Plan Review Notes
Plan Review Notes For Permit 21020212
Permit Number 21020212
Review Stop E
Sequence Number 1
Notes
Date Text
2021-06-22 07:49:15ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 THIS IS NOT A REVISION TO THE SITE PLAN, THIS IS A
 REVISION TO THE BUILDING PERMIT FOR EACH BUILDING
 INVOLVED WITH THIS NEW PROJECT. PLEASE SUBMIT A
 SEPARATE REVISION OR PERMIT FOR EACH BUILDING THAT IS
 RECEIVING NEW CHARGERS.
  
 PLEASE SUBMIT CUT SHEETS FOR THE CHARGERS. 110.3
  
 SUBMIT AN INDIVIDUAL SITE PLAN FOR EACH BUILDING
 SHOWING WHERE THE CHARGERS AND TO BE PLACED.
  
 PAGE E2 WILL NOT OPEN ??
  
 THIS PROJECT ALSO HAS A VALUE AND NO VALUE WAS ADDED TO
 THIS REVISION.
  
 HOW MANY TOTAL CHARGERS ARE GOING TO BE INSTALLED? TWO
 AT EACH BUILDING AND CLUB HOUSE?
  
 PLEASE SUBMIT A RISER DIAGRAM AND LOAD CALCULATION FOR
 EACH BUILDING INVOVLED.
  
 SHOW EXACT LOCATION OF WHERE CHARGERS ARE TO BE
 INSTALLED SHOW BOLLARDS IF REQUIRED.
  
  