Plan Review Notes
Plan Review Notes For Permit 21020294
Permit Number 21020294
Review Stop G
Sequence Number 2
Notes
Date Text
2021-05-27 17:53:092ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 21020294
 5/27/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 NFPA 58
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS FROM THE 1ST
 REVIEW ARE MARKED OR FAILED. NOTES HAVE BEEN ADDED TO
 FAILED COMMENT FOR FURTHER CLARIFICATION.
  
 1) PASSED. SHEET P3.0, GAS NOTE 3: PLEASE UPDATE THE
 2017 FBC CODE REFERENCE TO THE FBC 2020 7TH EDITION
 FUEL GAS CODE.
  
 2) PASSED. P3.0, GAS ISO: LABEL THE LP TANK LOCATION-
 SECTION 107.2.1 WPB.
  
 3) FAILED. P2.0 P3.0: SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE LP TANKS SHOWING THE TANKS ARE
 DESIGNED, FABRICATED, TESTED AND MARKED (STAMPED) IN
 ACCORDANCE WITH THE REGULATIONS AS REQUIRED BY THE
 REGULATORY AGENCIES AND COMPLIANCE STANDARDS LISTED IN
 SECTION 5.2.1.1 NFPA 58. CURRENTLY THE LP TANK AND
 SYSTEM UNDER PERMIT 21021293 ARE NOT UNDER REVIEW.
 PLEASE CONTACT [email protected].
  
 4) FAILED. P2.0 P3.0: PROVIDE LP TANK INSTALLATION
 DETAILS SHOWING THE REQUIRED MASONRY OR OTHER
 NON-COMBUSTIBLE STRUCTURAL SUPPORTS LOCATED ON CONCRETE
 OR MASONRY FOUNDATION WITH THE CONTAINER SUPPORTS-
 SECTION 6.6.3.1 NFPA 58. SHOW HOW THE TANK WILL BE
 ANCHORED TO RESIST WIND LOAD AND WIND PRESSURES-
 SECTION 6.6.3.3 (D) NFPA 58. CURRENTLY THE LP TANK AND
 SYSTEM UNDER PERMIT 21021293 ARE NOT UNDER REVIEW.
 PLEASE CONTACT [email protected].
  
 5) FAILED. P2.0 & P3.0: BASED ON GALLON SIZES OF THE
 TANKS, AND MANIFOLDING OF THE TANKS, PROVIDE CLEARANCE
 DISTANCES FOR THE TANK RELIEF VALVES TO THE REAR DOOR
 OPENING, MECHANICAL AIR INTAKES, DIRECT VENT SYSTEM,
 AND EXTERIOR SOURCES OF IGNITION- SECTIONS 6.4.4.3 &
 6.4.4.4 AND TABLE 6.4.4.3 NFPA 58. NOT PROVIDED.
  
 6) FAILED. P2.0 & P3.0: REFER TO SECTIONS 6.10.1.4 &
 6.10.2.1 NFPA AND SHOW COMPLIANCE ON THE PLAN: A
 TWO-STAGE REGULATOR SYSTEM, AN INTEGRAL TWO-STAGE
 REGULATOR OR A 2 PSI REGULATOR IS REQUIRED FOR THE
 SYSTEM BASED ON 11 IN. WC. PLEASE SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE REGULATOR. NOT PROVIDED.
  
 7) FAILED. P2.0 & P3.0: REFER TO SECTION 6.10.1.7 NFPA
 58 AND INDICATE THE REQUIRED CLEARANCES FOR REGULATOR
 PRESSURE RELIEF VENT DISCHARGES TO THE DOOR OPENING,
 MECHANICAL AIR INTAKES, DIRECT VENT SYSTEM, AND ANY
 SOURCE OF IGNITION. NOT PROVIDED.
  
 8) FAILED. P3.0: SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE TANKLESS WATER HEATER AND THE CONCENTRIC VENT
 SYSTEM- SECTION 624.1 FBC FG. PLEASE NOTE THE SPECS MAY
 BE DEFERRED SUBMITTALS BY REQUEST- SECTION 107.3.4.1
 WPB. NOT PROVIDED.
  
 9) PASSED. P3.0: PROVIDE A CONDENSATE DISPOSAL PLAN FOR
 THE WATER HEATER- SECTIONS 307.2- 307.6 FBC FG. PLEASE
 NOTE THE MANUFACTURER'S SPECIFICATIONS MAY RECOMMEND
 INSTALLATION OF AN ACID NEUTRALIZING DEVICE FOR THE
 CONDENSATE.
  
 10) FAILED. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THE GAS-FIRED PROBAT L12 AND THE DIEDRICH IR-1-
 SECTION- 305.1 FBC FG. THE SPECS MAY BE DEFERRED
 SUBMITTALS BY REQUEST- SECTION 107.3.4.1 WPB.THE
 DIEDRICH SPECS NOT PROVIDED.
  
 11) FAILED. PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 PROBAT L12 AND DIEDRICH IR-1 AND INDICATE HOW THE
 COMBUSTION AIR WILL BE PROVIDED- SECTION 304.1 FBC FG.
 NOT PROVIDED ON P2 OR M3.1. IF PROVIDING COMBUSTION AIR
 MECHANICALLY PLEASE REFER TO SECTION 304.9 FBC FG AND
 PROVIDE THE CALCULATION.
  
 12) FAILED. PROVIDE VENTING DIAGRAMS AND SPECIFICATIONS
 FOR THE PROBAT L12 AND DIEDRICH IR-1- SECTIONS 305.1
 AND 503.1 FBC FG. THE VENTING DIAGRAM ON M2 IS
 INCOMPLETE. REFER TO SECTION 202 AND TABLE 503.4 AND
 SPECIFY THE TYPE OF VENT SYSTEM BASED ON THE CATEGORY
 OF THE APPLIANCES- CATEGORY I, II, III, OR IV. THE
 SUBMITTED SPECS FOR THE PROBAT INDICATES A 6- 8 INCH
 EXHAUST DUCT. PLEASE PROVIDE AN ENLARGED ELEVATION VIEW
 SHOWING THE VERTICAL EXHAUST DUCTS FROM EACH APPLIANCE
 AND HOW THEY ARE CONNECTING INTO THE 18 INCH HORIZONTAL
 DUCT. PLEASE CLARIFY HOW THE 18 INCH DUCT WAS SIZED AND
 PROVIDE DUCT MATERIAL SPECIFICATIONS. IS THE DUCT
 REQUIRED TO SLOPE? PLEASE REVIEW SECTIONS 503.6.9.1-
 503.7.9 AND PROVIDE COMPLETE DETAILS INCLDUDING HOW THE
 DUCT IS TO BE SUPPORTED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  