| 2021-02-25 08:59:38 | RESTAURANT ALT. |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENTS |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) CODE IN EFFECT CHANGED ON 1/1/2021 - PLEASE REVISE |
| | THE DRAWINGS SHOWING THE DESIGN PER THE CODE IN EFFECT |
| | (2020 FBC AND ASCE 7-16) |
| | 2) ROOF TOP EQUIPMENT IS SUBJECT TO GRAVITY AND WIND |
| | LOADS ? PLEASE PROVIDE STRUCTURAL CALCULATIONS FOR SUCH |
| | OR SIGNED AND SEALED STRUCTURAL MOUNTING DETAILS FROM |
| | AN ARCHITECT OR ENGINEER FBC 1609 ? FBC EXISTING |
| | BUILDING 707.2ADDITION OR REPLACEMENT OF ROOFING OR |
| | REPLACEMENT OF EQUIPMENT. |
| | WHERE ADDITION OR REPLACEMENT OF ROOFING OR REPLACEMENT |
| | OF EQUIPMENT RESULTS IN ADDITIONAL DEAD LOADS, |
| | STRUCTURAL COMPONENTS SUPPORTING SUCH REROOFING OR |
| | EQUIPMENT SHALL COMPLY WITH THE GRAVITY LOAD |
| | REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING. |
| | 3) PLEASE SHOW THE WIND DESIGN CRITERIA USED PER FBC |
| | 1603.1.4 |
| | 4) FBC 1510.10 MECHANICAL UNITS. |
| | ROOF MOUNTED MECHANICAL UNITS SHALL BE MOUNTED ON CURBS |
| | RAISED A MINIMUM OF 8 INCHES (203 MM) ABOVE THE ROOF |
| | SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH THE |
| | UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM |
| | CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE 1510.10. |
| | 5) A BUILDING PERMIT APPLICATION COMPLETED BY A |
| | CONTRACTOR LICENSED TO PERFORM THE STRUCTURAL WORK IS |
| | REQUIRED ? IF THE STRUCTURAL WORK IS ON A SEPARATE |
| | PERMIT PLEASE PROVIDE THE PERMIT NUMBER. |
| | |