2021-07-19 11:57:07WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21020172
 ADD: 416 CLEMATIS ST.
 CONT: STUART M LEDIS LLC
 TEL: 561-718-7162
 E-MAIL: [email protected]
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
 2ND REVIEW / NEW DESIGN TEAM
 DATE: MON. JULY 19TH/2021
 ACTION: DENIED
 1) COMPLIED
  
 2) 2ND REVIEW, SAME COMMENT FOR THE NEW AREA OF THE 2ND
 STORY HOW THE NEW FLOOR AREA WILL BE SEPARATED FROM THE
 2-STORY HIGH ATRIUM, ONE HOUR SEPARATION IS REQUIRED.
 SINCE THERE IS TO BE NEW 2ND STORY AREA, THIS AREA NOW
 NEEDS SEPARATION FROM THE 2-STORY ATRIUM AREA (1 HOUR
 RATED WALLS OR GLASS WALL WITH A WATER CURTAIN BOTH
 SIDES AND GASKETED GLAZING). SHEETS A-1 & S-1. WITH THE
 NEW PARTIAL 2ND FLOOR EXPANSION THERE LEAVES AN AREA
 OPEN TO THE 2ND STORY, THIS IS ONLY ALLOWED WHEN IT IS
 A MEZZANINE. THE AREA IN QUESTION IS OVER 1/3RD OF THE
 FLOOR AREA THAT WAS OPEN AREA. THE COVERSHEET INDICATES
 THAT THIS BUILDING IS FIRE SPRINKLERED. THE OPEN AREA
 THAT IS NOW AN OPEN 2 STORY AREA WILL NOW NEED TO MEET
 THE REQUIREMENTS FOR A ATRIUM. SEE SECTION 404.6
 ENCLOSURES OF ATRIUMS AND EXCEPTIONS.
  
 3) BUILDING PROVISO: SHEET S-1. PLEASE SHOW COMPLIANCE
 WITH: WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE
 WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED.
 REPORTS SUBMITTED TO BUILDING INSPECTOR AT TIME OF
 FRAMING INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN
 CONRAD AT 561-805-6666.
  
 4-6) COMPLIED.
  
 7) SEE IMPACT REVIEW STOP. THE PLANS WILL NEED TO BE
 REVIEWED BY PALM BEACH COUNTY IMPACT FEE FOR THE
 INCREASE IN FLOOR AREA.
  
 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  