| 2021-02-25 15:18:50 | 1ST REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 21020231 |
| | 2/25/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS RISER: THE TOTAL 930,000 BTU LOAD IS INCORRECT. |
| | TOTAL LOAD SHOWN ON THE RISER INCLUDING THE FUTURE WH |
| | IS 1,130,000 BTU- SECTION 402.2 FBC FG. |
| | |
| | 2) GAS RISER: SHOW THE PIPE SIZING TABLE USED. THE LOW- |
| | PRESSURE TABLE 402.4(2) WITH A PRESSURE DROP OF 0.5 |
| | IN.WC SHOWS AN 1-1/2 IN. MAIN SUPPLY PIPE FROM THE |
| | METER IS UNDERSIZED FOR 1,130,000 GAS LOAD AT 41 FT. |
| | TOTAL LENGTH. |
| | |
| | 3) GAS RISER: SHOW REQUIRED REGULATORS AT EACH |
| | APPLIANCE CONNECTION TO DROP PRESSURE FROM 12 IN.WC- |
| | SECTION 410.1. |
| | |
| | 4) GAS RISER: SHOW THE AUTOMATIC SHUT OFF VALVE FOR THE |
| | COOKING LINE GAS SUPPLY- SECTION 10.4.1 NFPA 96. |
| | |
| | 5) A1: SHOW THE LOCATION OF THE NEW FUTURE WATER |
| | HEATER- SECTION 624.1 FBC FG. |
| | |
| | 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE COOKING |
| | APPLIANCE- SECTION 623.1 FBC FG. |
| | |
| | 7) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE COOKING |
| | APPLIANCES AND INDICATE HOW THE AIR WILL BE PROVIDED- |
| | SECTION 304.1 FBC FG. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | CCOLE@WPB |
| | |
| 2021-02-25 15:18:33 | 1ST REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 21020231 |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | PLAN REVIEW RESULTS: DENIED. |
| | 1) GAS RISER: THE TOTAL 930,000 BTU LOAD IS INCORRECT. |
| | TOTAL LOAD SHOWN ON THE RISER INCLUDING THE FUTURE WH |
| | IS 1,130,000 BTU- SECTION 402.2 FBC FG. |
| | 2) GAS RISER: SHOW THE PIPE SIZING TABLE USED. THE LOW- |
| | PRESSURE TABLE 402.4(2) WITH A PRESSURE DROP OF 0.5 |
| | IN.WC SHOWS AN 1-1/2 IN. MAIN SUPPLY PIPE FROM THE |
| | METER IS UNDERSIZED FOR 1,130,000 GAS LOAD AT 41 FT. |
| | TOTAL LENGTH. |
| | 3) GAS RISER: SHOW REQUIRED REGULATORS AT EACH |
| | APPLIANCE CONNECTION TO DROP PRESSURE FROM 12 IN.WC- |
| | SECTION 410.1. |
| | 4) GAS RISER: SHOW THE AUTOMATIC SHUT OFF VALVE FOR THE |
| | COOKING LINE GAS SUPPLY- SECTION 10.4.1 NFPA 96. |
| | 5) A1: SHOW THE LOCATION OF THE NEW FUTURE WATER |
| | HEATER- SECTION 624.1 FBC FG. |
| | 6) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE COOKING |
| | APPLIANCE- SECTION 623.1 FBC FG. |
| | 7) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE COOKING |
| | APPLIANCES AND INDICATE HOW THE AIR WILL BE PROVIDED- |
| | SECTION 304.1 FBC FG. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |