Plan Review Notes
Plan Review Notes For Permit 21020261
Permit Number 21020261
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-02-16 15:01:17THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET FA 1 - THERE ARE INDICATIONS OF CIRCUITS AND
 DEVICES ARE CLASS B.
  
 PLEASE REVIEW AND EXPLAIN WHAT HAPPENS IF A BREAK
 OCCURS, DO THE DEVICES DOWN LINE CONTINUE TO FUNCTION
 OR DOES IT SIMPLY GO TO TROUBLE?
  
 IT IS IMPERAIVE IN A HIGH RISE BUILDING THAT THE FA
 DEVICES ARE CLASS A OR THAT NO DEVICE IS NOT FUNCTIONAL
 DUE TO A BREAK OR TROUBLE?
  
  
  
 2) THERE ARE INDICATIONS OF TWO NFPA 72 CODE REFERENCES
 THAT DO NOT APPEAR TO BE RELATED TO THE INTENT.
  
 UNDER EXISTING POWER SUPPLY #N8 IT STATES REQUIRED
 OPERATION TIME FROM NFPA 72 10.2.6.2.2 & 10.5.6.3.1.
  
 I AM NOT SURE WHAT CODE EDITION IT IS CITING BUT NFPA
 72 2013 , DOES NOT HAVE THOSE REFERENCES.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 3) THERE ARE INDICATIONS OF TWO NFPA 72 CODE REFERENCES
 THAT DO NOT APPEAR TO BE RELATED TO THE INTENT.
  
 UNDER EXISTING NFS - 3030 FACP IT STATES REQUIRED
 OPERATION TIME FROM NFPA 72 4.4.1.5.2.2(1) &
 4.4.1.5.3.1
  
 I AM NOT SURE WHAT CODE EDITION IT IS CITING BUT NFPA
 72 2013 , DOES NOT HAVE THOSE REFERENCES.
  
 PLEASE REVIEW AND CORRECT.
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]