| 2021-03-11 18:19:40 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21020294 |
| | 3/11/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET G1.0: PLEASE UPDATE THE APPLICABLE CODES TO |
| | THE FBC 2020 7TH EDITION. |
| | |
| | 2) SHEETS A1.0 & A1.1: ACCESSIBILITY CORRECTIONS- FBC |
| | ACC. |
| | |
| | A) THE TOILET COMPARTMENT SHALL NOT SWING INTO THE |
| | CLEAR FLOOR SPACE FOR THE LAVATORY- SECTION 603.2.3. |
| | |
| | B) GRAB BAR NOT POSITIONED ACCORDING TO SECTIONS AND |
| | FIGURES 604.5.1 & 604.5.2. |
| | |
| | C) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSET NOT SHOWN- SECTION |
| | 604.7. |
| | |
| | D) HEIGHT OF THE MIRROR FROM THE FINISHED FLOOR TO THE |
| | REFLECTIVE SURFACE NOT SHOWN- SECTION 603.3. |
| | |
| | 3) A1.1: SHOW THE DEPTH OF THE WOMEN'S TOILET |
| | COMPARTMENTS- SECTION 405.3.1 FBC P. |
| | |
| | 4) LSP: THE OCCUPANT LOAD AND PLUMBING FIXTURE |
| | CALCULATIONS TABLE DO NOT INCLUDE THE LOAD FROM THE 2ND |
| | FLOOR- TABLE 403.1 FBC P. |
| | |
| | 5) P2.0 & P3.0: A GREASE INTERCEPTOR IS REQUIRED TO |
| | RECEIVE THE DRAINAGE FROM THE FIXTURES IN THE RETAIL |
| | BAR, COFFEE BREWING, ROASTING, AND UTILITY AREAS. |
| | FIXTURES REQUIRED TO DRAIN INTO THE INTERCEPTOR INCLUDE |
| | THE 3-COMPARTMENT SINKS, DISHWASHER, FLOOR SINKS, AND |
| | TRENCH DRAIN. PLEASE REVISE THE DRAWINGS AND DETAILS TO |
| | SHOW COMPLIANCE- SECTION 1003.3.1 FBC P. A) PROVIDE |
| | GREASE WASTE CALCULATIONS IN ACCORDANCE WITH SECTIONS |
| | 1003.3.5 OR 1003.3.7 FBC P. |
| | |
| | 6) P2.0- NOTE 16, & P3.0: A SEPARATE PERMIT IS REQUIRED |
| | FOR THE NEW BACKFLOW PREVENTER. PLEASE NOTE- A FL. |
| | LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A SEPARATE |
| | PERMIT FOR INSTALLATION OF THE BACKFLOW PREVENTER IN |
| | ACCORDANCE WITH SECTION 105.1 WPB AND SEC. 90-33 WPB |
| | CODE OF ORDINANCES. THE DEVICE SHALL BE TESTED AND |
| | CERTIFIED BY THE WPB UTILITIES DEPARTMENT PRIOR TO |
| | FINAL INSPECTION BY THE BUILDING DEPARTMENT. PLEASE |
| | CONTACT THE WPB UTILITIES CENTRAL OPERATIONS DEPT.AT |
| | 561-822-2210 FOR FURTHER INFORMATION. |
| | |
| | 7) P2.0 & P3.0: PLEASE SHOW THE LOCATIONS OF AND |
| | PROVIDE EQUIPMENT SCHEDULES FOR REQUIRED THE BACKFLOW |
| | PREVENTERS FOR WATER LINES SUPPLYING THE PUMPHOUSE |
| | EQUIPMENT IN THE RETAIL BAR, AND COFFEE BREWING AREAS- |
| | SECTION 608.3 FBC P. |
| | |
| | 8) P2.0 & P3.0: PLEASE INCLUDE THE FLOOR SINKS AND THE |
| | TRENCH DRAIN IN THE FIXTURE SCHEDULE- SECTION 413 FBC |
| | P. |
| | |
| | 9) P2.0 & P3.0: PLEASE INCLUDE THE WALL HYDRANT AND |
| | HOSE BIBS IN THE FIXTURE SCHEDULE- SECTIONS 412.6 AND |
| | 608.16.4.2 FBC P. |
| | |
| | 10) P2.0 & P3.0 INDICATE HOW TEMPERED WATER WILL BE |
| | PROVIDED TO THE LAVATORIES- SEE SECTIONS 419.5 & |
| | 607.2.1 FBC P. |
| | |
| | 11) P2.0 & P3.0: SHOW THE 2-WAY CLEANOUT IN THE |
| | SANITARY RISER- SECTION 708.1.3 FBC P. |
| | |
| | 12) P4.0: PROVIDE AN INDIRECT WASTE DETAIL FOR THE |
| | 3-COMPARTMENT SINKS- SECTION 802.1.1 FBC P. |
| | |
| | 13) P4.0: PROVIDE A WATER HEATER PLUMBING PIPING |
| | DIAGRAM SHOWING CW, HW, & HWR CONNECTIONS, LOCATIONS OF |
| | CHECK VALVES, RECIRCULATION PUMP, EXPANSION TANK, |
| | RELIEF VALVE, DRAIN PAN AND PAN LINE- SECTION- 501 FBC |
| | P. |
| | |
| | 14) P4.0: PROVIDE EQUIPMENT SCHEDULES FOR THE WATER |
| | HEATER, AND EXPANSION TANK- SECTIONS 501 & 607 FBC P. |
| | |
| | 15) PROVIDE A CIVIL OR SITE PLAN SHOWING THE POINTS OF |
| | CONNECTIONS TO THE MAIN WATER SERVICE AND SEWER PIPES- |
| | SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |