| 2021-06-14 16:00:40 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21020172 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M1: PLEASE PROVIDE PENETRATION PROTECTION |
| | WHERE THE MECHANICAL DUCTS PENETRATE THE NEW RATED WALL |
| | THAT DIVIDES THE VETERINARY OFFICE FROM THE OTHER |
| | TENANT SPACE. FBC M 607 |
| | |
| | 2) PLEASE REPLACE THE 24 INCH FLEX DUCT FOR THE RETURN |
| | FOR NEW AHU-7 THAT IS RUNNING THROUGH THE RATED TENANT |
| | SEPARATION WALL. FBC M 607 |
| | |
| | 3) PLEASE SHOW THE CONDENSATION PIPING AND TERMINATION |
| | LOCATION FOR AHU-7. FBC M 307 |
| | |
| | 4) PLEASE SHOW THE NEW DRYER EXHAUST DUCT WORK AND |
| | TERMINATION LOCATION. FBC M 501.3 AND 504 |
| | |
| | 5) THE VETERINARY BUSINESS IS A NEW USE OF SPACE SO |
| | THEREFORE PLEASE BREAK DOWN THE OUTDOOR AIR |
| | CALCULATIONS PER USE OF SPACE. I.E. THE RECEPTION AREA |
| | WILL BE MORE CONCENTRATED THAN THE EXAM ROOMS. FBC M |
| | 403.3.1.1 AND TABLE 403.3.1.1 |
| | |
| | 6) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| | CALCULATIONS FOR THE NEW AHU-7. FBC EC 403.2.1 AND FBC |
| | M 312 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |