| 2021-04-07 12:00:25 | 1ST REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 21020294 |
| | 3/11/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | NFPA 58 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P3.0, GAS NOTE 3: PLEASE UPDATE THE 2017 FBC |
| | CODE REFERENCE TO THE FBC 2020 7TH EDITION FUEL GAS |
| | CODE. |
| | 2) P3.0, GAS ISO: LABEL THE LP TANK LOCATION- SECTION |
| | 107.2.1 WPB. |
| | |
| | 3) P2.0 P3.0: SUBMIT MANUFACTURER?S SPECIFICATIONS FOR |
| | THE LP TANKS SHOWING THE TANKS ARE DESIGNED, |
| | FABRICATED, TESTED AND MARKED (STAMPED) IN ACCORDANCE |
| | WITH THE REGULATIONS AS REQUIRED BY THE REGULATORY |
| | AGENCIES AND COMPLIANCE STANDARDS LISTED IN SECTION |
| | 5.2.1.1 NFPA 58. |
| | |
| | 4) P2.0 P3.0: PROVIDE LP TANK INSTALLATION DETAILS |
| | SHOWING THE REQUIRED MASONRY OR OTHER NON-COMBUSTIBLE |
| | STRUCTURAL SUPPORTS LOCATED ON CONCRETE OR MASONRY |
| | FOUNDATION WITH THE CONTAINER SUPPORTS- SECTION 6.6.3.1 |
| | NFPA 58. SHOW HOW THE TANK WILL BE ANCHORED TO RESIST |
| | WIND LOAD AND WIND PRESSURES- SECTION 6.6.3.3 (D) NFPA |
| | 58. |
| | |
| | 5) P2.0 & P3.0: BASED ON GALLON SIZES OF THE TANKS, AND |
| | MANIFOLDING OF THE TANKS, PROVIDE CLEARANCE DISTANCES |
| | FOR THE TANK RELIEF VALVES TO THE REAR DOOR OPENING, |
| | MECHANICAL AIR INTAKES, DIRECT VENT SYSTEM, AND |
| | EXTERIOR SOURCES OF IGNITION- SECTIONS 6.4.4.3 & |
| | 6.4.4.4 AND TABLE 6.4.4.3 NFPA 58. |
| | |
| | 6) P2.0 & P3.0: REFER TO SECTIONS 6.10.1.4 & 6.10.2.1 |
| | NFPA AND SHOW COMPLIANCE ON THE PLAN: A TWO-STAGE |
| | REGULATOR SYSTEM, AN INTEGRAL TWO-STAGE REGULATOR OR A |
| | 2 PSI REGULATOR IS REQUIRED FOR THE SYSTEM BASED ON 11 |
| | IN. WC. PLEASE SUBMIT MANUFACTURER?S SPECIFICATIONS FOR |
| | THE REGULATOR. |
| | |
| | 7) P2.0 & P3.0: REFER TO SECTION 6.10.1.7 NFPA 58 AND |
| | INDICATE THE REQUIRED CLEARANCES FOR REGULATOR PRESSURE |
| | RELIEF VENT DISCHARGES TO THE DOOR OPENING, MECHANICAL |
| | AIR INTAKES, DIRECT VENT SYSTEM, AND ANY SOURCE OF |
| | IGNITION. |
| | |
| | 8) P3.0: SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | TANKLESS WATER HEATER AND THE CONCENTRIC VENT SYSTEM- |
| | SECTION 624.1 FBC FG. PLEASE NOTE THE SPECS MAY BE |
| | DEFERRED SUBMITTALS BY REQUEST- SECTION 107.3.4.1 WPB. |
| | |
| | 9) P3.0: PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE |
| | WATER HEATER- SECTIONS 307.2- 307.6 FBC FG. PLEASE NOTE |
| | THE MANUFACTURER?S SPECIFICATIONS MAY RECOMMEND |
| | INSTALLATION OF AN ACID NEUTRALIZING DEVICE FOR THE |
| | CONDENSATE. |
| | |
| | 10) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | GAS-FIRED PROBAT L12 AND THE DIEDRICH IR-1- SECTION- |
| | 305.1 FBC FG. THE SPECS MAY BE DEFERRED SUBMITTALS BY |
| | REQUEST- SECTION 107.3.4.1 WPB. |
| | |
| | 11) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE PROBAT |
| | L12 AND DIEDRICH IR-1 AND INDICATE HOW THE COMBUSTION |
| | AIR WILL BE PROVIDED- SECTION 304.1 FBC FG. |
| | |
| | 12) PROVIDE VENTING DIAGRAMS AND SPECIFICATIONS FOR THE |
| | PROBAT L12 AND DIEDRICH IR-1- SECTIONS 305.1 AND 503.1 |
| | FBC FG. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |