| 2021-05-27 16:50:30 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21020294 |
| | 5/27/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. COMMENTS FROM THE 1ST |
| | REVIEW ARE MARKED OR FAILED. NOTES HAVE BEEN ADDED TO |
| | FAILED COMMENT FOR FURTHER CLARIFICATION. |
| | |
| | 1) PASSED. SHEET G1.0: PLEASE UPDATE THE APPLICABLE |
| | CODES TO THE FBC 2020 7TH EDITION. |
| | |
| | 2) SHEETS A1.0 & A1.1: ACCESSIBILITY CORRECTIONS- FBC |
| | ACC. |
| | |
| | A) PASSED. THE TOILET COMPARTMENT SHALL NOT SWING INTO |
| | THE CLEAR FLOOR SPACE FOR THE LAVATORY- SECTION |
| | 603.2.3. |
| | B) FAILED. GRAB BAR NOT POSITIONED ACCORDING TO |
| | SECTIONS AND FIGURES 604.5.1 & 604.5.2. SHEET A1: THE |
| | SIDE GRAB BAR SHALL EXTEND A MINIMUM OF 54 INCHES FROM |
| | THE WALL. SHEET A1.1: REAR GRAB BAR NOT CENTERED |
| | PROPERLY. |
| | C) PASSED. CENTERLINE OF THE TOILET PAPER DISPENSER |
| | MEASURED FROM THE FRONTS OF THE WATER CLOSET NOT SHOWN- |
| | SECTION 604.7. |
| | D) PASSED. HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR |
| | TO THE REFLECTIVE SURFACE NOT SHOWN- SECTION 603.3. |
| | 3) PASSED. A1.1: SHOW THE DEPTH OF THE WOMEN'S TOILET |
| | COMPARTMENTS- SECTION 405.3.1 FBC P. |
| | |
| | 4) PASSED. LSP: THE OCCUPANT LOAD AND PLUMBING FIXTURE |
| | CALCULATIONS TABLE DO NOT INCLUDE THE LOAD FROM THE 2ND |
| | FLOOR- TABLE 403.1 FBC P. |
| | |
| | 5) FAILED. P2.0 & P3.0: A GREASE INTERCEPTOR IS |
| | REQUIRED TO RECEIVE THE DRAINAGE FROM THE FIXTURES IN |
| | THE RETAIL BAR, COFFEE BREWING, ROASTING, AND UTILITY |
| | AREAS. FIXTURES REQUIRED TO DRAIN INTO THE INTERCEPTOR |
| | INCLUDE THE 3-COMPARTMENT SINKS, DISHWASHER, FLOOR |
| | SINKS, AND TRENCH DRAIN. PLEASE REVISE THE DRAWINGS AND |
| | DETAILS TO SHOW COMPLIANCE- SECTION 1003.3.1 FBC P. A) |
| | PROVIDE GREASE WASTE CALCULATIONS IN ACCORDANCE WITH |
| | SECTIONS 1003.3.5 OR 1003.3.7 FBC P. SHEET P2: THE |
| | HANDSINK IS NOT ALLOWED TO DRAIN INTO THE GREASE |
| | INTERCEPTOR- SECTION 1003.3.1 FBC P. A) SHEET P5.0: THE |
| | SIZING CALCULATIONS ARE FOR A RESTAURANT AND NOT |
| | APLLICABLE TO THE PROPOSED OCCUPANCY. PLEASE PROVIDE |
| | CALCULATIONS IN ACCORDANCE WITH SECTION 1003.3.5 FBC P. |
| | |
| | 6) PASSED. P2.0- NOTE 16, & P3.0: A SEPARATE PERMIT IS |
| | REQUIRED FOR THE NEW BACKFLOW PREVENTER. PLEASE NOTE- A |
| | FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A |
| | SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW |
| | PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND SEC. |
| | 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE |
| | TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| | PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| | PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS |
| | DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. |
| | |
| | 7) FAILED. P2.0 & P3.0: PLEASE SHOW THE LOCATIONS OF |
| | AND PROVIDE EQUIPMENT SCHEDULES FOR REQUIRED THE |
| | BACKFLOW PREVENTERS FOR WATER LINES SUPPLYING THE |
| | PUMPHOUSE EQUIPMENT IN THE RETAIL BAR, AND COFFEE |
| | BREWING AREAS- SECTION 608.3 FBC P. THE BF PREVENTERS |
| | SHALL BE LOCATED ON THE INDIVIDUAL BRANCH LINES |
| | SUPPLYING EACH FIXTURE OR APPLIANCE IN ACCORDANCE WITH |
| | 608.3. KEYNOTE 19 SHOWS THE BF PREVENTERS ON THE MAIN |
| | LINES SUPPLYING THE GROUPED FIXTRURES AND APPLIANCES. |
| | PLEASE NOTE NO BF PREVENTERS ARE SHOWN FOR THE |
| | DISHWASHER AND ICE MACHINE- #32 & #33. THE DESIGN |
| | PROFESSIONAL WANT TO PROVIDE A GENERAL KEYNOTE FOR |
| | REQUIRED INDIVIDUAL BF PREVENTERS SAND PLACE THAST NOTE |
| | AL ALL LOCATIONS. |
| | |
| | 8) PASSED. P2.0 & P3.0: PLEASE INCLUDE THE FLOOR SINKS |
| | AND THE TRENCH DRAIN IN THE FIXTURE SCHEDULE- SECTION |
| | 413 FBC P. |
| | |
| | 9) PASSED. P2.0 & P3.0: PLEASE INCLUDE THE WALL HYDRANT |
| | AND HOSE BIBS IN THE FIXTURE SCHEDULE- SECTIONS 412.6 |
| | AND 608.16.4.2 FBC P. |
| | |
| | 10) FAILED. P2.0 & P3.0 INDICATE HOW TEMPERED WATER |
| | WILL BE PROVIDED TO THE LAVATORIES- SEE SECTIONS 419.5 |
| | & 607.2.1 FBC P. MIXING VALVE AT LAVATORIES NOT |
| | PROVIDED . |
| | |
| | 11) PASSED. P2.0 & P3.0: SHOW THE 2-WAY CLEANOUT IN THE |
| | SANITARY RISER- SECTION 708.1.3 FBC P. |
| | |
| | 12) FAILED. P4.0: PROVIDE AN INDIRECT WASTE DETAIL FOR |
| | THE 3-COMPARTMENT SINKS- SECTION 802.1.1 FBC P. NOT |
| | PROVIDED. |
| | |
| | 13) PASSED. P4.0: PROVIDE A WATER HEATER PLUMBING |
| | PIPING DIAGRAM SHOWING CW, HW, & HWR CONNECTIONS, |
| | LOCATIONS OF CHECK VALVES, RECIRCULATION PUMP, |
| | EXPANSION TANK, RELIEF VALVE, DRAIN PAN AND PAN LINE- |
| | SECTION- 501 FBC P. |
| | |
| | 14) PASSED. P4.0: PROVIDE EQUIPMENT SCHEDULES FOR THE |
| | WATER HEATER, AND EXPANSION TANK- SECTIONS 501 & 607 |
| | FBC P. |
| | |
| | 15) FAILED. PROVIDE A CIVIL OR SITE PLAN SHOWING THE |
| | POINTS OF CONNECTIONS TO THE MAIN WATER SERVICE AND |
| | SEWER PIPES- SECTION 107.2.1 WPB. NOT PROVIDED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |