Plan Review Notes
Plan Review Notes For Permit 21020172
Permit Number 21020172
Review Stop M
Sequence Number 3
Notes
Date Text
2021-06-14 16:00:401ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21020172
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1: PLEASE PROVIDE PENETRATION PROTECTION
 WHERE THE MECHANICAL DUCTS PENETRATE THE NEW RATED WALL
 THAT DIVIDES THE VETERINARY OFFICE FROM THE OTHER
 TENANT SPACE. FBC M 607
  
 2) PLEASE REPLACE THE 24 INCH FLEX DUCT FOR THE RETURN
 FOR NEW AHU-7 THAT IS RUNNING THROUGH THE RATED TENANT
 SEPARATION WALL. FBC M 607
  
 3) PLEASE SHOW THE CONDENSATION PIPING AND TERMINATION
 LOCATION FOR AHU-7. FBC M 307
  
 4) PLEASE SHOW THE NEW DRYER EXHAUST DUCT WORK AND
 TERMINATION LOCATION. FBC M 501.3 AND 504
  
 5) THE VETERINARY BUSINESS IS A NEW USE OF SPACE SO
 THEREFORE PLEASE BREAK DOWN THE OUTDOOR AIR
 CALCULATIONS PER USE OF SPACE. I.E. THE RECEPTION AREA
 WILL BE MORE CONCENTRATED THAN THE EXAM ROOMS. FBC M
 403.3.1.1 AND TABLE 403.3.1.1
  
 6) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR THE NEW AHU-7. FBC EC 403.2.1 AND FBC
 M 312
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  