Plan Review Notes
Plan Review Notes For Permit 21020172
Permit Number 21020172
Review Stop B
Sequence Number 5
Notes
Date Text
2021-08-24 09:57:24WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21020172
 ADD: 416 CLEMATIS ST.
 CONT: STUART M LEDIS LLC
 TEL: 561-718-7162
 E-MAIL: [email protected]
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
 3RD REVIEW / NEW DESIGN TEAM
 DATE: TUES. AUGUST 24, 2021
 ACTION: DENIED
  
 1) COMPLIED
  
 2A) (1) 3RD REVIEW, I SEE WHERE THE DESIGNER OF RECORD
 IS TRYING TO KEEP A OPEN MEZZANINE AS THE DESIGN
 PARAMETERS. THE CONCEPT OF THE OPEN MEZZANINE AND HOW
 THE AREAS WERE FIGURED IS MISLEADING. IN THE MEETING WE
 HAD I KEPT TRYING TO SHOW WHAT AREAS COULD BE USED IN
 ALLOWABLE FLOOR AREA, ALLOWABLE FLOOR AREA IS THAT AREA
 THAT ATMOSPHERICALLY COMMUNICATES. YOU USE THE FLOOR
 AREA ON THE 1ST FLOOR (GROUND FLOOR) WHICH THE DEMO
 SHEET SHOWS 1776.34 SQ. FT. THEN YOU DIVIDE THIS AREA
 BY 1/3 (2020 FBC-B 505.2.1) WHICH WILL GIVE YOU 592 SQ.
 FT. THE ALLOWABLE AREA FOR MEZZANINE. YOU ARE TAKING
 EXCEPTION # 2 FOR TYPE I, TYPE II CONSTRUCTION. THE
 1776 SQ. FT. / 2 = 888 SQ. FT. ALLOWABLE AREA FOR
 MEZZANINES. THE EXISTING MEZZANINE 405 SQ. FT. + 1305.8
 SQ. FT. NEW MEZZANINE = 1711 SQ. FT. (SHOWN ON THE D-1
 SHEET) OVER THE ALLOWABLE AREA. THE OTHER ISSUE WITH
 EXCEPTION # 2 IS THAT THIS BUILDING TYPE IS DECLARED AS
 TYPE VB CONSTRUCTION SPRINKLERED.
  
 2A)(2) PLEASE NOTE THE ATRIUM AREA IS THE ONLY WAY TO
 FIGURE THE 2ND STORY AREA OVER THE VETERINARY TENANT
 AREA. THE QUESTION IS WITH THE REMAINDER OF THE
 EXISTING MEZZANINE HOW WILL THIS AREA BE HANDLED WILL
 IT BE WALLED OFF TO THE ATRIUM OR A GLASS ENCLOSURE
 WITH A FIRE CURTAIN ON BOTH SIDES. 107.2.1.2
 2ND REVIEW, SAME COMMENT FOR THE NEW AREA OF THE 2ND
 STORY HOW THE NEW FLOOR AREA WILL BE SEPARATED FROM THE
 2-STORY HIGH ATRIUM, ONE HOUR SEPARATION IS REQUIRED.
 SINCE THERE IS TO BE NEW 2ND STORY AREA, THIS AREA NOW
 NEEDS SEPARATION FROM THE 2-STORY ATRIUM AREA (1 HOUR
 RATED WALLS OR GLASS WALL WITH A WATER CURTAIN BOTH
 SIDES AND GASKETED GLAZING). SHEETS A-1 & S-1. WITH THE
 NEW PARTIAL 2ND FLOOR EXPANSION THERE LEAVES AN AREA
 OPEN TO THE 2ND STORY, THIS IS ONLY ALLOWED WHEN IT IS
 A MEZZANINE. THE AREA IN QUESTION IS OVER 1/3RD OF THE
 FLOOR AREA THAT WAS OPEN AREA. THE COVERSHEET INDICATES
 THAT THIS BUILDING IS FIRE SPRINKLERED. THE OPEN AREA
 THAT IS NOW AN OPEN 2 STORY AREA WILL NOW NEED TO MEET
 THE REQUIREMENTS FOR A ATRIUM. SEE SECTION 404.6
 ENCLOSURES OF ATRIUMS AND EXCEPTIONS.
  
 2B) NEW COMMENT. CAF?/ MERCANTILE. PLEASE REVIEW
 SECTION 301.1 & 301.2 OF THE 2020 FBC-BUILDING CODE ON
 HOW TO CLASSIFY THIS OCCUPANCY AND OCCUPANT LOADS.
  
 2C) THE NEW FRONT DOOR # 2 INDICATES A SIDE APPROACH
 WHERE YOU HAVE SHOWN 48 INCHES OF WIDTH. THE 2020
 FBC-ACCESS. CODE SEE FIGURE 404.2.4.1(I) REQUIRES A
 MINIMUM OF 54 INCHES IN WIDTH TO BE ABLE TO MAKE THE
 TURN AND AN ADDITIONAL 24 INCHES FROM THE LATCH SIDE OF
 THE DOOR PARALLEL WITH THE DOOR.
  
 2D) THERE IS A NEW COUNTER IN THE NEW CORRIDOR 6 FEET
 LONG AT 34 INCHES IN HEIGHT THE PLANS DO NOT INDICATE
 IF THIS IS A WALL HUNG COUNTER AND OR IF IT HAS LEGS,
 SHOW COMPLIANCE WITH THE 2020 ACCESSIBILITY CODE
 SECTION PROTRUDING OBJECTS 307.2 PROTRUSION LIMITS
 307.2. OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES
 AND NOT MORE THAN 80 INCHES ABOVE THE FLOOR SHALL NOT
 PROTRUDE MORE THAN 4 INCHES HORIZONTALLY INTO THE
 CIRCULATION PATH.
  
 2E) THERE IS NO ACTUAL 2ND FLOOR PLAN FOR EGRESS, THE
 DEMO SHEET SHOWS A MEASUREMENT OF 70.7 FEET IN LENGTH =
 11.1 FEET ACROSS THE MEZZANINE AND AN ADDITIONAL 19
 FEET TO TWO MEANS OF EGRESS. PLEASE SHOW ON A LIFE
 SAFETY SHEET COMPLIANCE WITH COMMON PATH OF TRAVEL
 TABLE 1006.2.1 OF THE 2020 FBC-BUILDING CODE.
  
 3A) BUILDING PROVISO: SHEET S-1. PLEASE SHOW COMPLIANCE
 WITH: WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE
 WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED.
 REPORTS SUBMITTED TO BUILDING INSPECTOR AT TIME OF
 FRAMING INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN
 CONRAD AT 561-805-6666.
  
 3B) DEFERRED SUBMITTALS. COMPONENTS & CLADDING
 2020 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, CURBS, ROOF TOP
 VENTILATORS
  
  
 4-6) COMPLIED.
  
 7) SEE IMPACT REVIEW STOP. THE PLANS WILL NEED TO BE
 REVIEWED BY PALM BEACH COUNTY IMPACT FEE FOR THE
 INCREASE IN FLOOR AREA.
  
 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  