Plan Review Notes
Plan Review Notes For Permit 21020294
Permit Number 21020294
Review Stop G
Sequence Number 1
Notes
Date Text
2021-04-07 12:00:251ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 21020294
 3/11/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 NFPA 58
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P3.0, GAS NOTE 3: PLEASE UPDATE THE 2017 FBC
 CODE REFERENCE TO THE FBC 2020 7TH EDITION FUEL GAS
 CODE.
 2) P3.0, GAS ISO: LABEL THE LP TANK LOCATION- SECTION
 107.2.1 WPB.
  
 3) P2.0 P3.0: SUBMIT MANUFACTURER?S SPECIFICATIONS FOR
 THE LP TANKS SHOWING THE TANKS ARE DESIGNED,
 FABRICATED, TESTED AND MARKED (STAMPED) IN ACCORDANCE
 WITH THE REGULATIONS AS REQUIRED BY THE REGULATORY
 AGENCIES AND COMPLIANCE STANDARDS LISTED IN SECTION
 5.2.1.1 NFPA 58.
  
 4) P2.0 P3.0: PROVIDE LP TANK INSTALLATION DETAILS
 SHOWING THE REQUIRED MASONRY OR OTHER NON-COMBUSTIBLE
 STRUCTURAL SUPPORTS LOCATED ON CONCRETE OR MASONRY
 FOUNDATION WITH THE CONTAINER SUPPORTS- SECTION 6.6.3.1
 NFPA 58. SHOW HOW THE TANK WILL BE ANCHORED TO RESIST
 WIND LOAD AND WIND PRESSURES- SECTION 6.6.3.3 (D) NFPA
 58.
  
 5) P2.0 & P3.0: BASED ON GALLON SIZES OF THE TANKS, AND
 MANIFOLDING OF THE TANKS, PROVIDE CLEARANCE DISTANCES
 FOR THE TANK RELIEF VALVES TO THE REAR DOOR OPENING,
 MECHANICAL AIR INTAKES, DIRECT VENT SYSTEM, AND
 EXTERIOR SOURCES OF IGNITION- SECTIONS 6.4.4.3 &
 6.4.4.4 AND TABLE 6.4.4.3 NFPA 58.
  
 6) P2.0 & P3.0: REFER TO SECTIONS 6.10.1.4 & 6.10.2.1
 NFPA AND SHOW COMPLIANCE ON THE PLAN: A TWO-STAGE
 REGULATOR SYSTEM, AN INTEGRAL TWO-STAGE REGULATOR OR A
 2 PSI REGULATOR IS REQUIRED FOR THE SYSTEM BASED ON 11
 IN. WC. PLEASE SUBMIT MANUFACTURER?S SPECIFICATIONS FOR
 THE REGULATOR.
  
 7) P2.0 & P3.0: REFER TO SECTION 6.10.1.7 NFPA 58 AND
 INDICATE THE REQUIRED CLEARANCES FOR REGULATOR PRESSURE
 RELIEF VENT DISCHARGES TO THE DOOR OPENING, MECHANICAL
 AIR INTAKES, DIRECT VENT SYSTEM, AND ANY SOURCE OF
 IGNITION.
  
 8) P3.0: SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 TANKLESS WATER HEATER AND THE CONCENTRIC VENT SYSTEM-
 SECTION 624.1 FBC FG. PLEASE NOTE THE SPECS MAY BE
 DEFERRED SUBMITTALS BY REQUEST- SECTION 107.3.4.1 WPB.
  
 9) P3.0: PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE
 WATER HEATER- SECTIONS 307.2- 307.6 FBC FG. PLEASE NOTE
 THE MANUFACTURER?S SPECIFICATIONS MAY RECOMMEND
 INSTALLATION OF AN ACID NEUTRALIZING DEVICE FOR THE
 CONDENSATE.
  
 10) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 GAS-FIRED PROBAT L12 AND THE DIEDRICH IR-1- SECTION-
 305.1 FBC FG. THE SPECS MAY BE DEFERRED SUBMITTALS BY
 REQUEST- SECTION 107.3.4.1 WPB.
  
 11) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE PROBAT
 L12 AND DIEDRICH IR-1 AND INDICATE HOW THE COMBUSTION
 AIR WILL BE PROVIDED- SECTION 304.1 FBC FG.
  
 12) PROVIDE VENTING DIAGRAMS AND SPECIFICATIONS FOR THE
 PROBAT L12 AND DIEDRICH IR-1- SECTIONS 305.1 AND 503.1
 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  