2021-08-21 06:47:305TH REVIEW FBC-2020 MECHANICAL
 PERMIT-21020172
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1 OF 2: THE DRYER DUCT PENETRATING THE RATED
 WALL MUST COMPLY WITH FBC M 504.2
  
 2) SHEET M1 OF 2: OUTDOOR AIR CALCULATIONS SHOW
 EXISTING BUSINESSES ON 1ST FLOOR AND ON THE 2ND FLOOR
 BUT THE SCOPE OF WORK SHOWN ON THE DRAWING INDICATES
 ONLY THE NEW VET BUSINESS. PLEASE CLARIFY. FBC 107.2.1
  
 3) THERE ARE 2 M1 OF 2 SHEETS ONE IS THE VET BUSINESS
 AND THE OTHER IS THE ROOF PLAN. IS THERE ANOTHER SHEET?
 THERE APPEARS TO BE MORE WORK ON THE A SHEETS. PLEASE
 CLARIFY. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  