| 2021-05-27 17:53:09 | 2ND REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 21020294 |
| | 5/27/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | NFPA 58 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. COMMENTS FROM THE 1ST |
| | REVIEW ARE MARKED OR FAILED. NOTES HAVE BEEN ADDED TO |
| | FAILED COMMENT FOR FURTHER CLARIFICATION. |
| | |
| | 1) PASSED. SHEET P3.0, GAS NOTE 3: PLEASE UPDATE THE |
| | 2017 FBC CODE REFERENCE TO THE FBC 2020 7TH EDITION |
| | FUEL GAS CODE. |
| | |
| | 2) PASSED. P3.0, GAS ISO: LABEL THE LP TANK LOCATION- |
| | SECTION 107.2.1 WPB. |
| | |
| | 3) FAILED. P2.0 P3.0: SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE LP TANKS SHOWING THE TANKS ARE |
| | DESIGNED, FABRICATED, TESTED AND MARKED (STAMPED) IN |
| | ACCORDANCE WITH THE REGULATIONS AS REQUIRED BY THE |
| | REGULATORY AGENCIES AND COMPLIANCE STANDARDS LISTED IN |
| | SECTION 5.2.1.1 NFPA 58. CURRENTLY THE LP TANK AND |
| | SYSTEM UNDER PERMIT 21021293 ARE NOT UNDER REVIEW. |
| | PLEASE CONTACT [email protected]. |
| | |
| | 4) FAILED. P2.0 P3.0: PROVIDE LP TANK INSTALLATION |
| | DETAILS SHOWING THE REQUIRED MASONRY OR OTHER |
| | NON-COMBUSTIBLE STRUCTURAL SUPPORTS LOCATED ON CONCRETE |
| | OR MASONRY FOUNDATION WITH THE CONTAINER SUPPORTS- |
| | SECTION 6.6.3.1 NFPA 58. SHOW HOW THE TANK WILL BE |
| | ANCHORED TO RESIST WIND LOAD AND WIND PRESSURES- |
| | SECTION 6.6.3.3 (D) NFPA 58. CURRENTLY THE LP TANK AND |
| | SYSTEM UNDER PERMIT 21021293 ARE NOT UNDER REVIEW. |
| | PLEASE CONTACT [email protected]. |
| | |
| | 5) FAILED. P2.0 & P3.0: BASED ON GALLON SIZES OF THE |
| | TANKS, AND MANIFOLDING OF THE TANKS, PROVIDE CLEARANCE |
| | DISTANCES FOR THE TANK RELIEF VALVES TO THE REAR DOOR |
| | OPENING, MECHANICAL AIR INTAKES, DIRECT VENT SYSTEM, |
| | AND EXTERIOR SOURCES OF IGNITION- SECTIONS 6.4.4.3 & |
| | 6.4.4.4 AND TABLE 6.4.4.3 NFPA 58. NOT PROVIDED. |
| | |
| | 6) FAILED. P2.0 & P3.0: REFER TO SECTIONS 6.10.1.4 & |
| | 6.10.2.1 NFPA AND SHOW COMPLIANCE ON THE PLAN: A |
| | TWO-STAGE REGULATOR SYSTEM, AN INTEGRAL TWO-STAGE |
| | REGULATOR OR A 2 PSI REGULATOR IS REQUIRED FOR THE |
| | SYSTEM BASED ON 11 IN. WC. PLEASE SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE REGULATOR. NOT PROVIDED. |
| | |
| | 7) FAILED. P2.0 & P3.0: REFER TO SECTION 6.10.1.7 NFPA |
| | 58 AND INDICATE THE REQUIRED CLEARANCES FOR REGULATOR |
| | PRESSURE RELIEF VENT DISCHARGES TO THE DOOR OPENING, |
| | MECHANICAL AIR INTAKES, DIRECT VENT SYSTEM, AND ANY |
| | SOURCE OF IGNITION. NOT PROVIDED. |
| | |
| | 8) FAILED. P3.0: SUBMIT MANUFACTURER'S SPECIFICATIONS |
| | FOR THE TANKLESS WATER HEATER AND THE CONCENTRIC VENT |
| | SYSTEM- SECTION 624.1 FBC FG. PLEASE NOTE THE SPECS MAY |
| | BE DEFERRED SUBMITTALS BY REQUEST- SECTION 107.3.4.1 |
| | WPB. NOT PROVIDED. |
| | |
| | 9) PASSED. P3.0: PROVIDE A CONDENSATE DISPOSAL PLAN FOR |
| | THE WATER HEATER- SECTIONS 307.2- 307.6 FBC FG. PLEASE |
| | NOTE THE MANUFACTURER'S SPECIFICATIONS MAY RECOMMEND |
| | INSTALLATION OF AN ACID NEUTRALIZING DEVICE FOR THE |
| | CONDENSATE. |
| | |
| | 10) FAILED. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR |
| | THE GAS-FIRED PROBAT L12 AND THE DIEDRICH IR-1- |
| | SECTION- 305.1 FBC FG. THE SPECS MAY BE DEFERRED |
| | SUBMITTALS BY REQUEST- SECTION 107.3.4.1 WPB.THE |
| | DIEDRICH SPECS NOT PROVIDED. |
| | |
| | 11) FAILED. PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| | PROBAT L12 AND DIEDRICH IR-1 AND INDICATE HOW THE |
| | COMBUSTION AIR WILL BE PROVIDED- SECTION 304.1 FBC FG. |
| | NOT PROVIDED ON P2 OR M3.1. IF PROVIDING COMBUSTION AIR |
| | MECHANICALLY PLEASE REFER TO SECTION 304.9 FBC FG AND |
| | PROVIDE THE CALCULATION. |
| | |
| | 12) FAILED. PROVIDE VENTING DIAGRAMS AND SPECIFICATIONS |
| | FOR THE PROBAT L12 AND DIEDRICH IR-1- SECTIONS 305.1 |
| | AND 503.1 FBC FG. THE VENTING DIAGRAM ON M2 IS |
| | INCOMPLETE. REFER TO SECTION 202 AND TABLE 503.4 AND |
| | SPECIFY THE TYPE OF VENT SYSTEM BASED ON THE CATEGORY |
| | OF THE APPLIANCES- CATEGORY I, II, III, OR IV. THE |
| | SUBMITTED SPECS FOR THE PROBAT INDICATES A 6- 8 INCH |
| | EXHAUST DUCT. PLEASE PROVIDE AN ENLARGED ELEVATION VIEW |
| | SHOWING THE VERTICAL EXHAUST DUCTS FROM EACH APPLIANCE |
| | AND HOW THEY ARE CONNECTING INTO THE 18 INCH HORIZONTAL |
| | DUCT. PLEASE CLARIFY HOW THE 18 INCH DUCT WAS SIZED AND |
| | PROVIDE DUCT MATERIAL SPECIFICATIONS. IS THE DUCT |
| | REQUIRED TO SLOPE? PLEASE REVIEW SECTIONS 503.6.9.1- |
| | 503.7.9 AND PROVIDE COMPLETE DETAILS INCLDUDING HOW THE |
| | DUCT IS TO BE SUPPORTED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |