| Date |
Text |
| 2021-04-08 13:50:07 | PLAN REVIEW FOR GAS WAS DONE UNDER 21020231. |
| | THE PLANS WERE MOVED FO A MASTER PERMIT 20121263, BUT |
| | THE COMMENTS FOR GAS REVIEW THAT WAS COMPLETED WERE NOT |
| | MOVED. |
| | THE PLANS GOT REVIEWED AS IF NEW AND THE PREVIOUS |
| | REVIEWER HAS WORKED OUT ITEMS ALREADY AND ALSO DID A |
| | SITE VISIT TO CLARIFY THE GAS THAT WAS INSTALLED PRIOR |
| | TO PERMIT. |
| | |
| | FOR THE 3RD REVIEW ATELYO WILL PASTE HIS COMMENTS INTO |
| | THE NOTES AND HE WILL DO FINAL REVIEW UPON RESUBMITTAL. |
| 2021-04-06 09:31:29 | 2ND REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 21020231 |
| | 4/6/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | COMMENTS PRINTED BELOW FROM THE 1ST REVIEW WERE NOT |
| | ADDRESSED AND THERE WAS NO NARRATIVE RESPONSE PROVIDED. |
| | PLEASE COMPLY WITH THE COMMENTS. BASED ON THE SCOPE OF |
| | WORK SHOWN ON THE PLANS THE $5500.00 VALUE FOR THE |
| | PROJECT APPEARS LOW. PLEASE PROVIDE COPIES OF CONTRACTS |
| | AND/OR COPIES OF ESTIMATES AND INVOICES FOR THE ENTIRE |
| | SCOPE OF WORK INCLUDING LABOR, MATERIAL, FIXTURES, |
| | APPLIANCES, EQUIPMENT, DESIGN FEES AND SITE WORK- |
| | SECTION 109.3 WPB. |
| | |
| | 1) GAS RISER: THE TOTAL 930,000 BTU LOAD IS INCORRECT. |
| | TOTAL LOAD SHOWN ON THE RISER INCLUDING THE FUTURE WH |
| | IS 1,130,000 BTU- SECTION 402.2 FBC FG. |
| | |
| | 2) GAS RISER: SHOW THE PIPE SIZING TABLE USED. THE LOW- |
| | PRESSURE TABLE 402.4(2) WITH A PRESSURE DROP OF 0.5 |
| | IN.WC SHOWS AN 1-1/2 IN. MAIN SUPPLY PIPE FROM THE |
| | METER IS UNDERSIZED FOR 1,130,000 GAS LOAD AT 41 FT. |
| | TOTAL LENGTH. |
| | |
| | 3) GAS RISER: SHOW REQUIRED REGULATORS AT EACH |
| | APPLIANCE CONNECTION TO DROP PRESSURE FROM 12 IN.WC- |
| | SECTION 410.1. |
| | |
| | 4) GAS RISER: SHOW THE AUTOMATIC SHUT OFF VALVE FOR THE |
| | COOKING LINE GAS SUPPLY- SECTION 10.4.1 NFPA 96. |
| | |
| | 5) A1: SHOW THE LOCATION OF THE NEW FUTURE WATER |
| | HEATER- SECTION 624.1 FBC FG. |
| | |
| | 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE COOKING |
| | APPLIANCE- SECTION 623.1 FBC FG. |
| | |
| | 7) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE COOKING |
| | APPLIANCES AND INDICATE HOW THE AIR WILL BE PROVIDED- |
| | SECTION 304.1 FBC FG. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | CCOLE@WPB |
| | |
| | |