.
  
 A) PASSED. THE TOILET COMPARTMENT SHALL NOT SWING INTO
 THE CLEAR FLOOR SPACE FOR THE LAVATORY- SECTION
 603.2.3.
 B) FAILED. GRAB BAR NOT POSITIONED ACCORDING TO
 SECTIONS AND FIGURES 604.5.1 & 604.5.2. SHEET A1: THE
 SIDE GRAB BAR SHALL EXTEND A MINIMUM OF 54 INCHES FROM
 THE WALL. SHEET A1.1: REAR GRAB BAR NOT CENTERED
 PROPERLY.
 C) PASSED. CENTERLINE OF THE TOILET PAPER DISPENSER
 MEASURED FROM THE FRONTS OF THE WATER CLOSET NOT SHOWN-
 SECTION 604.7.
 D) PASSED. HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR
 TO THE REFLECTIVE SURFACE NOT SHOWN- SECTION 603.3.
 3) PASSED. A1.1: SHOW THE DEPTH OF THE WOMEN'S TOILET
 COMPARTMENTS- SECTION 405.3.1 FBC P.
  
 4) PASSED. LSP: THE OCCUPANT LOAD AND PLUMBING FIXTURE
 CALCULATIONS TABLE DO NOT INCLUDE THE LOAD FROM THE 2ND
 FLOOR- TABLE 403.1 FBC P.
  
 5) FAILED. P2.0 & P3.0: A GREASE INTERCEPTOR IS
 REQUIRED TO RECEIVE THE DRAINAGE FROM THE FIXTURES IN
 THE RETAIL BAR, COFFEE BREWING, ROASTING, AND UTILITY
 AREAS. FIXTURES REQUIRED TO DRAIN INTO THE INTERCEPTOR
 INCLUDE THE 3-COMPARTMENT SINKS, DISHWASHER, FLOOR
 SINKS, AND TRENCH DRAIN. PLEASE REVISE THE DRAWINGS AND
 DETAILS TO SHOW COMPLIANCE- SECTION 1003.3.1 FBC P. A)
 PROVIDE GREASE WASTE CALCULATIONS IN ACCORDANCE WITH
 SECTIONS 1003.3.5 OR 1003.3.7 FBC P. SHEET P2: THE
 HANDSINK IS NOT ALLOWED TO DRAIN INTO THE GREASE
 INTERCEPTOR- SECTION 1003.3.1 FBC P. A) SHEET P5.0: THE
 SIZING CALCULATIONS ARE FOR A RESTAURANT AND NOT
 APLLICABLE TO THE PROPOSED OCCUPANCY. PLEASE PROVIDE
 CALCULATIONS IN ACCORDANCE WITH SECTION 1003.3.5 FBC P.
  
 6) PASSED. P2.0- NOTE 16, & P3.0: A SEPARATE PERMIT IS
 REQUIRED FOR THE NEW BACKFLOW PREVENTER. PLEASE NOTE- A
 FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A
 SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW
 PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND SEC.
 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE
 TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION.
  
 7) FAILED. P2.0 & P3.0: PLEASE SHOW THE LOCATIONS OF
 AND PROVIDE EQUIPMENT SCHEDULES FOR REQUIRED THE
 BACKFLOW PREVENTERS FOR WATER LINES SUPPLYING THE
 PUMPHOUSE EQUIPMENT IN THE RETAIL BAR, AND COFFEE
 BREWING AREAS- SECTION 608.3 FBC P. THE BF PREVENTERS
 SHALL BE LOCATED ON THE INDIVIDUAL BRANCH LINES
 SUPPLYING EACH FIXTURE OR APPLIANCE IN ACCORDANCE WITH
 608.3. KEYNOTE 19 SHOWS THE BF PREVENTERS ON THE MAIN
 LINES SUPPLYING THE GROUPED FIXTRURES AND APPLIANCES.
 PLEASE NOTE NO BF PREVENTERS ARE SHOWN FOR THE
 DISHWASHER AND ICE MACHINE- #32 & #33. THE DESIGN
 PROFESSIONAL WANT TO PROVIDE A GENERAL KEYNOTE FOR
 REQUIRED INDIVIDUAL BF PREVENTERS SAND PLACE THAST NOTE
 AL ALL LOCATIONS.
  
 8) PASSED. P2.0 & P3.0: PLEASE INCLUDE THE FLOOR SINKS
 AND THE TRENCH DRAIN IN THE FIXTURE SCHEDULE- SECTION
 413 FBC P.
  
 9) PASSED. P2.0 & P3.0: PLEASE INCLUDE THE WALL HYDRANT
 AND HOSE BIBS IN THE FIXTURE SCHEDULE- SECTIONS 412.6
 AND 608.16.4.2 FBC P.
  
 10) FAILED. P2.0 & P3.0 INDICATE HOW TEMPERED WATER
 WILL BE PROVIDED TO THE LAVATORIES- SEE SECTIONS 419.5
 & 607.2.1 FBC P. MIXING VALVE AT LAVATORIES NOT
 PROVIDED .
  
 11) PASSED. P2.0 & P3.0: SHOW THE 2-WAY CLEANOUT IN THE
 SANITARY RISER- SECTION 708.1.3 FBC P.
  
 12) FAILED. P4.0: PROVIDE AN INDIRECT WASTE DETAIL FOR
 THE 3-COMPARTMENT SINKS- SECTION 802.1.1 FBC P. NOT
 PROVIDED.
  
 13) PASSED. P4.0: PROVIDE A WATER HEATER PLUMBING
 PIPING DIAGRAM SHOWING CW, HW, & HWR CONNECTIONS,
 LOCATIONS OF CHECK VALVES, RECIRCULATION PUMP,
 EXPANSION TANK, RELIEF VALVE, DRAIN PAN AND PAN LINE-
 SECTION- 501 FBC P.
  
 14) PASSED. P4.0: PROVIDE EQUIPMENT SCHEDULES FOR THE
 WATER HEATER, AND EXPANSION TANK- SECTIONS 501 & 607
 FBC P.
  
 15) FAILED. PROVIDE A CIVIL OR SITE PLAN SHOWING THE
 POINTS OF CONNECTIONS TO THE MAIN WATER SERVICE AND
 SEWER PIPES- SECTION 107.2.1 WPB. NOT PROVIDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  