| 2021-07-20 15:43:25 | 4TH REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21020172 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE DRYER DUCT AND DRYER BOX ARE IN A RATED WALL, |
| | THIS DRYER BOX MUST BE FIRE RATED AND THE DUCT MUST BE |
| | PROTECTED FROM WHERE IT LEAVES THE DRYER BOX TO THE |
| | EXTERIOR TERMINATION LOCATION. FBC M 504.2 DUCTS THAT |
| | EXHAUST CLOTHES DRYERS SHALL NOT PENETRATE OR BE |
| | LOCATED WITHIN ANY FIRE BLOCKING, DRAFT STOPPING OR ANY |
| | WALL, FLOOR/CEILING OR OTHER ASSEMBLY REQUIRED BY THE |
| | FLORIDA BUILDING CODE, BUILDING TO BE FIRE-RESISTANCE |
| | RATED, UNLESS SUCH DUCT IS CONSTRUCTED OF GALVANIZED |
| | STEEL OR ALUMINUM OF THE THICKNESS SPECIFIED IN SECTION |
| | 603.4 AND THE FIRE-RESISTANCE RATING IS MAINTAINED IN |
| | ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING. |
| | FIRE DAMPERS, COMBINATION FIRE/SMOKE DAMPERS AND ANY |
| | SIMILAR DEVICES THAT WILL OBSTRUCT THE EXHAUST FLOW |
| | SHALL BE PROHIBITED IN CLOTHES DRYER EXHAUST DUCTS. |
| | |
| | 2) THE WALL AROUND THE AH-7 APPEARS TO BE RATED. PLEASE |
| | SHOW THE PROTECTION IN THIS WALL BY THE 8 INCH OUTDOOR |
| | AIR DUCT PENETRATION. FBC M 607 |
| | |
| | 3) PLEASE EXPLAIN THE CONDENSATE LINES RUNNING UP TO |
| | ROOF. IS THERE A CONDENSATE PUMP THAT IS NOT LISTED OR |
| | SHOWN ON THE DRAWINGS? |
| | |
| | 4) IT DOES NOT APPEAR THAT THIS IS A PET SHOP SO PLEASE |
| | PROVIDE THE CORRECT OCCUPANCY CLASSIFICATION. THIS NEW |
| | TENANT SPACE APPEARS TO BE A DR. OFFICE. IF IT WERE TO |
| | BE A PET SHOP YOU WOULD NEED TO PROVIDE 1,029 CFM OF |
| | EXHAUST IN THE ANIMAL AREAS. I DO NOT SEE AN ANIMAL |
| | AREA. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |