| 2021-02-10 10:52:58 | 1ST REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 21020232 |
| | 2/10/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE REVIEW THE ENGINEER OF RECORD'S NOTE ON SHEET |
| | P.1 OF THE APPROVED RESTAURANT PLANS UNDER PERMIT |
| | 20071220. THE ENGINEER SPECIFIED THE CONTRACTOR SHALL |
| | SUBMIT A SEPARATE GAS PERMIT AND PLAN INCLUDING "AN |
| | ISOMETRIC DRAWING WITH PIPE SIZES, MATERIALS & LENGTHS, |
| | THE TYPE OF GAS, THE BTUH LOAD FOR EACH APPLIANCE, THE |
| | SIZING TABLES USED, & SPEC SHEETS/INSTALLATION MANUAL |
| | FOR THE GAS EQUIPMENT & APPLIANCES." THE SUBMITTED |
| | ISOMETRIC IS INCOMPLETE ACCORDING TO THE NOTE AND ALSO |
| | SECTION 401.3 & 401.4 FBC FG. |
| | |
| | 2) GAS RISER: |
| | A) SHOW THE TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM |
| | THE METER TO THE MOST REMOTE OUTLET, AND THE BRANCH |
| | PIPING LENGTHS TO EACH APPLIANCE- SECTION 402.4.1 & |
| | 402.4.2 FBC FG. |
| | B) SHOW THE TYPES OF PIPING USED IN THE SYSTEM- 403.1. |
| | C) SHOW THE DELIVERY PRESSURE AT THE METER AND PIPE |
| | SIZING TABLES USED FOR EACH TYPE OF PIPE IN THE SYSTEM- |
| | 402.2 & 402.3. |
| | D) SHOW THE BTUH LOAD OF THE WATER HEATER AND THE LOAD |
| | OF EACH COOKING APPLIANCE- 402.1. |
| | E) LABEL THE WATER HEATER AND COOKING APPLIANCES AS |
| | EITHER NEW OR EXISTING- SECTION 107.2.1 WPB. |
| | F) SHOW THE LOCATIONS OF APPLIANCE SHUT OFF VALVES- |
| | 409.5 |
| | G) SHOW THE LOCATIONS OF REGULATORS- 410.1 & 410.2 |
| | H) SHOW THE LOCATION OF THE AUTO SHUTOFF VALVE FOR THE |
| | GAS TO THE COOKING LINE- SEC.10.4.1 NFPA 96. |
| | |
| | 3) THE UNDERGROUND CSST IS PROHIBITED UNLESS IT IS |
| | ENCASED IN A CONDUIT OF WROUGHT IRON, PLASTIC OR STEEL |
| | PIPE, OR OTHER APPROVED MATERIALS- SECTION 404.14. |
| | PLEASE INDICATE THE GAS PIPE AND CONDUIT WILL BE BURIED |
| | A MINIMUM OF 12 INCHES BELOW GRADE, WILL BE PROTECTED |
| | FROM CORROSION- SECTIONS 404.11 & 404.12 FBC FG. |
| | |
| | 4) AS NOTED IN COMMENT #1 PLEASE SUBMIT SPECS FOR THE |
| | WATER HEATER AND THE COOKING APPLIANCES- SECTIONS 301.3 |
| | & 305.1 FBC FG. ALL APPLIANCES SHALL BE LISTED AND |
| | LABELED. LABEL THE HEATER AS EITHER STORAGE TANK OR |
| | TANKLESS ON THE RISER, AND PROVDE VENTING |
| | SPECIFICATIONS- SECTIONS 624.1 AND 503.1 FBC FG. |
| | |
| | 5) PROVIDE COMBUSTION AIR CALCULATIONS AND INDICATE HOW |
| | THE AIR WILL BE PROVIDED- SECTION 304.1 FBC FG. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | CCOLE@WPB |
| | |
| 2021-02-10 09:27:23 | THE SUBMITTTED GAS DRAWING IS SEVERELY DEFICIENT WITH |
| | REQUIRED INFORMATION. PLEASE SUBMIT THE FOLLWING |
| | INFORMATION: |
| | 1) |