| 2021-04-06 08:58:27 | RESTAURANT ALT. | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) ROOF TOP EQUIPMENT IS SUBJECT TO GRAVITY AND WIND | | | LOADS. FOR DRAWING S1- PLEASE PROVIDE STRUCTURAL | | | CALCULATIONS FOR SUCH OR SIGNED AND SEALED STRUCTURAL | | | MOUNTING DETAILS FROM AN ARCHITECT OR ENGINEER FBC | | | 1609. FBC EXISTING BUILDING 707.2ADDITION OR | | | REPLACEMENT OF ROOFING OR REPLACEMENT OF EQUIPMENT. | | | WHERE ADDITION OR REPLACEMENT OF ROOFING OR REPLACEMENT | | | OF EQUIPMENT RESULTS IN ADDITIONAL DEAD LOADS, | | | STRUCTURAL COMPONENTS SUPPORTING SUCH REROOFING OR | | | EQUIPMENT SHALL COMPLY WITH THE GRAVITY LOAD | | | REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING. | | | 2) FBC 1510.10 MECHANICAL UNITS. | | | ROOF MOUNTED MECHANICAL UNITS SHALL BE MOUNTED ON CURBS | | | RAISED A MINIMUM OF 8 INCHES (203 MM) ABOVE THE ROOF | | | SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH THE | | | UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM | | | CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE 1510.10. | | | | | | |
|