2021-08-31 15:07:01ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-3.6.0
  
 PANEL "H" UPGRADED TO 400 AMPS FROM 250 AMPS
 ADDED LOADS OF TRASH COMPACTOR AND CAR CHARGERS
 PANEL "MDP" ADDED SURGE PROTECTOR
 PANEL LL UPGRADED TO 250 AMPS FROM 200 AMPS
 ADDED LOADS OF ACCESS CONTROL, LANDSCAPE LIGHTING, CAR
 CHAGERS, IRIGATION PUMPS
  
 NEED TO SUBMIT A NEW RISER DIAGRAM SHOWING NEW PANEL
 AND WIRE SIZES.
  
 NEED TO INCLUDE VALUE OF THE ADDITIONAL WORK.
  
 NEED TO SUBMIT CUT SHEETS FOR THE CHARGERS. WHO MAKE IT
 AND WHAT TYPE.