Plan Review Notes
Plan Review Notes For Permit 21020238
Permit Number 21020238
Review Stop M
Sequence Number 1
Notes
Date Text
2021-02-26 08:19:241ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21020238
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) THE ADDRESS ON THE ENERGY GAUGE REPORT DOES NOT
 MATCH THE ADDRESS ON THE PERMIT APPLICATION. PLEASE
 SUBMIT AN ENERGY GAUGE REPORT FOR THE ADDRESS OF THE
 PROJECT. FBC 107.2.1
  
 2) PLEASE SHOW THAT THIS REPAIR GARAGE WILL MEET TABLE
 403.3.1.1 OF THE FBC M FOR THE .75 CFM/SQ.FT. EXHAUST
 AIRFLOW RATE.
  
 3) SHEET M7-1 SHOWS A GREENHECK/EVH-660D LOUVER, PLEASE
 SHOW THE LOCATION OF THIS LOUVER ON SHEET M2-1. FBC
 107.2.1
  
 4) PLEASE PROVIDE THE NOA FOR THE GREENHECK/EVH-660D
 LOUVER. FBC 107.2.1
  
 5) PLEASE PROVIDE THE NOA FOR THE ROOF MOUNTED EXH. FAN
 FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  