Plan Review Notes
Plan Review Notes For Permit 21020172
Permit Number 21020172
Review Stop P
Sequence Number 2
Notes
Date Text
2021-04-06 11:59:322ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21020172
 4/6/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
 FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW
 WITH NOTES ADDED IN CAP LETTERS FOR FURTHER
 CLARIFICATION.
  
 6) FAILED. P-1: PROVIDE A PLUMBING FIXTURE SCHEDULE
 INDICATING THE MAKES AND MODELS OF THE ACCESSIBLE
 TOILET FIXTURES AND FAUCET, SERVICE SINK, EXAM AND
 TREATMENT ROOM SINKS, WASHING MACHINE, HOSE BIB, FLOOR
 DRAINS, AND WATER HEATER- SECTION 107.2.1 WPB. THE EXAM
 AND SERVICE SINKS WERE NOT INCLUDED IN THE SCHEDULE.
 PLEASE NOTE THAT THE SPECS FOR THE SINKS MAY BE
 DEFERRED SUBMITTALS BY REQUEST. PLEASE LABEL THE
 SERVICE SINK ON THE PLAN. IT APPEARS TO BE LOCATED BY
 THE WASHING MACHINE.
  
 7) FAILED. P-1 & P-2: PROVIDE PLUMBING RISER DRAWINGS-
 SANITARY DRAIN AND VENT, AND WATER DISTRIBUTION-
 SECTION 107.3.5.1.3 WPB. PLEASE SHOW THE LOCATIONS OF
 THE REQUIRED SHUTOFF VALVES, WATER HAMMER ARRESTORS,
 AND BACKFLOW PREVENTERS ON THE WATER RISER- SECTIONS
 604.9, 606.1, 606.2, & 608.3 FBC P. THE SANITARY ISO IS
 SHOWING DOTTED LINES FOR DRAINS AND SOLID LINES FOR
 VENTS WHICH IS NOT IN ACCORDANCE WTHE LEGEND ON P1.
  
 10) FAILED. P-1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE
 WATER HEATER AND SUBMIT MANUFACTURER?S SPECIFICATIONS
 SHOWING THE MAKE, MODEL, GALLON SIZE, AND EFFICIENCY
 RATING- SECTION 502.1 FBC P AND TABLE C404.2 FBC EC.
 WATER HEATER SPECS NOT SUBMITTED BUT MAY BE DEFERRED BY
 REQUEST,
  
 13) FAILED. P-1 & P-2: PROVIDE AN EQUIPMENT SCHEDULE
 FOR THE NEW WASHING MACHINE INDICATING MAKE AND MODEL
 AND SUBMIT MANUFACTURER'S SPECIFICATIONS. WASHING
 MACHINE SPECS NOT SUBMITTED BUT MAY BE DEFERRED BY
 REQUEST,
  
 A) FAILED. 1003.6 CLOTHES WASHER DISCHARGE INTERCEPTOR.
 CLOTHES WASHERS SHALL DISCHARGE THROUGH AN INTERCEPTOR
 THAT IS PROVIDED WITH A WIRE BASKET OR SIMILAR DEVICE,
 REMOVABLE FOR CLEANING, THAT PREVENTS PASSAGE INTO THE
 DRAINAGE SYSTEM OF SOLIDS 1/2 INCH OR LARGER IN SIZE,
 STRING, RAGS, BUTTONS OR OTHER MATERIALS DETRIMENTAL TO
 THE PUBLIC SEWAGE SYSTEM. PLEASE SUBMIT SPECS FOR THE
 JR SMITH SOLIDS INTERECEPTOR SHOWN IN THE FIXTURE
 SCHEDULE TO VERIFY IT IS RECOMMENDED FOR WASHING
 MACHINE DRAINAGE. THE SPECIFIED UNIT IS DESIGNED FOR
 FLOOR MOUNTING. PLEASE PROVIDE AN ENLARGED PLUMBING
 PIPING INSTALLATION DETAIL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  