| 2021-02-09 15:17:01 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21020172 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2020 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2020 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS BASED ON USE |
| | OF SPACE FROM TABLE 403.3.1.1. DO NOT USE ARCHITECTURAL |
| | OCCUPANT COUNT. PLEASE PICK THE OCCUPANCY |
| | CLASSIFICATION THAT BEST FITS THIS BUSINESS OCCUPANCY |
| | AND IDENTIFY ALL SPACES IN THIS BUILDING IN THE OUTDOOR |
| | AIR CALCULATIONS. FBC M 403.3.1.1, TABLE 403.3.1.1 |
| | |
| | 2) PLEASE SHOW THE FA-1 IN THE AIR BALANCE SCHEDULE. |
| | FBC 107.2.1 |
| | |
| | 3) PLEASE EXPLAIN THE USE OF THE FA-1, IS THE NEW |
| | MECHANICAL SYSTEM DESIGNED TO REMOVE THE HUMIDITY THIS |
| | FAN WILL BRING INTO THE BUILDING? |
| | |
| | 4) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING |
| | CALCULATION. FBC EC C403.2.1 |
| | |
| | 5) PLEASE SHOW THE CALCULATIONS FOR THE EXISTING |
| | MECHANICAL SYSTEMS SUPPLYING THE REQUIRED OUTDOOR AIR |
| | FOR THE ENTIRE AREA, SHOW UNIT SIZES. FBC M 403.3.1.1 |
| | |
| | 6) PLEASE IDENTIFY THE AHU AND THE ACU MENTIONED IN THE |
| | AIR BALANCE SCHEDULE. FBC 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |