Plan Review Notes
Plan Review Notes For Permit 21020172
Permit Number 21020172
Review Stop P
Sequence Number 3
Notes
Date Text
2021-06-14 13:40:493RD REVIEW FBC-2020 PLUMBING
 PERMIT- 21020172
 6/14/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. NEW PLANS HAVE BEEN
 SUBMITTED. THE ORIGINAL PLANS THAT FAILED 1ST AND 2ND
 REVIEWS HAVE BEEN REMOVED FROM THE SETS.
 NEW COMMENTS.
  
 1) SHEETS A1 & D1: BOTH OF THESE SHEETS ARE LABELED IN
 THE MARGINS AS "LEVEL #2 INTERIOR REMODELING ONLY"
 HOWEVER THE A1 FLOOR PLAN INDICATES "NEW FIRST FLOOR
 PLAN" THE NEW FIRST FLOOR PLAN ALSO SHOWS MANY
 "EXISTING" ROOMS INCLUDING TWO UNISEX TOILET ROOM AND
 AN ACCESSIBLE DRINKING FOUNTAIN. THE ORIGINAL PLANS
 THAT WERE WITHDRAWN SHOW AN OPEN SPACE WHERE THE NEW
 PLANS INDICATE "EXISTING". I AM UNABLE TO LOCATE A
 PERMIT AND PLANS FOR THOSE ROOMS IN THE WPB DEPT.
 BUILDING RECORDS. PLEASE ADVISE OF THE PERMIT FOR THOSE
 ROOMS OR REVISE THE PLANS TO SHOW THEM AS "NEW"-
 SECTION 107.2.1 WPB.
  
 2) SHEETS P1 & P2: : BOTH OF THESE SHEETS ARE LABELED
 IN THE MARGINS AS "LEVEL #2 INTERIOR REMODELING ONLY"
 HOWEVER THE P1 FLOOR PLAN INDICATES "NEW FIRST FLOOR
 PLUMBING PLAN"- SECTION 107.2.1 WPB.
  
 3) A1. P1 & P2: THE PLANS APPEAR TO SHOW A MIXED
 OCCUPANCY OF OFFICES, PHARMACY, COFFEE/JUICE BAR, AND
 VETERINARY CLINIC- BUSINESS AND MERCANTILE OCCUPANCIES.
 PLEASE PROVIDE PLUMBING FIXTURE CALCULATIONS IN
 COMPLIANCE WITH TABLE 403.1 FBC P BASED ON THE OCCUPANT
 LOADS SHOWN. PROVIDE A SCHEDULE THAT INDICATES THE
 REQUIRED AND PROVIDED NUMBER OF PLUMBING FIXTURES.
 VERIFY THAT ALL TENANT OCCUPANTS WILL HAVE ACCESS TO
 THE FIXTURES.
  
 4) P1 & P2: A GREASE INTERCEPTOR IS REQUIRED FOR THE
 NEW COFFEE SHOP IN ACCORDANCE WITH SECTION 1003.3.1 FBC
 P. PLEASE REVISE THE PLAN: A) SHOW THE LOCATION OF THE
 INTERCEPTOR. B) PROVIDE AN EQUIPMENT SCHEDULE AND
 SIZING CALCULATIONS. C) PROVIDE NEW PLUMBING FLOOR PLAN
 AND ISOMETRIC DRAWING THAT INCORPORATE THE REQUIRED
 INTERCEPTOR. D) SUBMIT MANUFACTURER'S SPECIFICATIONS
 AND INSTALL GUIDELINES.
  
 5) P1 & P2: PROVIDE AN INTERCEPTOR FOR THE WASHING
 MACHINE IN ACCORDANCE WITH SECTION 1003.6 FBC P.
 CLOTHES WASHERS SHALL DISCHARGE THROUGH AN INTERCEPTOR
 THAT IS PROVIDED WITH A WIRE BASKET OR SIMILAR DEVICE,
 REMOVABLE FOR CLEANING, THAT PREVENTS PASSAGE INTO THE
 DRAINAGE SYSTEM OF SOLIDS 1/2 INCH OR LARGER IN SIZE,
 STRING, RAGS, BUTTONS OR OTHER MATERIALS DETRIMENTAL TO
 THE PUBLIC SEWAGE SYSTEM. LIST THE MAKE AND MODEL OF
 THE WASHING MACHINE AND INTERCEPTOR ON THE PLAN, AND
 SUBMIT MANUFACTURER?S SPECIFICATIONS, REVISE THE
 PLUMBING DRAWINGS.
  
 6) P1: THE SANITARY PIPING LAYOUT PLAN AND ISOMETRIC
 DRAWING DO NOT INCLUDE THE ?EXISTING? TOILET ROOMS,
 ?EXISTING? DRINKING FOUNTAINS. ?EXISTING? DOUBLE SINK
 IN THE PHARMACY- SECTION 107.2.1 & 107.3.5.3.1 FBC P.
 NOTE- NOT REQUIRED IF PROOF OF PERMIT AND INSPECTION
 CAN BE PROVIDED.
  
 7) P1: PROVIDE A NEW EAST WATER RISER THAT INCLUDES THE
 SUPPLY LINES TO THE "EXISTING" TOILET ROOMS, "EXISTING"
 DRINKING FOUNTAINS. "EXISTING" DOUBLE SINK IN THE
 PHARMACY, AND THE NEW COFFEE/JUICE BAR- SECTION 107.2.1
 & 107.3.5.3.1 FBC P. NOTE- NOT REQUIRED IF PROOF OF
 PERMIT AND INSPECTION CAN BE PROVIDED'
  
 8) P1: PROVIDE A NUMBERED EQUIPMENT PLAN AND
 CORRESPONDING NUMBER EQUIPMENT SCHEDULE FOR THE
 COFFEE/JUICE BAR- SECTION 107.2.1 WPB.
  
 9) P1: PROVIDE ENLARGED SANITARY AND WATER SUPPLY PLAN
 FOR THE COFFEE/JUICE BAR THAT SHOWS THE LOCATIONS OF
 ALL FLOOR SINKS, HUB DRAIN, AND FLOOR DRAINS NEEDED FOR
 BEVERAGE DISPENSER, ICE MAKER, WATER FILTER, AND
 REFRIGERATOR AND FREEZER EQUIPMENT DRAINAGE ETC. PLEASE
 SHOW THE LOCATIONS OF REQUIRED WATER HAMMER ARRESTORS
 AND BACKFLOW PREVENTERS FOR SUPPLY LINES TO THE
 EQUIPMENT- SECTION 604.9 & 608.3 FBC P.
  
 10) P1 & P2: PROVIDE AN ENLARGED INDIRECT WASTE DETAIL
 FOR THE 3-COMPARTMENT SINK- SECTION 802.1.1 FBC P.
  
 11) P1 & P2: THE NEW WEST WATER RISER SHOWS A WATER
 HEATER FOR THE WEST HOWEVER NO EAST RISER HAS BEEN
 PROVIDED TO SHOW REQUIRED HOT WATER BEING PROVIDED TO
 THE FIXTURES- SECTION 607.1 FBC P.
  
 12) P1 & P2: PLEASE PROVIDE EQUIPMENT SCHEDULES FOR THE
 WEST AND EAST WATER HEATERS AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS- SECTION 502.1 FBC P.
  
 13) P1 & P2: PROVIDE ENLARGED PIPING DRAWINGS FOR THE
 WATER HEATERS SHOWING LOCATIONS OF THERMAL EXPANSION
 TANKS, RECIRCULATION PUMPS, SHUTOFF VALVES, CHECK
 VALVES, RELIEF VALVE, ETC.- SECTIONS 502.1, 607.2.1.2,
 607.3 FBC P.
  
 14) P1 & P2: PROVIDE PANS AND PAN DRAINS FOR THE NEW
 WATER HEATERS. SHOW THE TYPE AND SIZE OF PANS, AND THE
 TYPE AND SIZE OF PAN DRAIN PIPES, THE DRAIN PIPE RUNS
 AND DISCHARGE LOCATIONS- SECTIONS 504.6- 504.7.2 FBC P.
  
 15) P1 & P2: LABEL THE LAVATORY IN THE WEST WATER
 RISER- SECTION 419.1 FBC P. REFER TO SECTION C404.5.1
 AND TABLE C404.5.1 FBC ENERGY CONSERVATION- THE RISER
 SHOWS THE LENGTH OF THE 1/2-INCH HOT WATER SUPPLY PIPE
 TO THE LAVATORY FROM THE WATER HEATER HAS EXCEED THE
 MAXIMUM ALLOWABLE LENGTH OF 2FT. EITHER A POINT OF USE
 WATER HEATER AT THE LAVATORY OR A RECIRCULATION PUMP
 FOR THE HOT WATER SYSTEM SHALL BE INSTALLED.
  
 16) P1 & P2: WHERE HOT WATER IS SUPPLIED TO A LAVATORY,
 THE WATER SHALL BE TEMPERED IN ACCORDANCE WITH SECTIONS
 419.5 & 607.1.2 FBC P. PLEASE PROVIDE A MIXING VALVE
 THAT CONFORMS TO ASSE 1070. PROVIDE A PIPING DETAIL ON
 THE PLAN FOR INSTALLATION. NOTE- NOT REQUIRED FOR THE
 EAST LAVATORIES IF PROOF OF PERMIT AND INSPECTION CAN
 BE PROVIDED.
  
 17) P1: LABEL THE LAVATORY IN THE WEST WATER RISER-
 SECTION 419.1 FBC P. IT IS INCORRECTLY LABELED AS H.S.
  
 18) P1: LABEL THE TWO FIXTURES ABOVE THE FLOOR DRAINS
 IN THE VET CLINIC, AND PROVIDE A PLUMBING FIXTURE
 SCHEDULE FOR THE VET CLINIC- SECTION 107.2.1 WPB.
 INDICATE HOW THE FLOOR DRAINS ARE VENTED IN THE RISER
 DRAWING- SECTION 901.2.1 FBC P.
  
 19) P1, P2, & A1: INDICATE THE TYPE OF FINISH WALL AND
 FLOOR MATERIALS TO BE INSTALLED IN THE NEW AND
 "EXISTING" TOILET ROOMS AND AT THE MOP SINKS IN THE VET
 CLINIC AND THE COFFEE/JUICE BAR- SEE SECTIONS 310.3 FBC
 P AND 1210.2. FBC B.
  
 20) P2: THE ACCESSIBILITY DETAILS FOR THE TOILET ROOMS
 APPEAR TO INCOMPLETE AND NOT CORRECT. PLEASE REFER TO
 FBC ACC AND PROVIDED ENLARGED DRAWINGS AND DETAILS
 SHOWING:
  
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
 C) TURNING SPACE DIAMETERS- SECTION 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SECTION 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOOR- SECTION 606.3.
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.
 I) LOCATION OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
 J) CENTERLINES OF THE TOILET PAPER DISPENSER MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2.
  
 21) P2: THE ACCESSIBLE DRINKING FOUNTAIN DETAILS ARE
 INCOMPLETE AND HAVE ILLEGIBLE PRINT. REFER TO SECTIONS
 306, 307, AND 602 FBC ACC AND PROVIDE DRINKING FOUNTAIN
 INSTALLATION DETAILS AND ELEVATION VIEWS SHOWING KNEE
 AND TOE CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS.
 SHOW THE REQUIRED 30 X 48 IN. CLEAR FLOOR SPACE FOR A
 FORWARD WHEELCHAIR APPROACH TO THE FOUNTAIN- SECTION
 602.2 FBC ACC, AND SHOW HOW THE LOCATIONS OF THE
 FOUNTAINS WILL BE IN COMPLIANCE WITH SECTION 307.2
 PROTRUSION LIMITS.
  
 22) P1 & P2: REFER TO SECTION 212.3 FBC ACC. SINKS AND
 INDICATE WHICH SINKS IN THE VET CLINIC AND PHARMACY
 WILL BE MADE ACCESSIBLE. PLEASE NOTE WHERE SINKS ARE
 PROVIDED, AT LEAST 5 PERCENT, BUT NO FEWER THAN ONE, OF
 EACH TYPE PROVIDED IN EACH ACCESSIBLE ROOM OR SPACE
 SHALL COMPLY WITH 606. SHOW THE CLEAR FLOOR SPACE
 DIAGRAM AND DIMENSION AT EACH ACCESSIBLE SINK ON THE
 FLOOR PLAN, AND PROVIDE AN ELEVATION DRAWING SHOWING
 SINK HEIGHT AND KNEE AND TOE CLEARANCES- SECTIONS 606.2
 & 606.3 FBC P.
  
 23) P2: REFER TO TABLE C403.2.10 FBC EC AND PROVIDE HOT
 WATER PIPE INSULATION SPECIFICATIONS.
  
 24) P2: PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1
 WPB.
  
 25) P1 & P2: CLARIFY WHAT TYPE OF PROCEDURES WILL TAKE
 PLACE IN THE VET CLINIC AND PROVIDE MEDICAL GAS PIPING
 DETAILS AND SPECIFICATIONS IF APPLICABLE- SECTION
 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  