2021-02-16 16:19:35CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1) SHEETS E-1 AND E-2: WILL NEW PANEL A SUPPLY ALL NEW
 AND EXISTING CIRCUITS? IT SEEMS THAT PANEL SCHEDULE
 SUBMITTED DOES NOT INCLUDE THE EXISTING CIRCUITS. FOR
 EXAMPLE, AN EXISTING A/C UNIT IS SHOWN ON POWER PLAN,
 BUT IT IS NOT SHOWN ON PANEL SCHEDULE. IF ONLY PANEL A
 WILL BE USED PLEASE INCLUDE ALL EXISTING CIRCUITS ON
 PANEL SCHEDULE AND CALCULATIONS AND IF THERE IS ANOTHER
 PANEL, PLEASE SHOW IT ON DRAWINGS AND SUBMIT PANEL
 SCHEDULE.
 2) PLEASE ADD NOTES/SPECIFICATIONS TO ELECTRICAL POWER
 AND LIGHTING SYSTEMS TO SHOW COMPLIANCE WITH SECTION
 C405, FBC, ENERGY CONSERVATION CODE 2020 EDITION.
 3) SHEET E-2 ? PLEASE MODIFY ELECTRICAL NOTE 1 TO
 CLEARLY SPECIFY COMPLIANCE WITH FBC 2020 7TH EDITION
 AND NEC 2017.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
  
 ENRIQUE QUINONEZ P.E.
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved