2021-02-18 14:18:061ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21020172
 2/18/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) T-1: THE PLUMBING FIXTURE CALCULATIONS ARE
 INDICATING DRINKING FOUNTAINS WILL BE PROVIDED. PLEASE
 SHOW THE FOUNTAIN LOCATIONS ON THE ARCHITECTURAL AND
 PLUMBING PLANS, AND PROVIDE PLUMBING PIPING DETAILS-
 SECTION 107.2.1 WPB. PLEASE NOTE THAT DRINKING
 FOUNTAINS ARE NOT REQUIRED FOR AN OCCUPANT LOAD OF 15
 OR FEWER- SECTION 410.2 FBC P. IF TO BE INSTALLED
 COMPLY WITH ITEMS A & B:
  
 A) IN ACCORDANCE WITH SECTION 211.2 FBC ACC- NO FEWER
 THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE
 DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6
 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.7.
  
 B) DRINKING FOUNTAIN ACCESSIBILITY: REFER TO SECTIONS
 306, 307, AND 602 FBC ACC AND PROVIDE DRINKING FOUNTAIN
 INSTALLATION DETAILS AND ELEVATION VIEWS SHOWING KNEE
 AND TOE CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS.
 SHOW THE REQUIRED 30 X 48 IN. CLEAR FLOOR SPACE FOR A
 FORWARD WHEELCHAIR APPROACH TO THE FOUNTAIN- SECTION
 602.2 FBC ACC, AND SHOW HOW THE LOCATIONS OF THE
 FOUNTAINS WILL BE IN COMPLIANCE WITH SECTION 307.2
 PROTRUSION LIMITS.
  
 2) A-4: PROVIDE AN ENLARGED TOILET ROOM DETAIL SHOWING
 THE LENGTH AND WIDTH OF THE ROOM, CLEAR FLOOR SPACE
 DIAGRAMS AND DIMENSIONS FOR THE WATER CLOSET AND
 LAVATORY, AND TURNING CIRCLE DIAMETER- SECTIONS 604.3,
 606.2, & 304.3 FBC ACC.
  
 3) A-4 PROVIDE REAR GRAB BAR INSTALLATION DETAILS AS
 SHOWN IN FIGURE 604.5.2, AND REAR GRAB BAR HEIGHT-
 SECTION 609.4 FBC ACC.
  
 4) A-4: SHOW THE CORRECT INSTALLATION HEIGHT OF THE
 MIRROR FROM THE FINISHED FLOOR TO THE REFLECTIVE
 SURFACE- 606.3 FBC ACC.
  
 5) ARCHITECTURAL PLANS: IN ACCORDANCE WITH SECTION
 212.3 FBC ACC, SINKS- WHERE SINKS ARE PROVIDED, AT
 LEAST 5 PERCENT, BUT NO FEWER THAN ONE, OF EACH TYPE
 PROVIDED IN EACH ACCESSIBLE ROOM OR SPACE SHALL COMPLY
 WITH 606. PLEASE SHOW THE LOCATIONS OF THE ACCESSIBLE
 EXAM ROOM AND TREATMENT AREA SINKS. SHOW THE CLEAR
 FLOOR SPACE DIAGRAM AND DIMENSION AT EACH ACCESSIBLE
 SINK LOCATION- SECTION 606.2; AND PROVIDE ELEVATION
 VIEWS SHOWING THE REQUIRED SINK HEIGHTS AND KNEE AND
 TOE CLEARANCES- SECTIONS 305, 306, AND 606.3 FBC ACC.
  
 6) P-1: PROVIDE A PLUMBING FIXTURE SCHEDULE INDICATING
 THE MAKES AND MODELS OF THE ACCESSIBLE TOILET FIXTURES
 AND FAUCET, SERVICE SINK, EXAM AND TREATMENT ROOM
 SINKS, WASHING MACHINE, HOSE BIB, FLOOR DRAINS, AND
 WATER HEATER- SECTION 107.2.1 WPB.
  
 7) P-1 & P-2: PROVIDE PLUMBING RISER DRAWINGS- SANITARY
 DRAIN AND VENT, AND WATER DISTRIBUTION- SECTION
 107.3.5.1.3 WPB. PLEASE SHOW THE LOCATIONS OF THE
 REQUIRED SHUTOFF VALVES, WATER HAMMER ARRESTORS, AND
 BACKFLOW PREVENTERS ON THE WATER RISER- SECTIONS 604.9,
 606.1, 606.2, & 608.3 FBC P.
  
 8) P-2: THE PLAN SHOWS HOT WATER SUPPLY TO THE LAVATORY
 SAINK. INDICATE HOW TEMPERED WATER WILL BE PROVIDED-
 SECTION 419.5 AND 607.1.2 FBC P.
  
 9) P-2: THE 1/2 IN. HW LINE TO THE LAVATORY IS
 EXCEEDING THE MAXIMUM LENGTH OF 2 FT. FROM THE NEAREST
 SOURCE OF HEATED WATER- TABLE C404.5.1 FBC EC. PLEASE
 NOTE: A RECIRCULATION PUMP FOR THE SYSTEM, OR A SECOND
 WATER HEATER WITHIN 2 FT. OF THE LAVATORY WILL HAVE TO
 BE INSTALLED IF HOT WATER IS TO BE SUPPLIED TO THE
 LAVATORY. SECTION 419.5 ALLOWS EITHER COLD OR TEMPERED
 WATER TO BE PROVIDED TO THE LAVATORY.
  
 10) P-1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE WATER
 HEATER AND SUBMIT MANUFACTURER?S SPECIFICATIONS SHOWING
 THE MAKE, MODEL, GALLON SIZE, AND EFFICIENCY RATING-
 SECTION 502.1 FBC P AND TABLE C404.2 FBC EC.
  
 11) P-1: PROVIDE A WATER HEATER INSTALLATION DETAIL
 SHOWING THE LOCATION OF THE REQUIRED EXPANSION TANK,
 SHUTOFF VALVE, CHECK VALVE, RELIEF VALVE, RELIEF VALVE
 PIPE, DRAIN PAN, AND DRAIN PAN LINE AND TERMINATION
 LOCATION- SEE SECTIONS 502, 503, & 504 FBC P.
  
 12) P-1 & P-2: PROVIDE TRAP SEAL PROTECTION FOR THE
 FLOOR DRAINS IN THE CAGES AND THE TREATMENT AREA
 SECTION 1002.4.1 FBC P.
  
 13) P-1 & P-2: PROVIDE AN EQUIPMENT SCHEDULE FOR THE
 NEW WASHING MACHINE INDICATING MAKE AND MODEL AND
 SUBMIT MANUFACTURER'S SPECIFICATIONS.
  
 A) 1003.6 CLOTHES WASHER DISCHARGE INTERCEPTOR. CLOTHES
 WASHERS SHALL DISCHARGE THROUGH AN INTERCEPTOR THAT IS
 PROVIDED WITH A WIRE BASKET OR SIMILAR DEVICE,
 REMOVABLE FOR CLEANING, THAT PREVENTS PASSAGE INTO THE
 DRAINAGE SYSTEM OF SOLIDS 1/2 INCH OR LARGER IN SIZE,
 STRING, RAGS, BUTTONS OR OTHER MATERIALS DETRIMENTAL TO
 THE PUBLIC SEWAGE SYSTEM.
  
 14) P-1 & P-2: INDICATE HOW DRAINAGE AND/OR
 CONDENSATION FROM THE FREEZER WILL BE DISPOSED OF-
 SECTION 314.2 FBC P.
  
 15) P-1 & P-2: PLEASE CLARIFY IF A MEDICAL GAS SYSTEM
 WILL BE INSTALLED FOR THE PURPOSE OF PERFORMING
 SURGERIES- SECTION 107.2.1 WPB. PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS IF APPLICABLE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  