| 2021-02-22 15:20:04 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE INSUFFICIENT DETAIL PROVIDED FOR THE TYPE OF |
| | PROCESSING THAT IS BEING PROPOSED. |
| | |
| | PLEASE REVIEW AND PROVIDE A DETAILED NARRATIVE OF THE |
| | PROPOSED PROCESS. |
| | |
| | |
| | 1A) PLEASE PROVIDE A DETAILS AND MANUFACTURES'S |
| | SPECIFICATION SHEETS OF THE PROPOSED EQUIPMENT USED IN |
| | THE PROCESSING OF THE PROPOSED. |
| | |
| | PLEASE INCLUDE A SEQUENCE OF OPERATION, START TO |
| | FINISH. |
| | |
| | |
| | 2) SHEET G 1.0 - THERE IS NO INDICATION OF COMPLIANCE |
| | WITH THE CURRENT FLORIDA LIFE SAFETY CODE AND ALL OTHER |
| | APPLICABLE CODES. |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 7TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH |
| | INCLUDES THE 2018 EDITION OF NFPA 1 AND NFPA 101. |
| | |
| | THE BELOW LIST ARE THE MOST COMMON REFERENCED CODES: |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2016 EDITION. |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2016 EDITION. |
| | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 241, 2013 EDITION. |
| | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 10, 2018 EDITION. |
| | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2017 EDITION. |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE OF REVIEW AND |
| | COMPLIANCE. |
| | |
| | |
| | |
| | 3) SHEET F 2.0 - THERE IS INDICATIONS OF FIRE SPRINKLER |
| | WORK; HOWEVER, THERE IS NO INDICATION THAT ALL WORK, |
| | INCLUDING DEMO SHALL BE UNDER SEPARATE PERMIT & SHOP |
| | DRAWINGS. |
| | |
| | PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGMENT. |
| | |
| | |
| | 3A) SHEET G 1.0 - THERE IS INDICATIONS OF FIRE ALARM |
| | SYSTEM; HOWEVER, THERE IS NO INDICATION THAT ALL WORK, |
| | INCLUDING DEMO SHALL BE UNDER SEPARATE PERMIT & SHOP |
| | DRAWINGS. |
| | |
| | PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGMENT. |
| | |
| | |
| | 3B) THE EXISTING FIRE SPRINKLER & FIRE ALARM SYSTEMS |
| | SHALL REMIAN ACTIVE THROUGHOUT DEMO AND RECONSTRUCTION. |
| | |
| | PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGMENT. |
| | |
| | |
| | |
| | 4) SHEET LSP - THERE ARE INDICATIONS OF 1 HOUR FIRE |
| | RATED TENANT SEPARATION WALLS; HOWEVER, THERE ARE NO |
| | INDICATIONS OF THE OCCUPANCY CLASSIFICATION OF THE |
| | TENANTS ON EACH SIDE. |
| | |
| | PER NFPA 101, CH 6, |
| | |
| | 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.) |
| | |
| | 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED, |
| | EACH PART OF THE |
| | BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED |
| | IN THIS CHAPTER, |
| | SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY |
| | FIRE-RESISTIVE |
| | ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3, |
| | TABLE 6.1.14.4.1(A), |
| | AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED |
| | BY APPROVED |
| | EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY |
| | 6.1.14.4.6. |
| | |
| | 6.1.14.4.2 OCCUPANCY SEPARATIONS SHALL BE CLASSIFIED AS |
| | 3-HOUR FIRE |
| | RESISTANCE?RATED, 2-HOUR FIRE RESISTANCE?RATED, OR |
| | 1-HOUR FIRE |
| | RESISTANCE?RATED AND SHALL MEET THE REQUIREMENTS OF |
| | CHAPTER 8. |
| | 6.1.14.4.3 THE MINIMUM FIRE RESISTANCE RATING SPECIFIED |
| | IN TABLE |
| | 6.1.14.4.1(A) AND TABLE 6.1.14.4.1(B) SHALL BE |
| | PERMITTED TO BE |
| | REDUCED BY 1 HOUR, BUT IN NO CASE SHALL IT BE REDUCED |
| | TO LESS THAN 1 |
| | HOUR, WHERE THE BUILDING IS PROTECTED THROUGHOUT BY AN |
| | APPROVED |
| | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH |
| | 9.7.1.1(1) AND |
| | SUPERVISED IN ACCORDANCE WITH 9.7.2, UNLESS PROHIBITED |
| | BY THE |
| | DOUBLE-DAGGER FOOTNOTE ENTRIES IN THE TABLES. |
| | 6.1.14.4.4 OCCUPANCY SEPARATIONS SHALL BE VERTICAL, |
| | HORIZONTAL, OR |
| | BOTH OR, WHEN NECESSARY, OF SUCH OTHER FORM AS REQUIRED |
| | TO PROVIDE |
| | COMPLETE SEPARATION BETWEEN OCCUPANCY DIVISIONS IN THE |
| | BUILDING. |
| | |
| | PLEASE REVIEW AND PROVIDE THE REQUIRED FIRE SEPARATED |
| | RATINGS OR JUSTIFY EXISTING CONDITIONS. |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |