| Plan Review Notes For Permit 21020212 |
| Permit Number |
21020212 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-06-22 07:49:15 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | THIS IS NOT A REVISION TO THE SITE PLAN, THIS IS A | | | REVISION TO THE BUILDING PERMIT FOR EACH BUILDING | | | INVOLVED WITH THIS NEW PROJECT. PLEASE SUBMIT A | | | SEPARATE REVISION OR PERMIT FOR EACH BUILDING THAT IS | | | RECEIVING NEW CHARGERS. | | | | | | PLEASE SUBMIT CUT SHEETS FOR THE CHARGERS. 110.3 | | | | | | SUBMIT AN INDIVIDUAL SITE PLAN FOR EACH BUILDING | | | SHOWING WHERE THE CHARGERS AND TO BE PLACED. | | | | | | PAGE E2 WILL NOT OPEN ?? | | | | | | THIS PROJECT ALSO HAS A VALUE AND NO VALUE WAS ADDED TO | | | THIS REVISION. | | | | | | HOW MANY TOTAL CHARGERS ARE GOING TO BE INSTALLED? TWO | | | AT EACH BUILDING AND CLUB HOUSE? | | | | | | PLEASE SUBMIT A RISER DIAGRAM AND LOAD CALCULATION FOR | | | EACH BUILDING INVOVLED. | | | | | | SHOW EXACT LOCATION OF WHERE CHARGERS ARE TO BE | | | INSTALLED SHOW BOLLARDS IF REQUIRED. | | | | | | |
|