| Notes |
| Date |
Text |
| 2021-08-31 15:07:01 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGE E-3.6.0 | | | | | | PANEL "H" UPGRADED TO 400 AMPS FROM 250 AMPS | | | ADDED LOADS OF TRASH COMPACTOR AND CAR CHARGERS | | | PANEL "MDP" ADDED SURGE PROTECTOR | | | PANEL LL UPGRADED TO 250 AMPS FROM 200 AMPS | | | ADDED LOADS OF ACCESS CONTROL, LANDSCAPE LIGHTING, CAR | | | CHAGERS, IRIGATION PUMPS | | | | | | NEED TO SUBMIT A NEW RISER DIAGRAM SHOWING NEW PANEL | | | AND WIRE SIZES. | | | | | | NEED TO INCLUDE VALUE OF THE ADDITIONAL WORK. | | | | | | NEED TO SUBMIT CUT SHEETS FOR THE CHARGERS. WHO MAKE IT | | | AND WHAT TYPE. |
|